Skip to content

Run an edge runtime next to eaxScada

eaxPLCHow-to guideFreeProView as Markdown

Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.

eaxplc-rt.exe is the eaxPLC runtime without the Web Studio, for edge devices. It runs the project, its I/O and UNS publishing, and is driven over NATS: eaxScada works with it through its broker, and the Studio attaches to it from any machine with plc-server --attach.

Network topologyAn edge runtime, the eaxScada broker and an attached Web Studio
An edge runtime, the eaxScada broker and an attached Web StudioThe edge device runs eaxplc-rt with its fieldbus I/O and no HTTP listener. It connects out to the NATS broker on the eaxScada host with its own NKey identity, which may use only its own subjects, publish UNS telemetry and receive UNS commands. eaxScada is the sign-in and e-signature authority and raises an alarm when the PLC stops on a fault. An engineer runs plc-server --attach on another machine: it serves the Web Studio locally and carries every call to the runtime through the broker.TRUST BOUNDARY · EDGE DEVICETRUST BOUNDARY · EAXSCADA HOSTTRUST BOUNDARY · ENGINEER'S MACHINEeaxplc-rtruns the project;no HTTP listener;NKey <id>.nkField devicesover its fieldbusesNATS brokerport 4222;a PLC identity usesits own subjectseaxScada--edge-plcs <id>;sign-in ande-signatures;ALM-PLC-<ID>-FAULTplc-server --attachthe Web Studio,served here; no PLCruns in itEngineera browsertelemetry,repliesCMDAPI calls,UNS commandssign-in and e-signature authorityevery /api/ call,live valuesStudioinputsCMDoutputs
Nothing listens on the edge device: every request reaches it through the broker, and is checked there like an HTTP request.
  • Product
  • Service or process
  • Field equipment
  • Person or role
  • Trust boundary
  • Data or telemetry
  • Command to equipment
  • Authentication
Read as text

The edge device runs eaxplc-rt with its fieldbus I/O and no HTTP listener. It connects out to the NATS broker on the eaxScada host with its own NKey identity, which may use only its own subjects, publish UNS telemetry and receive UNS commands. eaxScada is the sign-in and e-signature authority and raises an alarm when the PLC stops on a fault. An engineer runs plc-server --attach on another machine: it serves the Web Studio locally and carries every call to the runtime through the broker.

Parts

  • Edge device (trust boundary)
  • eaxScada host (trust boundary)
  • Engineer's machine (trust boundary)
  • eaxplc-rt (product, inside Edge device): runs the project; no HTTP listener; NKey <id>.nk
  • Field devices (field equipment, inside Edge device): over its fieldbuses
  • NATS broker (service or process, inside eaxScada host): port 4222; a PLC identity uses its own subjects
  • eaxScada (product, inside eaxScada host): --edge-plcs <id>; sign-in and e-signatures; ALM-PLC-<ID>-FAULT
  • plc-server --attach (service or process, inside Engineer's machine): the Web Studio, served here; no PLC runs in it
  • Engineer (person or role, inside Engineer's machine): a browser

Connections

  • eaxplc-rt → NATS broker (data or telemetry): telemetry, replies. Opened by the runtime, outbound. It publishes on plc.<id>.> and UNS telemetry.
  • NATS broker → eaxplc-rt (command to equipment): API calls, UNS commands. On plc.<id>.> and uns.command.>. Each request is checked like an HTTP request: the user's credential, the permission level, the e-signature, and the audit records the user.
  • eaxScada → NATS broker (relation)
  • eaxScada → eaxplc-rt (authentication): sign-in and e-signature authority. With --scada-url, users sign in with their eaxScada accounts and e-sign there; the runtime trusts eaxScada's token key, fetched once and pinned. With --standalone the runtime's own local users are the authority instead.
  • plc-server --attach ↔ NATS broker (data or telemetry): every /api/ call, live values. Over plc.<id>.api, with the browser's credential: the runtime signs in, checks and audits.
  • Engineer ↔ plc-server --attach (data or telemetry): Studio
  • Field devices → eaxplc-rt (data or telemetry): inputs
  • eaxplc-rt → Field devices (command to equipment): outputs

Start eaxScada with the edge PLC ids (comma separated):

eaxscada-<tier>.exe ... --edge-plcs edge-7,edge-8

On start eaxScada creates each PLC’s broker identity, data\security\nkeys\<id>.nk, and a built-in critical alarm ALM-PLC-<ID>-FAULT that turns on when that PLC stops on a fault (watchdog or scan fault). With HA, provision the seeds once and give both nodes --edge-plc-seed-dir <dir>.

Copy <id>.nk to the edge device (it is the device’s credential: keep it readable by the runtime’s account only).

eaxplc-rt.exe --plc-id edge-7 --nats nats://<scada-host>:4222 --nats-nkey edge-7.nk ^
--scada-url http://<scada-host>:8080 --no-http --no-modbus --cpu eaxCPU-500
  • --nats-nkey: the identity from step 1. The broker lets it use its own subjects only (plc.edge-7.>), publish UNS telemetry and receive UNS commands.
  • --scada-url: users sign in with their eaxScada accounts, and deploys and watchdog changes are e-signed there. Forcing needs the plc.force right (Lead_Engineer, Administrator; never the AI co-pilot) and no e-signature; every force is audited. Writing a value once needs the plc.write right (Shift_Operator and above), see step 4. --standalone instead uses the runtime’s own local users (eaxplc-rt user add ...).
  • --no-http: nothing listens on the device; everything goes through the broker. Leave HTTP on (loopback by default) only if something local needs it.
  • --no-modbus, or -modbus-bind to expose Modbus TCP (it has no authentication).

Every request over NATS is checked like an HTTP request: the user’s credential, the permission level, the e-signature, and the audit records the user.

The runtime has no Windows service mode yet: run it at boot with Task Scheduler (“At startup”, “Run whether user is logged on or not”) or a service wrapper.

Soft real-time on Windows IoT Enterprise: see rt\Enable-SoftRealTime.ps1.

From any machine that reaches the broker:

plc-server.exe --attach edge-7 --nats nats://<scada-host>:4222 ^
--nats-user <scada user> --nats-pass <password> -http 8086

then open http://127.0.0.1:8086. This runs the Web Studio only (no PLC): sign in with your eaxScada account; online values, deploys, forces and the flight recorder are the edge runtime’s. --nats-nkey <file> can be used instead of a user and password.

In eaxScada, the PLC flight recorder and PLC hardware views have a PLC selector listing the local PLC and the edge PLCs.

The Studio’s watch grid has two different actions on a value. Pick the one you mean:

Write once Force
What happens The value lands once, at the next scan. The program may overwrite it on any later scan. The value is held on every scan until someone unforces it, whatever the field or the program writes.
Who may do it plc.write right: Shift_Operator, Process_Supervisor, Lead_Engineer, Administrator plc.force right: Lead_Engineer, Administrator
Studio Write once on a row, or Write Recipe once for every Recipe Preset Force, Change force, Unforce, Release Forces
API POST /api/write POST /api/force
Audit IO_WRITE / WRITE, WRITE_DENIED, WRITE_REJECTED IO_FORCE / FORCE, UNFORCE, …

Neither action needs an e-signature. The AI co-pilot can do neither, even when its account has an engineer role. The PLC refuses a caller without the right (403) and records the refusal (WRITE_DENIED, FORCE_DENIED).

A write request carries one or more values and is applied all or none:

POST /api/write
{"writes": [{"address": "%MW10", "value": 1200},
{"symbol": "Mixer_Speed", "value": 42.5},
{"symbol": "Agitator_On", "value": true}],
"reason": "recipe B", "source": "IDE"}
  • A value is a direct address (%QX0.1, %MW10) or a variable of the running program (BOOL, integer, REAL, LREAL).
  • The PLC checks every entry before it writes anything: the address must lie in the process image, the value must fit the type, the variable must exist, and no two entries may share a location. A request holds 1 to 256 entries. If one entry fails, the PLC writes nothing and refuses the request with 400, naming the entry (write N of M: ...). A body that is not valid JSON, or not a write request, is also a 400.
  • If a location is forced, the PLC refuses the whole request with 409 and names the force (who forced it, the value and since when). A write would not hold against a force, so the PLC does not accept it silently. Unforce first, or change the forced value.
  • The ledger gets one IO_WRITE / WRITE record per value, all with the same request id. Each record holds the user and roles, the address and symbol, the live value before the write, the new value, the reason and the source (HTTP or NATS, plus the client’s source tag).
  • The ledger records refusals too:
    • 403 (no plc.write right) and 409 (forced location): one WRITE_DENIED record per requested value.
    • 400 (invalid request): one WRITE_REJECTED record per request, because nothing was written. The record holds the user and roles, the source, a request id, the failing entry and why it failed (write N of M: ...), and the address or symbol and value as the client sent them. For a body that does not parse, the record holds the parse error and the first 256 bytes of the body, escaped. Long fields are truncated, so a record stays under 4 KB.

Over NATS, plc.<id>.api with path /api/write follows the same rules.