Alarm banner
The alarm banner: the most urgent standing alarms of the area on one to ten lines, coloured by their alarm class and priority, with counters by priority, a Ack shown button that acknowledges exactly the lines shown, and a silence button. A click on a line opens the alarm’s details (or a screen). The product’s built-in safety alarms (plant emergency stop, PLC faults) are always listed first, whatever the filters. Acknowledging goes through the acknowledge dialog: the signer is the signed-in user, and a reason is required where the alarm class asks for one.

| Palette | Not in the palette |
JSON type |
AlarmBanner |
| Name in the inspector | Alarm banner |
| Size | drawn from width and height; a resize changes them |
| Added by | designer_alarm_widgets.js |
Properties
Section titled “Properties”| Shown as | Key | Type | Unit | Default | Allowed values | What it does |
|---|---|---|---|---|---|---|
| Screen to open | navScreen |
Screen id | — | The screen opened on a click when the click action is “Open the screen”. Inspector hint: Opened on click when the click action is “Open the screen”. | ||
| Lines | bannerRows |
Number | — | 1 to 10 | Number of alarm lines shown. More alarms than lines: the most urgent (by the order below) are shown, and the counters show the total. | |
| Order | bannerSort |
Choice | — | priority Most urgent firstnewest Newest firstfirst_out First out (oldest first) |
Which alarms come first: the most urgent (priority, then newest), the newest, or the first out (the oldest standing alarm first: shows what started an alarm flood). | |
| Columns | bannerColumns |
Column list | — | prioritytimeareatagmessagevaluesetpointstateclass |
The columns of a line, in order, comma separated. Empty: priority, time, tag, message, value, state. | |
| Priorities | alarmPriorities |
List (comma separated) | — | The priorities shown (CRITICAL, HIGH, MEDIUM, LOW, INFO), comma separated. Empty: all. Inspector hint: None checked: every priority. | ||
| Classes | alarmClasses |
List (comma separated) | — | The alarm classes shown (Safety, Process, Environmental, Equipment, Diagnostic, and the project’s own), comma separated. Empty: all. Inspector hint: None checked: every class. | ||
| Only unacknowledged alarms | onlyUnacked |
Yes / no | — | Shows only alarms not yet acknowledged. | ||
| Click on a line | clickAction |
Choice | — | details Alarm detailsscreen Open the screennone Nothing |
What a click on a line does: the alarm’s details, open the screen (navScreen), or nothing. | |
| Rotate (one line), seconds | rotateSeconds |
Number | s | — | 0 to 60 | One-line banner: shows the standing alarms one after the other, this many seconds each. 0: no rotation. Never rotates away from a built-in safety alarm. Inspector hint: 0: no rotation. Never rotates away from a built-in safety alarm. |
| Counters by priority | showCounters |
Yes / no | — | Shows the unacknowledged / total counter of each priority. | ||
| “Ack shown” button (acknowledges the lines shown only) | showAckPage |
Yes / no | — | Shows the Ack shown button: it acknowledges the unacknowledged alarms on the lines shown, never alarms hidden by a filter. | ||
| Silence button | showSilence |
Yes / no | — | Shows the Silence button, which silences the alarm sound in this browser (it acknowledges nothing). | ||
| — | width |
Number | 480 |
Width of the banner. | ||
| — | height |
Number | 48 |
Height of the banner: give each line about 36 pixels. | ||
| — | fill |
Colour | "#450a0a" |
Kept from the first banner; the banner is drawn in the alarm classes’ colours. | ||
| — | stroke |
Colour | "#ef4444" |
Kept from the first banner; not drawn. | ||
| — | strokeWidth |
Number | 1.5 |
Kept from the first banner; not drawn. | ||
| — | label |
Text | "ISA-18.2 ALARMS" |
The banner’s name in the layers list. | ||
| Area (tag folder) | alarmAreaFilter |
Tag folder | — | Only the alarms of tags under this folder (Plant/Line1). Built-in safety alarms are always shown. | ||
| Role | alarmRoleFilter |
Text | — | Only the alarms whose target roles include this role (ALL or empty: every alarm). Kept from banners made with the first banner; not in the inspector. | ||
| Severity filter (first banner) | alarmSeverityFilter |
Text | — | Read from banners made with the first banner (ALL, CRITICAL, HIGH_AND_CRITICAL…) and turned into priorities; new banners use Priorities. | ||
| X | x |
Number | px | — | Horizontal position of the object’s top-left corner on the screen, in screen pixels from the left edge. | |
| Y | y |
Number | px | — | Vertical position of the object’s top-left corner, in screen pixels from the top edge. | |
| Rotation | rotation |
Number | ° | — | Rotation of the object, clockwise, in degrees. | |
| Opacity | opacity |
Number | — | 0 (invisible) to 1 (opaque). An object disabled by an interlock is drawn at 0.45 whatever this says. | ||
| States | states |
Object | — | This object’s own state styles (normal, hover, pressed, on, disabled, bad, locked, unconfigured), edited in the inspector’s States section. Visual only. Empty: the project’s state styles. | ||
| State family | styleFamily |
Text | — | The state family whose project styles apply (button, input, toggle, selector, faceplateButton, default). Empty: the family of the object’s type. |
Bindings and conditions
Section titled “Bindings and conditions”The Bind tab ties a property to a tag or an expression: a tag binding takes the tag’s value, an expression binding computes one (see the expression language), optionally through a map, format or script transform. The targets the Bind tab offers for this object:
| Bind tab target | Key | What the bound value does |
|---|---|---|
| Fill Color | fill |
Sets the fill colour from the value (a colour text such as #22c55e, or a colour mapped by a map transform). |
| Stroke / Border Color | stroke |
Sets the outline colour from the value. |
| Opacity (0.0 - 1.0) | opacity |
Sets the opacity from the value (0 to 1). |
| Visibility (Boolean) | visible |
Shows the object when the value is true or non-zero, hides it otherwise. |
| Rotation (°) | rotation |
Rotates the object by the value, in degrees. |
| Scale / Pulse | scale |
Scales the object by the value (1 = drawn size). |
| Text / Label | text |
Replaces the text drawn with the value, formatted by the binding’s format. On a Text object a number is followed by the object’s unit, as with the Value target (never a word). A Bad value shows a dash. |
| Value (Numeric) | value |
Shows the value as the object’s readout (with the unit and decimals). A Bad value shows a dash. |
The Cond tab adds rules evaluated on every value change: Visibility (show or hide, by condition or role), Color & Fill (colour bands, alarm blinking), Position and Size & Fill (motion and level mapped from a value), Rotation (angle or continuous spin; an empty input range is 0 to 100 and empty angles are -135° to 135°, while 0 is a value), Security & Touch (the interlock: a disable condition, the role required, what happens when the interlock reads a Bad value) and Text & Value (formatted text). A condition that reads a Bad value is never applied as if the value were good: visibility shows the object marked Bad, colours go neutral grey, motion stays where it is, text shows a dash.
Actions
Section titled “Actions”Any object can carry a click or tap action (the Action tab, or Full Dialog…). A write action whose tag, value or target is missing is not configured: the inspector says so and the operator’s press does nothing (unconfigured means disabled). Navigation actions write nothing and ask no confirmation. On touch screens only a deliberate tap runs an action: a swipe or a pinch that ends on the object never does. Action types:
| Action | Key (action.type) |
What it does |
|---|---|---|
| Set tag to 1 | set_1 |
Writes 1 to the action’s tag. |
| Set tag to 0 | set_0 |
Writes 0 to the action’s tag. |
| Toggle tag value | toggle |
Writes the opposite of the tag’s LIVE value: 0 when it is not 0, 1 when it is 0. When the live value is unknown, not Good or not a number, nothing is written and the operator is told why; when it changes while the operator confirms or signs, nothing is written either. |
| Set tag to 1 on press and to 0 on release | momentary_1_0 |
Writes 1 while pressed and 0 on release (hold to run). On touch, the press counts only after the finger is held still; the release is always sent. A held press is also released when the browser window loses focus or the page is hidden, and in the designer when a drag or a resize of the object starts. |
| Set tag to 0 on press and to 1 on release | momentary_0_1 |
Writes 0 while pressed and 1 on release. Released in the same cases as the 1/0 momentary. |
| Write custom value | write_val |
Writes the number in write_value. |
| Run script | run_command |
Runs a client script with the scripting API (system.tag.write, system.nav.openPopup…). Ctrl+Space completes the API. |
| Navigate to page / screen | navigate |
Opens another screen, optionally with parameters or a parameter set. |
| Open popup screen | open_popup |
Opens a screen in a popup window: modal or not, centred, next to the object or at a fixed position, with parameters. |
| Close popup | close_popup |
Closes the popup the object is in, or the popup with the given id. |
| Open dock | open_dock |
Opens a screen docked to an edge of the runtime (top, bottom, left, right). |
| Close dock | close_dock |
Closes the dock on that edge. |
| Open or close dock | toggle_dock |
Opens or closes the dock on that edge. |
| Back | nav_back |
Goes back to the previous screen. |
| Forward | nav_forward |
Goes forward again after Back. |
| Home screen | nav_home |
Opens the project’s home screen. |
| Open downtime panel | open_downtime |
Opens the operator runtime’s Downtime panel (OEE and downtime, Pro and Enterprise), optionally on one machine (its machine id). Navigation only: nothing is written to a tag or a machine. A machine the operator may not read is not shown; where the panel is not available, a notice says so. Offered in the designer only when the licence includes OEE and downtime. |
States, text and parameters
Section titled “States, text and parameters”States. An object’s look follows its state: normal, hover, pressed, on, disabled, bad (quality), locked (role) and unconfigured. The project’s state styles (opened from an object’s States section, or from the Project manager’s Operator runtime section) give each family of objects its colours per state, and the inspector’s States section overrides them for one object (stored in props.states). States are visual only: whether an object can be operated is decided by its interlock, the user’s rights and the server.
This object belongs to the state family default (all other objects): disabled (an interlock dims it to 0.45 opacity), bad (a tag it reads is Bad) and locked (missing role) apply when the object has conditions or an action; the other states apply to objects that are operated.
Screen parameters. On a screen with parameters, {Name} in any text of the object (tag paths of bindings and actions, expressions, conditions, interlocks, the confirmation tag, texts) is replaced by the parameter’s value when the screen opens, so one screen serves many pieces of equipment ({Pump}/Running). See screen parameters.
Quality. When a value the object reads is Bad, not readable, Uncertain or stale, the object is marked: a red x and a grey veil (or hatching, per the project’s quality style) for Bad or no connection, a blue lock for a tag the signed-in account may not read, an amber ? for Uncertain, a dashed outline for stale. A tag that is not readable is greyed as Bad and its value is never shown as good. The lock shows only when every Bad tag of the object is not readable: a device fault keeps the red x. Each object shows one marker, for its worst state, and markers that would overlap merge into one, drawn on the largest object with the worst state of all. The marker’s tooltip lists every tag, its quality and its age. A Bad value is never drawn as a good one. See show bad and stale values.
Comments. In the studio, right-click the object and choose Add comment to start a design-review thread on it; a numbered pin marks objects with open threads (Starter, Pro and Enterprise). Pins are shown in the designer only, never in the runtime. See review screens before deploy.
Examples
Section titled “Examples”A one-line banner in a screen header
Section titled “A one-line banner in a screen header”A one-line banner across the top of every screen, showing the most urgent alarm of the processing area, rotating every 5 seconds through the others, with the counters on the right.
- Place Alarm banner (1 line) from the Alarms palette group, 760 × 44.
- Area (tag folder)
Plant/Processing; Rotate 5 seconds; columns priority, time, message, value. - Put it on a header screen docked at the top (Display settings), so every screen shows it.

The alarm banner as saved in the screen (JSON)
{ "type": "AlarmBanner", "props": { "bannerRows": 1, "rotateSeconds": 5, "bannerColumns": "priority,time,message,value", "alarmAreaFilter": "Plant/Processing", "label": "Header banner" }}