Fieldbus configuration
The fieldbus configuration: buses (masters and scanners), their devices and the process-image I/O entries.
Keys are the JSON keys. Optional marks keys that are omitted when empty, or that may be absent (pointers).
Config
Section titled “Config”Config is the whole fieldbus configuration.
Source: eaxPLC/pkg/fieldbus/config.go
| Key | Type | Optional | Description |
|---|---|---|---|
version |
integer | ||
buses |
list of Bus |
Bus is one master/scanner and its devices.
Source: eaxPLC/pkg/fieldbus/config.go
| Key | Type | Optional | Description |
|---|---|---|---|
id |
string | ||
name |
string | yes | |
type |
string | ||
enabled |
boolean | ||
local_ip |
string | yes | LocalIP: the network interface to use (EtherNet/IP binds its I/O port 2222 there; empty: all interfaces / the system’s choice). |
interface |
string | yes | EtherCAT: the network interface dedicated to the line (e.g. eth1) and the cycle time (default 1000 us). |
cycle_us |
integer | yes | |
bit_rate |
integer | yes | CANopen: Interface is the CAN port (can0: SocketCAN on Linux; slcan:COM5, slcan:/dev/ttyACM0, slcan:tcp://host:port: an SLCAN adapter or a serial device server; sim: virtual nodes in the runtime), the bit rate (default 500000), the SYNC period (default 10000 us) and the master’s node id (0: none; 1..127: no node may use it, and the master produces its heartbeat every master_heartbeat_ms, default 100, for the nodes’ heartbeat consumers). |
sync_us |
integer | yes | |
master_node_id |
integer | yes | |
master_heartbeat_ms |
integer | yes | |
brokers |
list of string | yes | Brokers: tcp://, ssl:// (tls://, mqtts://), ws:// or wss:// URLs, tried in order; no user or password in a URL. A plaintext URL to anything but this computer is refused unless allow_plaintext, with a reason (the e-signed change carries it): on plaintext anyone on the path can inject PLC inputs. |
client_id |
string | yes | empty: eaxPLC-<plc id>-in |
username |
string | yes | |
ca_pem |
string | yes | |
cert_pem |
string | yes | |
keepalive_sec |
integer | yes | default 5 (2..60) |
allow_plaintext |
boolean | yes | |
plaintext_reason |
string | yes | |
bus_max_msgs_per_sec |
integer | yes | Limits of the whole connection: messages per second (default 10000), the size of one payload (default 256 KiB) and the metrics of one Sparkplug payload (default 10000). Over them, messages are dropped and counted. |
max_payload_bytes |
integer | yes | |
max_metrics |
integer | yes | |
devices |
list of Device |
Device
Section titled “Device”Device is one field device (Modbus server, EtherNet/IP adapter).
Source: eaxPLC/pkg/fieldbus/config.go
| Key | Type | Optional | Description |
|---|---|---|---|
id |
string | ||
name |
string | yes | |
enabled |
boolean | ||
host |
string | ||
port |
integer | yes | 502 / 44818 when 0 |
unit_id |
integer | yes | Modbus TCP |
poll_ms |
integer | yes | cycle time, default 100 |
timeout_ms |
integer | yes | per request, default 1000 |
rpi_ms |
number | yes | EtherNet/IP (Class 1) |
connection |
string | yes | exclusive_owner (default) | input_only | listen_only |
config_instance |
integer | yes | |
input_instance |
integer | yes | T->O (produced by the adapter) |
output_instance |
integer | yes | O->T (or the heartbeat instance) |
input_size |
integer | yes | bytes, without the sequence count |
output_size |
integer | yes | bytes, without sequence count and run/idle header |
config_data |
string | yes | hex, sent with the Forward Open |
slot |
integer | yes | backplane slot (routes 1,<slot>); -1: no route |
timeout_multiplier |
integer | yes | |
multicast |
boolean | yes | T->O multicast (default point-to-point) |
position |
integer | yes | EtherCAT: the slave’s place in the line (1 = next to the master), the identity it must have (0: not checked); input_size / output_size are its process data bytes (from a bus scan). |
vendor_id |
integer | yes | |
product_code |
integer | yes | |
node_id |
integer | yes | CANopen: the node id; the identity it must have (vendor_id, product_code and revision, object 0x1018; 0: not checked); its heartbeat producer time (written to 0x1017, default 100 ms) and the consumer time after which the master declares it lost (default 3 x the producer time); how long the master waits for its boot-up message (default 5000 ms); its PDOs and the SDO writes of its boot sequence. input_size / output_size are derived from the TPDOs / RPDOs. The identity is checked on the other buses too: EtherCAT against the slave’s SII (the revision per revision_check), EtherNet/IP as the Forward Open’s electronic key (per electronic_key; revision is major*256 + minor there). |
revision |
integer | yes | |
heartbeat_ms |
integer | yes | |
heartbeat_timeout_ms |
integer | yes | |
boot_timeout_ms |
integer | yes | |
pdos |
list of PDO | yes | |
boot_sdos |
list of SDOWrite | yes | |
revision_check |
string | yes | RevisionCheck (EtherCAT, CANopen): off | min (the device’s revision is at least the configured one: a newer device replacing an older one starts) | equal. Unset: off without a revision, min with one. |
electronic_key |
string | yes | ElectronicKey (EtherNet/IP): off (no key: any adapter answers) | compatible (vendor and product must match; a compatible newer revision is accepted) | exact (the revision too). Unset: compatible when vendor_id or product_code is set, else off. |
descriptor |
Descriptor | yes | Descriptor: the device description file imported for this device (identity, object dictionary or assemblies, process data), as parsed. |
inputs_on_fault |
string | yes | Behaviour |
outputs_on_stop |
string | yes | EtherNet/IP: idle (default) | zero; Modbus: hold (default) | zero; EtherCAT: zero (default) | hold; CANopen: preop (default) | zero |
status_address |
string | yes | optional %IX bit: TRUE while the device exchanges data |
source |
string | yes | sparkplug | json |
group_id |
string | yes | Sparkplug B: the edge node (and one of its devices). |
edge_node_id |
string | yes | |
device_id |
string | yes | |
request_rebirth |
boolean | yes | RequestRebirth (D4, off by default): after a sequence gap or a value before any birth, send the node one “Node Control/Rebirth” command, at most once per 30 s, logged. |
topic_root |
string | yes | JSON: entries’ topics are below TopicRoot. TimestampUnit of the payloads’ “timestamp” (ns, ms or s: never guessed); EaxPLCJSON: the source is an eaxPLC publisher (ns). OnlineTopic: a topic saying whether the source is alive (false or 0: every entry comm failure). |
timestamp_unit |
string | yes | |
eaxplc_json |
boolean | yes | |
online_topic |
string | yes | |
max_age_ms |
integer | yes | Defaults of the entries: max_age_ms (JSON: max_age_ms or online_topic is required; Sparkplug: 0, off), on_bad (hold). |
on_bad |
string | yes | |
max_source_age_ms |
integer | yes | MaxSourceAgeMs: an update whose own timestamp is older than this on arrival is history only (Stale, 68); 0: off. |
max_msgs_per_sec |
integer | yes | MaxMsgsPerSec: this source’s messages per second (default 1000). |
io |
list of IOEntry |
PDO is one CANopen process data object of a node: a TPDO (the node transmits; its data goes to %I) or an RPDO (the node receives; its data comes from %Q), with its communication parameters and its mapping.
A node’s input image is its TPDOs’ data one after the other, in the order configured, each taking its whole bytes; the output image is its RPDOs’ data the same way. I/O entries address these images by byte_offset / bit, like an EtherCAT slave’s process data.
Source: eaxPLC/pkg/fieldbus/canopen_config.go
| Key | Type | Optional | Description |
|---|---|---|---|
direction |
string | tpdo | rpdo | |
number |
integer | 1..512 (communication object 0x1800/0x1400 + number - 1) | |
cob_id |
integer | yes | COBID: 0 is the predefined connection set (PDO 1..4 only): TPDO 0x180/0x280/0x380/0x480 + node id, RPDO 0x200/0x300/0x400/0x500 + node id. |
transmission_type |
integer | TransmissionType: 0 acyclic synchronous, 1..240 every n-th SYNC, 254 / 255 event-driven (manufacturer / device profile). | |
event_timer_ms |
integer | yes | TPDO 254/255: also sent every period |
entries |
list of PDOMapEntry |
SDOWrite
Section titled “SDOWrite”SDOWrite is one SDO download of a node’s boot sequence (written after its PDOs, before its heartbeat time and NMT start).
Source: eaxPLC/pkg/fieldbus/canopen_config.go
| Key | Type | Optional | Description |
|---|---|---|---|
index |
integer | ||
sub |
integer | ||
data_type |
string | BOOLEAN, INTEGER8..64, UNSIGNED8..64, REAL32, REAL64, VISIBLE_STRING, OCTET_STRING (hex) | |
value |
string | ||
name |
string | yes |
Descriptor
Section titled “Descriptor”Descriptor is an imported device description, as parsed: what the configurator and the identity check need, not the whole file.
Source: eaxPLC/pkg/fieldbus/descriptor.go
| Key | Type | Optional | Description |
|---|---|---|---|
format |
string | ||
file_name |
string | yes | |
sha256 |
string | ||
identity |
DescriptorIdentity | ||
objects |
list of ODObject | yes | CANopen: the object dictionary’s identity, PDO and mappable objects; the PDOs and boot SDOs a DCF / XDC configures (an EDS / XDD: its default PDO mapping); the node id and bit rate of a DCF / XDC. |
pdos |
list of PDO | yes | |
boot_sdos |
list of SDOWrite | yes | |
node_id |
integer | yes | |
bit_rate |
integer | yes | |
heartbeat_ms |
integer | yes | DCF / XDC: 0x1017 as configured |
ethercat_pdos |
list of ECATPDO | yes | EtherCAT: the PDOs (RxPDO outputs, TxPDO inputs) with their entries, the default assignment’s process data sizes, and the CoE init commands (written at PS: information, the master does not run them yet). |
init_commands |
list of ECATInitCmd | yes | |
assemblies |
list of EIPAssembly | yes | EtherNet/IP: the assemblies and the connections the EDS declares. |
connections |
list of EIPConnection | yes | |
input_size |
integer | yes | Process data bytes (EtherCAT: the default PDOs; EtherNet/IP: the first exclusive owner connection). |
output_size |
integer | yes | |
registers |
list of IOEntry | yes | Modbus register map: the I/O entries (without PLC addresses). |
warnings |
list of string | yes | Warnings: what was read but is not used, or was skipped. |
IOEntry
Section titled “IOEntry”IOEntry maps a range of a device’s process data to the PLC.
Source: eaxPLC/pkg/fieldbus/config.go
| Key | Type | Optional | Description |
|---|---|---|---|
id |
string | ||
name |
string | yes | |
direction |
string | in (device -> %I) | out (%Q -> device) | |
area |
string | yes | Modbus: coil | discrete_input | holding_register | input_register, 0-based address |
address |
integer | yes | |
byte_offset |
integer | yes | EtherNet/IP: offset in the assembly (and bit, for BOOL) |
bit |
integer | yes | |
data_type |
string | BOOL SINT USINT BYTE INT UINT WORD DINT UDINT DWORD REAL | |
count |
integer | yes | elements, default 1 |
word_order |
string | yes | Modbus 32-bit: ABCD (default, high word first) | CDAB |
plc_address |
string | first element: %IX0.0, %IW4, %QD8 … | |
metric |
string | yes | Sparkplug: the metric name |
topic |
string | yes | JSON: below the source’s topic_root |
quality_address |
string | yes | The entry’s quality outputs, in %I: quality_address (%IX, TRUE only while Good: Uncertain and Stale are FALSE), status_address (%IB, the quality code), timestamp_address (%IL, the source’s timestamp in Unix ms), age_address (%ID, ms since the last accepted update). |
status_address |
string | yes | |
timestamp_address |
string | yes | |
age_address |
string | yes | |
on_bad |
string | yes | |
substitute |
string | yes | a literal of the entry’s type |
max_age_ms |
integer | yes | nil: the source’s |
PDOMapEntry
Section titled “PDOMapEntry”PDOMapEntry is one object mapped into a PDO (index, sub-index, length).
Source: eaxPLC/pkg/fieldbus/canopen_config.go
| Key | Type | Optional | Description |
|---|---|---|---|
index |
integer | ||
sub |
integer | ||
bits |
integer | ||
name |
string | yes | |
data_type |
string | yes | the object’s CANopen data type (information) |
DescriptorIdentity
Section titled “DescriptorIdentity”DescriptorIdentity is who the device is.
Source: eaxPLC/pkg/fieldbus/descriptor.go
| Key | Type | Optional | Description |
|---|---|---|---|
vendor_id |
integer | yes | |
vendor_name |
string | yes | |
product_code |
integer | yes | |
product_name |
string | yes | |
revision |
integer | yes | |
order_code |
string | yes | |
device_type |
integer | yes | CANopen 0x1000, EtherNet/IP product type |
ODObject
Section titled “ODObject”ODObject is a CANopen object dictionary entry.
Source: eaxPLC/pkg/fieldbus/descriptor.go
| Key | Type | Optional | Description |
|---|---|---|---|
index |
integer | ||
sub |
integer | ||
name |
string | ||
data_type |
string | BOOLEAN, INTEGER8.., UNSIGNED8.., REAL32, VISIBLE_STRING … | |
bits |
integer | yes | |
access |
string | ro, wo, rw, rwr, rww, const | |
pdo_mapping |
boolean | yes | |
default |
string | yes | |
value |
string | yes | DCF ParameterValue / XDC actualValue |
ECATPDO
Section titled “ECATPDO”ECATPDO is an EtherCAT PDO of an ESI.
Source: eaxPLC/pkg/fieldbus/descriptor.go
| Key | Type | Optional | Description |
|---|---|---|---|
direction |
string | rx (outputs) | tx (inputs) | |
index |
integer | ||
name |
string | yes | |
sm |
integer | sync manager of the default assignment, -1: not assigned | |
fixed |
boolean | yes | |
mandatory |
boolean | yes | |
entries |
list of PDOMapEntry |
ECATInitCmd
Section titled “ECATInitCmd”ECATInitCmd is a CoE init command of an ESI.
Source: eaxPLC/pkg/fieldbus/descriptor.go
| Key | Type | Optional | Description |
|---|---|---|---|
transition |
string | PS, SO … | |
index |
integer | ||
sub |
integer | ||
data |
string | hex | |
comment |
string | yes |
EIPAssembly
Section titled “EIPAssembly”EIPAssembly is an assembly an EtherNet/IP EDS declares.
Source: eaxPLC/pkg/fieldbus/descriptor.go
| Key | Type | Optional | Description |
|---|---|---|---|
key |
string | Assem100 | |
name |
string | yes | |
instance |
integer | ||
size |
integer | bytes, 0: variable / unknown |
EIPConnection
Section titled “EIPConnection”EIPConnection is a Class 1 connection an EtherNet/IP EDS declares.
Source: eaxPLC/pkg/fieldbus/descriptor.go
| Key | Type | Optional | Description |
|---|---|---|---|
key |
string | Connection1 | |
name |
string | yes | |
type |
string | exclusive_owner | input_only | listen_only | |
config_instance |
integer | yes | |
output_instance |
integer | yes | O->T |
input_instance |
integer | yes | T->O |
output_size |
integer | yes | |
input_size |
integer | yes | |
rpi_ms |
number | yes |