Sparkline card
The current value over a small trend of the last minutes, filled from the historian when the card opens. Limit lines come from the tag’s alarm limits or from manual limits, dashed; a Bad value is marked, never drawn as good.

| Card palette | Display Widgets › Sparkline Mini-Trend |
| Card kind | sparkline (body.widget) |
| Default size | 3 × 2 grid cells |
Settings
Section titled “Settings”Double-click the card (or select it and press Enter) to open its settings. The settings are stored in the card’s body.params.
| Shown as | Key (body.params) |
Type | Unit | Default | Allowed values | What it does |
|---|---|---|---|---|---|---|
| Tag | tagPath |
Tag path (read) | — | The tag shown. A card without a tag shows its fixed value marked STATIC, or a dash. | ||
| Unit | unit |
Text | — | Unit shown after the value. Display only. | ||
| Decimals | decimals |
Number | — | Decimals shown. Empty: automatic from the range. | ||
| Window (minutes) | historyMinutes |
Number | 15 |
The time window, filled from the historian when the card opens. Default 15. Settings hint: Filled from the historian when the tile opens. | ||
| Limit lines | bandsSource |
Choice | — | alarmsmanualnone |
Where the dashed limit lines come from: the tag’s alarm limits, manual limits (card JSON), or none. |
Quality and parameters
Section titled “Quality and parameters”The card reads its tag live, with its quality: a Bad, Uncertain or stale value is dimmed and labelled BAD QUALITY, UNCERTAIN or NO LINK - STALE, and before a first value the card shows a dash and NO DATA, never an invented number. A tag the signed-in account may not read shows a dash, a padlock and NOT READABLE on a blue label (NO ACCESS on a small card), and no trend: the samples kept from before are not drawn either. A card on a screen with parameters takes {Name} in its tag paths.
Examples
Section titled “Examples”Air pressure with its alarm limit line
Section titled “Air pressure with its alarm limit line”The compressed-air pressure over the last minute; its LOW alarm at 5 bar is drawn as a dashed line.
- Click Sparkline Mini-Trend in the dashboard palette.
- Double-click it: Tag
Plant/Processing/Utilities/Air/Pressure, Unitbar, Decimals 2, Window 1, Limit linesalarms.