Find references and the I/O map in eaxPLC
Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.
Before you change a variable, an output or a fieldbus mapping, you know every place in the program that reads or writes it, which fieldbus point each address is exchanged with, and (in eaxPLC Standard and Performance) whether an output is written from more than one place or more than one task.
Find references and the I/O map are in every edition, eaxPLC Free included. The checks are in eaxPLC Standard and Performance.
Before you start
Section titled “Before you start”- A program is deployed. The PLC’s compiler builds the cross-reference with every deploy and online change, from the program’s syntax tree (not a text search). Positions are those of the deployed program.
- Any signed-in Studio user can read the cross-reference and the I/O map.
Find the references of a variable
Section titled “Find the references of a variable”-
In the Structured Text editor, put the cursor on a variable name.
-
Press Shift+F12, or right-click and choose Find References.
-
The references panel opens under the editor. It lists:
- the declaration;
- the writes, marked
WRITE(a filled badge with a bar); - the reads, marked
READ(an outlined badge); - the calls of a function block instance, marked
CALL.
Each row shows the line and column, the POU, the context and the line of code, with the name highlighted.
-
Click a row (or press Enter on it) to jump to that line in the editor.
Put the cursor on the member of an instance (TON_1.Q) to list that member,
or on the instance (TON_1) to list the instance and all its members. A
variable located with AT and its address are the same storage: the
references of Motor AT %QX0.0 include the code that uses %QX0.0 directly.
If the editor holds changes that are not deployed, the panel says so: the line numbers are those of the deployed version.
What the contexts mean
Section titled “What the contexts mean”| Context | Access | Example |
|---|---|---|
| assignment | write | Motor := TRUE; |
| expression | read | Speed := Setpoint * 2; reads Setpoint |
| IF condition | read | IF StartPB THEN (and ELSIF) |
| CASE selector, CASE label | read | CASE Mode OF, a constant used as a label |
| WHILE condition, UNTIL condition | read | WHILE Sum < 100 DO, UNTIL Done |
| FOR variable | read and write | FOR i := ... (written and incremented) |
| FOR bound | read | the start, TO limit and BY step |
| function argument | read | LIMIT(0, Level, 100) |
| array index | read | Arr[i] reads i; writing Arr[i] is a write of Arr |
| block call | call | TON_1(...) |
| block input | write | TON_1(IN := x) writes TON_1.IN |
| block input value | read | TON_1(IN := x) reads x |
| block output (=>) | read / write | TON_1(Q => Done) reads TON_1.Q and writes Done |
| written by the block | write | when TON_1 runs it writes its outputs TON_1.Q and TON_1.ET |
| block in-out (by reference) | read and write | a VAR_IN_OUT parameter: what is passed may be read and written |
| initial value | write | Limit : INT := 10; |
A function block’s own outputs are written by the block when it is called:
the cross-reference records them as writes of the instance at the call
(written by the block). For a function block written in Structured Text,
only the outputs its body writes are recorded.
When the compiler cannot tell whether a reference reads or writes (a
VAR_IN_OUT parameter), it records both. A reference is never left out.
Open the Cross-ref view
Section titled “Open the Cross-ref view”Click Cross-ref in the view bar (or View > Cross-reference, I/O Map & Checks). It has three tabs.
Variables
Section titled “Variables”Every symbol of the program: variables, function block instances and their members, function block locals and direct addresses, with their type, address, number of writes and reads, POU and Unified Namespace path.
- Filter by name or address, and by kind.
- Double-click a row, or select it and press Enter or Shift+F12, to list its references in the editor.
I/O map
Section titled “I/O map”One row per %I, %Q and %M address of the program, plus every fieldbus
point the program does not use.
| Column | Shows |
|---|---|
| Address, Type, Bits | the address and the size of what is stored there |
| Variables | the variables located there (AT), and the address itself when the code uses it directly |
| Writes / reads | how many places write and read it |
| Bus, Device, Entry | the fieldbus, the device and the I/O entry ([n] for the nth element of an entry) |
| Bus point | Modbus TCP: the area and the 0-based coil or register number. EtherNet/IP: the assembly instance and the byte (and bit) offset. EtherCAT: the slave’s position and the byte (and bit) offset in its process data |
| Status | On a bus, No bus point (an input or output no bus point feeds or reads), Unused point (a bus point no address of the program uses), Memory (%M) |
Filter by text (address, variable, bus, device), by area and by status.
A bus that is switched off shows (off) after its name.
In a narrow window the I/O map starts with its secondary columns hidden, so the others fit: below 1440 pixels Bits, Writes / reads, Entry and Dir, below 1280 pixels also Type and Device. Columns, in the grid’s toolbar before CSV, shows them again (your choice wins over the window width and is remembered for this table; Reset goes back to the defaults). Address is pinned and always shown. CSV exports the columns shown.
Checks (eaxPLC Standard and Performance)
Section titled “Checks (eaxPLC Standard and Performance)”| Check | Severity | Finds |
|---|---|---|
| multiple-writers | warning | an output (%Q, or a variable located in %Q) written in more than one place. Writes through overlapping addresses (%QB1 and %QX1.3) count as the same output. The last write in the scan wins |
| multiple-tasks | error | an output written from more than one task: the program that writes it is called by two enabled tasks |
| unused-input | warning / info | an input (%I) the program never reads; information for a fieldbus input point that no address of the program covers |
| written-not-read | info | a variable written but never read. Outputs and function block outputs are not reported: the field or the caller reads them |
| read-not-written | info | a variable read but never written. Inputs, retained variables, function block inputs and variables that UNS commands or OPC UA clients may write (--uns-writable) are not reported. A variable only set by its initial value is reported with a hint to declare it CONSTANT |
| overlapping-addresses | warning / info | located variables that share memory (A AT %MW0 and B AT %MB1); information when the code uses an address that partly overlaps a located variable |
Every result has a severity, a message and its locations. Click a location to jump to it in the editor.
In eaxPLC Free the tab says the checks are available in eaxPLC Standard and Performance, with a link to Help > Licence. Find references and the I/O map keep working.
Use the API
Section titled “Use the API”The same data, for scripts and for eaxScada. Any signed-in user can read it
(GET only):
| Request | Returns |
|---|---|
GET /api/xref?offset=&limit=&q=&kind= |
the symbols, 500 per page by default (5000 at most); next_offset when there are more; q filters by name or address, kind by kind (variable, fb-instance, fb-member, fb-local, address) |
GET /api/xref/symbol?name=Motor |
one symbol with its members and aliases (404 if the deployed program has no such symbol) |
GET /api/io-map |
the I/O map rows and a summary |
GET /api/xref/checks |
the check results and their counts; 403 with available_in: ["Standard", "Performance"] in eaxPLC Free |
Each symbol carries its declaration (pou, file, line, col), its
references (access: read, write, readwrite or call; context;
via, the instance whose call made the reference) and, when the PLC
publishes to the Unified Namespace (--uns-prefix), uns.path and
uns.subject: the tag path it publishes as, and whether UNS commands may
write it.
Verify
Section titled “Verify”- Deploy a program with an output written twice, for example
Lamp := TRUE;and%QX0.1 := FALSE;withLamp AT %QX0.1 : BOOL;. - Put the cursor on
Lampand press Shift+F12: the panel lists both writes. - In eaxPLC Standard or Performance, the Checks tab reports
multiple-writersforLamp, %QX0.1with both lines.
Troubleshooting
Section titled “Troubleshooting”| Symptom | Cause | Fix |
|---|---|---|
| “is not a variable of the deployed program” | the name is a keyword, a literal, or a variable that is not deployed yet | deploy the program (F11), then search again |
| The jump lands on the wrong line | the editor holds changes that are not deployed (the panel says so) | deploy, or read the line numbers as those of the deployed version |
| “outside the editor” in the log | the reference is in a FUNCTION_BLOCK or before the program’s declarations, which the editor does not show | use the line and column shown in the row |
| The I/O map shows no bus | no fieldbus is configured on this PLC | configure it in the Fieldbus view |
| The Checks tab asks for a licence | the PLC runs eaxPLC Free | install a Standard or Performance licence (Help > Licence) |