Skip to content

Fieldbus configuration

eaxPLCReferenceFreeView as Markdown

The fieldbus configuration: buses (masters and scanners), their devices and the process-image I/O entries.

Keys are the JSON keys. Optional marks keys that are omitted when empty, or that may be absent (pointers).

Config is the whole fieldbus configuration.

Source: eaxPLC/pkg/fieldbus/config.go

Key Type Optional Description
version integer
buses list of Bus

Bus is one master/scanner and its devices.

Source: eaxPLC/pkg/fieldbus/config.go

Key Type Optional Description
id string
name string yes
type string
enabled boolean
local_ip string yes LocalIP: the network interface to use (EtherNet/IP binds its I/O port 2222 there; empty: all interfaces / the system’s choice).
interface string yes EtherCAT: the network interface dedicated to the line (e.g. eth1) and the cycle time (default 1000 us).
cycle_us integer yes
bit_rate integer yes CANopen: Interface is the CAN port (can0: SocketCAN on Linux; slcan:COM5, slcan:/dev/ttyACM0, slcan:tcp://host:port: an SLCAN adapter or a serial device server; sim: virtual nodes in the runtime), the bit rate (default 500000), the SYNC period (default 10000 us) and the master’s node id (0: none; 1..127: no node may use it, and the master produces its heartbeat every master_heartbeat_ms, default 100, for the nodes’ heartbeat consumers).
sync_us integer yes
master_node_id integer yes
master_heartbeat_ms integer yes
brokers list of string yes Brokers: tcp://, ssl:// (tls://, mqtts://), ws:// or wss:// URLs, tried in order; no user or password in a URL. A plaintext URL to anything but this computer is refused unless allow_plaintext, with a reason (the e-signed change carries it): on plaintext anyone on the path can inject PLC inputs.
client_id string yes empty: eaxPLC-<plc id>-in
username string yes
ca_pem string yes
cert_pem string yes
keepalive_sec integer yes default 5 (2..60)
allow_plaintext boolean yes
plaintext_reason string yes
bus_max_msgs_per_sec integer yes Limits of the whole connection: messages per second (default 10000), the size of one payload (default 256 KiB) and the metrics of one Sparkplug payload (default 10000). Over them, messages are dropped and counted.
max_payload_bytes integer yes
max_metrics integer yes
devices list of Device

Device is one field device (Modbus server, EtherNet/IP adapter).

Source: eaxPLC/pkg/fieldbus/config.go

Key Type Optional Description
id string
name string yes
enabled boolean
host string
port integer yes 502 / 44818 when 0
unit_id integer yes Modbus TCP
poll_ms integer yes cycle time, default 100
timeout_ms integer yes per request, default 1000
rpi_ms number yes EtherNet/IP (Class 1)
connection string yes exclusive_owner (default) | input_only | listen_only
config_instance integer yes
input_instance integer yes T->O (produced by the adapter)
output_instance integer yes O->T (or the heartbeat instance)
input_size integer yes bytes, without the sequence count
output_size integer yes bytes, without sequence count and run/idle header
config_data string yes hex, sent with the Forward Open
slot integer yes backplane slot (routes 1,<slot>); -1: no route
timeout_multiplier integer yes
multicast boolean yes T->O multicast (default point-to-point)
position integer yes EtherCAT: the slave’s place in the line (1 = next to the master), the identity it must have (0: not checked); input_size / output_size are its process data bytes (from a bus scan).
vendor_id integer yes
product_code integer yes
node_id integer yes CANopen: the node id; the identity it must have (vendor_id, product_code and revision, object 0x1018; 0: not checked); its heartbeat producer time (written to 0x1017, default 100 ms) and the consumer time after which the master declares it lost (default 3 x the producer time); how long the master waits for its boot-up message (default 5000 ms); its PDOs and the SDO writes of its boot sequence. input_size / output_size are derived from the TPDOs / RPDOs. The identity is checked on the other buses too: EtherCAT against the slave’s SII (the revision per revision_check), EtherNet/IP as the Forward Open’s electronic key (per electronic_key; revision is major*256 + minor there).
revision integer yes
heartbeat_ms integer yes
heartbeat_timeout_ms integer yes
boot_timeout_ms integer yes
pdos list of PDO yes
boot_sdos list of SDOWrite yes
revision_check string yes RevisionCheck (EtherCAT, CANopen): off | min (the device’s revision is at least the configured one: a newer device replacing an older one starts) | equal. Unset: off without a revision, min with one.
electronic_key string yes ElectronicKey (EtherNet/IP): off (no key: any adapter answers) | compatible (vendor and product must match; a compatible newer revision is accepted) | exact (the revision too). Unset: compatible when vendor_id or product_code is set, else off.
descriptor Descriptor yes Descriptor: the device description file imported for this device (identity, object dictionary or assemblies, process data), as parsed.
inputs_on_fault string yes Behaviour
outputs_on_stop string yes EtherNet/IP: idle (default) | zero; Modbus: hold (default) | zero; EtherCAT: zero (default) | hold; CANopen: preop (default) | zero
status_address string yes optional %IX bit: TRUE while the device exchanges data
source string yes sparkplug | json
group_id string yes Sparkplug B: the edge node (and one of its devices).
edge_node_id string yes
device_id string yes
request_rebirth boolean yes RequestRebirth (D4, off by default): after a sequence gap or a value before any birth, send the node one “Node Control/Rebirth” command, at most once per 30 s, logged.
topic_root string yes JSON: entries’ topics are below TopicRoot. TimestampUnit of the payloads’ “timestamp” (ns, ms or s: never guessed); EaxPLCJSON: the source is an eaxPLC publisher (ns). OnlineTopic: a topic saying whether the source is alive (false or 0: every entry comm failure).
timestamp_unit string yes
eaxplc_json boolean yes
online_topic string yes
max_age_ms integer yes Defaults of the entries: max_age_ms (JSON: max_age_ms or online_topic is required; Sparkplug: 0, off), on_bad (hold).
on_bad string yes
max_source_age_ms integer yes MaxSourceAgeMs: an update whose own timestamp is older than this on arrival is history only (Stale, 68); 0: off.
max_msgs_per_sec integer yes MaxMsgsPerSec: this source’s messages per second (default 1000).
io list of IOEntry

PDO is one CANopen process data object of a node: a TPDO (the node transmits; its data goes to %I) or an RPDO (the node receives; its data comes from %Q), with its communication parameters and its mapping.

A node’s input image is its TPDOs’ data one after the other, in the order configured, each taking its whole bytes; the output image is its RPDOs’ data the same way. I/O entries address these images by byte_offset / bit, like an EtherCAT slave’s process data.

Source: eaxPLC/pkg/fieldbus/canopen_config.go

Key Type Optional Description
direction string tpdo | rpdo
number integer 1..512 (communication object 0x1800/0x1400 + number - 1)
cob_id integer yes COBID: 0 is the predefined connection set (PDO 1..4 only): TPDO 0x180/0x280/0x380/0x480 + node id, RPDO 0x200/0x300/0x400/0x500 + node id.
transmission_type integer TransmissionType: 0 acyclic synchronous, 1..240 every n-th SYNC, 254 / 255 event-driven (manufacturer / device profile).
event_timer_ms integer yes TPDO 254/255: also sent every period
entries list of PDOMapEntry

SDOWrite is one SDO download of a node’s boot sequence (written after its PDOs, before its heartbeat time and NMT start).

Source: eaxPLC/pkg/fieldbus/canopen_config.go

Key Type Optional Description
index integer
sub integer
data_type string BOOLEAN, INTEGER8..64, UNSIGNED8..64, REAL32, REAL64, VISIBLE_STRING, OCTET_STRING (hex)
value string
name string yes

Descriptor is an imported device description, as parsed: what the configurator and the identity check need, not the whole file.

Source: eaxPLC/pkg/fieldbus/descriptor.go

Key Type Optional Description
format string
file_name string yes
sha256 string
identity DescriptorIdentity
objects list of ODObject yes CANopen: the object dictionary’s identity, PDO and mappable objects; the PDOs and boot SDOs a DCF / XDC configures (an EDS / XDD: its default PDO mapping); the node id and bit rate of a DCF / XDC.
pdos list of PDO yes
boot_sdos list of SDOWrite yes
node_id integer yes
bit_rate integer yes
heartbeat_ms integer yes DCF / XDC: 0x1017 as configured
ethercat_pdos list of ECATPDO yes EtherCAT: the PDOs (RxPDO outputs, TxPDO inputs) with their entries, the default assignment’s process data sizes, and the CoE init commands (written at PS: information, the master does not run them yet).
init_commands list of ECATInitCmd yes
assemblies list of EIPAssembly yes EtherNet/IP: the assemblies and the connections the EDS declares.
connections list of EIPConnection yes
input_size integer yes Process data bytes (EtherCAT: the default PDOs; EtherNet/IP: the first exclusive owner connection).
output_size integer yes
registers list of IOEntry yes Modbus register map: the I/O entries (without PLC addresses).
warnings list of string yes Warnings: what was read but is not used, or was skipped.

IOEntry maps a range of a device’s process data to the PLC.

Source: eaxPLC/pkg/fieldbus/config.go

Key Type Optional Description
id string
name string yes
direction string in (device -> %I) | out (%Q -> device)
area string yes Modbus: coil | discrete_input | holding_register | input_register, 0-based address
address integer yes
byte_offset integer yes EtherNet/IP: offset in the assembly (and bit, for BOOL)
bit integer yes
data_type string BOOL SINT USINT BYTE INT UINT WORD DINT UDINT DWORD REAL
count integer yes elements, default 1
word_order string yes Modbus 32-bit: ABCD (default, high word first) | CDAB
plc_address string first element: %IX0.0, %IW4, %QD8 …
metric string yes Sparkplug: the metric name
topic string yes JSON: below the source’s topic_root
quality_address string yes The entry’s quality outputs, in %I: quality_address (%IX, TRUE only while Good: Uncertain and Stale are FALSE), status_address (%IB, the quality code), timestamp_address (%IL, the source’s timestamp in Unix ms), age_address (%ID, ms since the last accepted update).
status_address string yes
timestamp_address string yes
age_address string yes
on_bad string yes
substitute string yes a literal of the entry’s type
max_age_ms integer yes nil: the source’s

PDOMapEntry is one object mapped into a PDO (index, sub-index, length).

Source: eaxPLC/pkg/fieldbus/canopen_config.go

Key Type Optional Description
index integer
sub integer
bits integer
name string yes
data_type string yes the object’s CANopen data type (information)

DescriptorIdentity is who the device is.

Source: eaxPLC/pkg/fieldbus/descriptor.go

Key Type Optional Description
vendor_id integer yes
vendor_name string yes
product_code integer yes
product_name string yes
revision integer yes
order_code string yes
device_type integer yes CANopen 0x1000, EtherNet/IP product type

ODObject is a CANopen object dictionary entry.

Source: eaxPLC/pkg/fieldbus/descriptor.go

Key Type Optional Description
index integer
sub integer
name string
data_type string BOOLEAN, INTEGER8.., UNSIGNED8.., REAL32, VISIBLE_STRING …
bits integer yes
access string ro, wo, rw, rwr, rww, const
pdo_mapping boolean yes
default string yes
value string yes DCF ParameterValue / XDC actualValue

ECATPDO is an EtherCAT PDO of an ESI.

Source: eaxPLC/pkg/fieldbus/descriptor.go

Key Type Optional Description
direction string rx (outputs) | tx (inputs)
index integer
name string yes
sm integer sync manager of the default assignment, -1: not assigned
fixed boolean yes
mandatory boolean yes
entries list of PDOMapEntry

ECATInitCmd is a CoE init command of an ESI.

Source: eaxPLC/pkg/fieldbus/descriptor.go

Key Type Optional Description
transition string PS, SO …
index integer
sub integer
data string hex
comment string yes

EIPAssembly is an assembly an EtherNet/IP EDS declares.

Source: eaxPLC/pkg/fieldbus/descriptor.go

Key Type Optional Description
key string Assem100
name string yes
instance integer
size integer bytes, 0: variable / unknown

EIPConnection is a Class 1 connection an EtherNet/IP EDS declares.

Source: eaxPLC/pkg/fieldbus/descriptor.go

Key Type Optional Description
key string Connection1
name string yes
type string exclusive_owner | input_only | listen_only
config_instance integer yes
output_instance integer yes O->T
input_instance integer yes T->O
output_size integer yes
input_size integer yes
rpi_ms number yes