Skip to content

Screen parameters

eaxScadaReferenceStarterProEnterpriseView as Markdown

Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.

A screen’s parameters let one screen stand for many plant stations. How to use them: Reusable screens with parameters.

Written Is Replaced by
{Pump} a parameter its value, else its declared default; with neither it stays as written
{Pump|Plant/Processing/Pumps/P100} a parameter with a default in place its value, else Plant/Processing/Pumps/P100
{Plant/Processing/Mode} a tag reference (expressions) never replaced
{UDT.Speed}, { return 1 } not a screen parameter never replaced
  • A parameter name is a letter, then letters, digits or _, at most 32 characters. It has no /: anything with a / (that is not a parameter with a default) is a tag reference.
  • The default after | may hold /. It may not start with |, so {a||b} in an expression is not a parameter.
  • There is no logic: no conditions, loops or filters. A value is inserted as text, once; a value is never read as another parameter.

{Name} works in every text of a screen: tag paths of bindings and actions, expressions and conditions, interlocks, confirmation tags, input objects’ tag, minimum and maximum tags, alarm-object filters, trend pens, texts and the popup title. Scripts (a startup script, Run script) are not substituted: they read system.params.get('Name') and system.params.all(), which are read-only.

The server and the browser use one tokenizer, tested on the same corpus (web/testdata/screen_params_corpus.json).

Display Settings > Parameters, stored in the screen as screen_params.declared:

Field
name The parameter name.
description For the engineer.
type tagFolder (letters, digits, _ . - and /), text, or number.
required The screen does not open without a value (a default counts).
default The value when none is given.
allowed_values The only values accepted.
allowed_pattern The folders accepted: a tag path where * stands for part of one folder name (Plant/Processing/Pumps/*, Plant/Processing/Pumps/P1*), and a whole ** segment for one or more folders (Plant/Processing/**).

A declaration with a bad name, a duplicate, an unknown type, a bad pattern, or a default or allowed value with a wildcard is refused on save (400).

screen_params.sets: named value sets ({"name": "P-101", "values": {"Pump": "Plant/Processing/Pumps/P101", "Label": "Feed pump P-101"}}), edited in a grid with CSV import and export. CSV: a set column, an optional description, one column per declared parameter (comma, semicolon or tab separated).

The values a screen opens with are: the declared defaults, then the set, then the values given beside it.

From How
A Navigate or Open popup action Parameter set of the target screen (param_set) and / or Parameters (params, Name=value lines). A value may pass the current screen’s own {Name} down.
The runtime address /runtime/<screen>?set=P-101, /runtime?screen=<screen>&set=P-101, ?Pump=Plant/Processing/Pumps/P101
A script system.nav.navigate(target, params, {set}), system.nav.openPopup(screen, {set, params}), system.nav.loadInnerDisplay(screen, container, {set, params}), system.nav.swapInner(container, screen, {set, params})
A dock, an embedded (inner) screen It gets the page’s values for the parameters it declares (all of them when it declares none), plus its own.

A value:

  • has at most 256 characters, no wildcard (* # + >), no brace, no control character, no . or .. folder;
  • from the address or a script: only letters, digits, spaces and _ . - / : , (nothing that could become code in an expression or markup in a text).

On a screen that declares parameters:

  • an undeclared name, a missing required value, a value of the wrong type, and a value outside the allowed values or folders are refused;
  • an unknown set is refused.

A refused screen does not open. The runtime shows the reason and buttons for the screen’s sets. A popup does not open and the action reports why.

The write policy (confirmation, e-signature, limits, interlocks) of a screen that declares parameters is derived:

The parameter has The server enforces
a set each set’s expanded targets exactly, with that set’s interlock, confirmation and limit tags (sources marked param_set: "set P-101")
allowed values (every parameter of the screen) every combination of allowed values exactly (at most 256), and nothing else
allowed folders, or nothing besides the sets, the target as a pattern: {Name} matches the allowed folders (Plant/Processing/Pumps/[A-Za-z0-9_.-]*), or any text without them (lint param-target-unbounded)
  • For a tag a set writes, the same object’s pattern is left out: the set’s own interlock and confirmation tags decide, not the pattern’s unresolved {Pump}/Fault.
  • For a value in the allowed folders but in no set, the pattern applies: the button’s confirmation or signature is required. An interlock that uses {Name} is evaluated per value: the server reads the parameters from the tag path being written and fills them in (a write to Plant/Processing/Pumps/P107/Start checks Plant/Processing/Pumps/P107/Fault). A filled-in interlock tag that does not exist reads as a Bad value and refuses the write. A limit tag that uses {Name} refuses every write (fail closed). Define every station as a set.
  • A set its own declaration refuses is not derived (the runtime never opens it); it is listed as unresolved in the write-policy listing.
  • An interlock with a {...} that the command’s tag path cannot fill in (a parameter the tag path does not have, or a brace that is not a parameter) fails closed: the server refuses every write of the command, unless If the interlock reads a Bad value is Allow, where it never blocks. An expression interlock is filled in only when every value is a plain tag path; otherwise it is enforced on the screen only, and it never lets a value past another object’s interlock on the same tag. A button that writes an exact tag (Line/Start) with a {Pump} interlock is decided by the derived sets, each with its own filled-in interlock; the interlock of the screen as designed does not open them. The Studio badge is judged with the tags the object writes. The lint names each case (interlock-parameter, interlock-per-parameter). See Interlocks with a parameter.
  • POST /api/tags/write takes the screen a write is sent from: screen, param_set and params (all optional). The operator runtime sends them for every write from a screen or popup opened with parameter values. When screen is given, the write is refused with 403 {"status": "parameters_refused", "code": "WRITE_DENIED_SCREEN_PARAMETERS", "reason": ...}, journaled, when that screen does not exist or does not admit those values. A write without screen is checked as before. NATS commands and assistant setpoints carry no screen.
  • Preview with: none, a set, or custom values. Bindings and conditions use them; the resolved-tags grid lists each {Name} reference, its resolved tag and live value; Open in the runtime opens the screen with them.
  • An object whose binding uses a {Name} without a value shows a violet {Name} chip. A button whose target keeps an unresolved {Name} sends nothing.
  • Lint: param-undeclared, param-unused, param-set-missing-required, param-set-value-not-allowed, param-target-unbounded (see the lint rules).
  • Find where used on a tag lists the screens that reach it through a set. Find and replace (Look in: Tag path, a whole path) lists them too, as “through set P-101” rows that are never applied: change the value in the set.
  • New: screen parameter declarations and sets, the runtime address ?set=, and the per-set write-policy derivation.
  • A parameter name is now [A-Za-z][A-Za-z0-9_]{0,31}: a popup’s parameter named with a . or starting with _ is refused.
  • Navigation actions’ parameters are applied to the target page (before, they were stored and ignored).
  • {Name} inside a script is no longer replaced in popups.
  • A write target with {Name} on a screen that declares allowed folders is enforced as a pattern no wider than those folders; before, {TagRoot}/Start gated every .../Start tag of the plant.