Connect alarms to the controller (handshake)

eaxScadaHow-to guideStarterProEnterpriseView as Markdown

Exchange an alarm’s life with the controller that raised it:

  • the controller learns that the alarm was shown to an operator, and that it was acknowledged (by an operator or from the field);
  • a pushbutton wired to the controller acknowledges the alarm in eaxScada;
  • an alarm can be defined as needing no acknowledgement: it is active while its condition holds and returns to normal on its own.

The handshake is part of Starter, Pro and Enterprise. It is not in Free: a definition that uses it cannot be saved there.

Open Alarms > Alarm Definitions Studio, select an alarm (or New Alarm) and open the Controller handshake section. Every setting is optional; an alarm without them behaves as before.

Setting Field in the definition What it does
Acknowledgement required ack_required On (the default): the ISA-18.2 lifecycle, an operator acknowledges. Off: the alarm needs no acknowledgement (see Alarms that need no acknowledgement).
Shown signal tag shown_tag eaxScada writes 1 to this tag once a signed-in operator’s screen has displayed the alarm (see What “shown” means).
Acknowledged signal tag ack_tag eaxScada writes 1 to this tag when the alarm is acknowledged, by an operator or by the controller.
Controller acknowledge tag plc_ack_tag eaxScada watches this tag. A change from 0 to non-zero while the alarm is unacknowledged acknowledges it, recorded as the controller’s (PLC:<tag>).

eaxScada writes 1, never 0. The controller resets the shown and acknowledged tags itself, normally when it resets the trip. Until it does, the tag stays at 1.

The tags are checked when you save:

  • each one is a different tag, and none is the alarm’s own tag;
  • each one is a boolean or an integer;
  • the shown and acknowledged tags are written, so each must be a writable device tag (a driver tag whose mapping is not read-only, or a member of an eaxPLC that outside clients may write) or a writable eaxTag;
  • the controller acknowledge tag is only read;
  • the plant emergency-stop signal is never a handshake tag.

Next to each tag the editor shows whether the alarm manager may write it (Writable by the alarm manager, or Not written until granted, with the reason). With Acknowledgement required off, the acknowledged signal tag and the controller acknowledge tag are shown as Ignored.

One-time setup: let the alarm manager write the tags

Section titled “One-time setup: let the alarm manager write the tags”

The handshake writes are made by a system actor, the alarm manager. It writes a tag only when the security permissions explicitly allow it, with the same rules as an operator’s write permission. A security administrator sets this up once:

  1. Open Security > Roles and create a role named exactly Alarm_Manager.
  2. Open Topic Rights and click to add a rule:
    • Target Role: Alarm_Manager;
    • Target Type: UNS Topic;
    • Action: publish (write tag / command);
    • Target Subject / Pattern: the tag, or a pattern that covers the signal tags, for example Plant/Tank1/> (* matches one level, > the rest of the path). For an eaxPLC member, a rule on one of its containers also matches;
    • Effect: ALLOW.
  3. Save. The editor’s check of each signal tag now says Writable by the alarm manager.

Rules for the grant:

  • A DENY wins. A publish DENY rule of the role that matches the tag (or one of its containers) refuses the write, whatever the ALLOW rules and the priorities say.
  • No role, or no matching ALLOW rule: every write is refused. Nothing is skipped silently: the refusal is audited and shown on the alarm’s row.
  • The role is for the alarm manager. Do not give it to people: they would get the same write rights.

After the grant, the write goes through the same checks as an operator’s write: an eaxPLC member that is read-only is refused, then the write policy applies as for an external writer (interlocks, write ranges and limits), then the tag’s engineering range, and only then the device or eaxTag write. Every write and every refusal is in the audit trail.

A tag the write policy asks a person to sign or confirm is never written by the alarm manager. Nobody signs for it, so the write is refused (WRITE_POLICY_PERSON_REQUIRED). Use signal tags without a signature or confirmation requirement.

In Alarms > Active Standing Alarms, the Controller handshake column shows each signal of the current activation: Shown and Ack, each written (✓), waiting (⧗), failed (✕) or not yet shown (•); a signal dropped because the alarm ended first shows Not sent: alarm ended. A row with a waiting or failed write gets a warning marker, and the chip above the grid (“2 handshake warnings”) filters to those rows. Click the marker for the detail: which write is missing (1 to which tag), the reason, the number of attempts and the fix.

The detail says Fix
The alarm manager may not write the tag (no role Alarm_Manager, no matching rule, or a rule denies it) Grant it as described above.
The write policy asks for a person’s signature or confirmation Use a signal tag without that requirement.
Refused by the write policy, out of range, read-only Change the tag’s write policy, range or access, or pick another tag.
A device write failed Check the device connection and the tag. The write is retried while the alarm stands; once it has ended the signal is dropped (see below).
This server is the standby Nothing to fix: the primary writes the controller signals.
The runtime is stopped Start the runtime: no controller signal is written while it is stopped.
The edition The handshake needs a Starter licence or higher.
State machineOne controller signal, from due to written or not sent
One controller signal, from due to written or not sentA shown or acknowledged signal of one activation starts as waiting. The primary writes 1 to its tag and the signal is written. A write that is refused or fails leaves it failed, and it is retried while the alarm stands. Once the alarm has ended, a signal that is not written is dropped and never sent. A new trip of the alarm ends the pending signals of the previous activation.WAITINGheld on a standby, or whilethe runtime is stoppedWRITTEN1 is in the tagNOT SENT"Not sent: alarm ended"FAILEDrefused, or not writtenWhen the alarm trips againthe waiting and failed signals of the previousactivation are never sent; the new one gets its ownthe primary writes 1refused, or thewrite failsretried after 1 s, doubling to 30 s;5 min or more when every try is auditeda retrysucceedsalarmendedalarm ended
Retries stop when the alarm ends: a late 1 would stand for a trip that nobody saw or acknowledged.
Read as text

A shown or acknowledged signal of one activation starts as waiting. The primary writes 1 to its tag and the signal is written. A write that is refused or fails leaves it failed, and it is retried while the alarm stands. Once the alarm has ended, a signal that is not written is dropped and never sent. A new trip of the alarm ends the pending signals of the previous activation.

States

  • WAITING (state): held on a standby, or while the runtime is stopped
  • WRITTEN (state): 1 is in the tag
  • NOT SENT (state): "Not sent: alarm ended"
  • FAILED (state): refused, or not written

Transitions

  • Start → WAITING (transition). The signal becomes due: a signed-in operator's screen showed the alarm, or the alarm was acknowledged.
  • WAITING → WRITTEN (transition): the primary writes 1. Only the primary with quorum writes, only while the runtime runs.
  • WAITING → FAILED (transition): refused, or the write fails
  • FAILED → FAILED (transition): retried after 1 s, doubling to 30 s; 5 min or more when every try is audited. Every try is audited after a refusal by the write policy, a refusal by the eaxPLC, or a device write that failed after its record.
  • FAILED → WRITTEN (transition): a retry succeeds
  • FAILED → NOT SENT (transition): alarm ended. The alarm is back to normal or shelved: no retry after that.
  • WAITING → NOT SENT (transition): alarm ended. A signal that became due at most 5 s before the end, or after it, and was never tried or held, gets one attempt: written if it succeeds, not sent if it fails. A standby keeps it waiting for the primary.
  • Only the primary writes. In a high availability pair (Enterprise), only the primary with quorum writes the signal tags and acts on the controller acknowledge tag. A standby refuses shown confirmations (409 not_primary): the primary records them, and its alarm states are replicated. The signals already written or dropped travel to the standby with the alarm states, so a new primary after a failover never sends them; one still pending, it sends under the same rules (writing 1 again is harmless).
  • Only while the runtime runs, and only in an edition that includes the handshake.
  • Only while the activation stands. Each trip starts a new activation. While the alarm stands (unacknowledged, acknowledged, or returned but unacknowledged), a write that fails is retried with a growing delay (1 s, doubling, up to 30 s; at least 5 minutes after a refusal by the write policy or by the eaxPLC, or after a device write that failed, because each of these attempts is audited). When the alarm trips again, the previous activation’s pending writes are dropped, never sent: the new activation gets its own.
  • A refusal is journaled once per distinct reason, not on every retry.

Once the alarm is back to normal or shelved, its activation has ended (the time is recorded as ended_time). A shown or acknowledged signal not yet written by then is no longer retried:

  • it gets at most one attempt, and only if it became due at most 5 s before the end, or after it (typically the acknowledgement that returns a returned-unacknowledged alarm to normal);
  • otherwise, or if that one attempt fails, or if this node may not write at that moment (for example the runtime is stopped), the signal is dropped: it is never sent, by this server or by a new primary after a failover (the dropped state is replicated);
  • a dropped signal is journaled once as a SIGNAL record, shown signal not written: the alarm returned to normal before the write succeeded (<reason>) (or acknowledged signal …), and audited once as MANUAL_OVERRIDE_REFUSED with the code SIGNAL_DROPPED_ALARM_ENDED. The alarm’s row shows Not sent: alarm ended.

The reason: after the end the controller may already have reset its tags, and a late 1 would stand for an activation that nobody saw or acknowledged on the next trip. A standby leaves an ended activation’s signal to the primary, and drops it itself if it takes over.

The shown signal is written once the alarm has been displayed to a person: a signed-in user’s screen showed it while the page was visible, and that user is allowed to see the alarm. These views confirm it:

  • the alarm banner, the alarm summary and the annunciator on runtime screens;
  • the alarm summary card of a dashboard;
  • the alarm list of the phone runtime, only while the list is open.

The first confirmation wins and is recorded with that user’s name.

These never confirm an alarm shown:

  • a kiosk screen without a signed-in user;
  • an API token or a PLC token;
  • the AI co-pilot;
  • a browser tab in the background (it confirms once it becomes visible).

Only a standing alarm is confirmed: unacknowledged, acknowledged, or returned but unacknowledged. An alarm back in the normal state, a shelved alarm, or an activation already replaced by a new trip is not.

The controller acknowledge tag: rising edges only

Section titled “The controller acknowledge tag: rising edges only”

Only a change from 0 to non-zero acknowledges, and only while the alarm is unacknowledged:

  • A held button acknowledges once. If the tag is still 1 when the alarm trips again, nothing happens: release the button (0) and press it again.
  • An edge while no alarm waits for acknowledgement is spent: it does not acknowledge a later trip.
  • The first value read is the reference, never an edge: after eaxScada starts, after the runtime is stopped and started again, and after the tag of the definition is changed. A button pressed across a runtime stop acknowledges nothing; press it again.
  • With Acknowledgement required off, the tag is ignored.

An acknowledgement by the controller is recorded like an operator’s, with the acknowledger PLC:<tag> and the reason “acknowledged by the controller”, and it makes the acknowledged signal due like any other acknowledgement.

With Acknowledgement required off:

  • the alarm is active while its condition holds (the grid shows ACTIVE, “Active (no acknowledgement required)”) and returns to normal on its own when the condition clears;
  • it never waits for an acknowledgement (no unacknowledged or returned unacknowledged state), so there is nothing to acknowledge;
  • it plays one short beep per activation when it trips live. The beep follows the alarm’s sound alert setting and its class sound (no sound, or volume 0, means silent); it never repeats, and reloading the page does not replay it. It also plays while the horn is silenced, without lifting the silence. The runtime’s backup horn, used when its main alarm sound module is not available, follows the same one-beep rule;
  • its trip and return records in the journal say “no acknowledgement required”;
  • the shown signal still works; the acknowledged signal and the controller acknowledge tag are ignored.

The AI assistant and the handshake settings

Section titled “The AI assistant and the handshake settings”

The handshake settings are set by an engineer, never by the AI assistant:

  • an alarm the assistant proposes cannot set Acknowledgement required, the Shown signal tag, the Acknowledged signal tag or the Controller acknowledge tag (ack_required, shown_tag, ack_tag, plc_ack_tag): such a proposal is refused;
  • a change the assistant makes to an existing alarm leaves these four settings as they are.

Worked example: a latched trip in the controller

Section titled “Worked example: a latched trip in the controller”

A tank’s high-level switch latches a trip that stops the pump. The operator acknowledges in eaxScada or with a pushbutton at the tank; a reset button clears the trip once the level is back and the alarm is acknowledged.

PROGRAM TankAlarm
VAR
HighLevel : BOOL; (* level switch, from the I/O *)
ResetPB : BOOL; (* reset pushbutton, from the I/O *)
AckPB : BOOL; (* field acknowledge pushbutton, from the I/O *)
Trip : BOOL; (* the alarm's tag: the eaxScada alarm watches it *)
Shown : BOOL; (* Shown signal tag: eaxScada writes 1 *)
Acked : BOOL; (* Acknowledged signal tag: eaxScada writes 1 *)
FieldAck : BOOL; (* Controller acknowledge tag: eaxScada watches its 0 -> 1 edge *)
PumpRun : BOOL; (* permissive: the pump runs only while no trip is latched *)
END_VAR
(* 1. Trip latch: the condition sets it; only the reset below clears it. *)
IF HighLevel THEN
Trip := TRUE;
END_IF;
(* 2. The field acknowledge button drives the controller acknowledge tag.
eaxScada acknowledges on a 0 -> 1 change only: a button held down
acknowledges once, never a later trip. *)
FieldAck := AckPB;
(* 3. Reset: only once the condition is gone and the alarm is acknowledged
(by an operator or by the field button: eaxScada writes Acked := 1 for
both). eaxScada never writes 0: the controller clears Shown and Acked,
so the next trip starts from 0. *)
IF ResetPB AND NOT HighLevel AND Acked THEN
Trip := FALSE;
Shown := FALSE;
Acked := FALSE;
END_IF;
PumpRun := NOT Trip;
END_PROGRAM

The alarm definition in eaxScada:

Setting Value
Tag Trip (condition HIGH, setpoint 1, deadband 0)
Acknowledgement required On
Shown signal tag Shown
Acknowledged signal tag Acked
Controller acknowledge tag FieldAck

Use the full tag paths your project gives these variables (pick them with Pick in the editor). Shown and Acked must be writable from the network on the PLC, and the role Alarm_Manager needs a publish ALLOW rule on them.

What happens:

SequenceA latched trip, shown, acknowledged and reset
A latched trip, shown, acknowledged and resetThe controller latches a trip and eaxScada raises the alarm. Once a signed-in operator's screen has displayed it, eaxScada writes 1 to the shown tag. The alarm is then acknowledged, by the operator on the screen or by the field pushbutton through the controller acknowledge tag, and eaxScada writes 1 to the acknowledged tag. The controller resets the trip and clears both tags itself, and the alarm returns to normal.ACKNOWLEDGED ON SCREENOR BY THE FIELD BUTTONControllerTankAlarmeaxScadaalarm managerRuntime screensigned-in userOperatorLatches the tripHighLevel rises: Trip := TRUEthe pump stops1Trip reads 1the alarm's tagRaises the alarmunacknowledged (UNACK_ALARM)a new activation2The alarm, unacknowledged3Confirms it was shownthe page was visible; the first confirmation wins4Writes Shown := 1only the primary, after the checks of a writeCMDA write that is refused or fails is retriedwhile the alarm standsAcknowledges5Acknowledgementby the operator6FieldAck goes 0 to 1AckPB pressed: recorded as PLC:<tag>Records the acknowledgementacknowledged (ACK_ALARM)the acknowledged signal is due7Writes Acked := 1for either acknowledgementCMDResets the tripResetPB, level back, Acked = 1clears Trip, Shown and Acked8Trip reads 0The alarm returns to normalthe activation has ended
eaxScada writes 1 and never 0: the controller clears Shown and Acked when it resets the trip, so the next trip starts from 0.
  • Product
  • Service or process
  • Device or controller
  • Person or role
  • Data or telemetry
  • Command to equipment
  • Alarm or event
Read as text

The controller latches a trip and eaxScada raises the alarm. Once a signed-in operator's screen has displayed it, eaxScada writes 1 to the shown tag. The alarm is then acknowledged, by the operator on the screen or by the field pushbutton through the controller acknowledge tag, and eaxScada writes 1 to the acknowledged tag. The controller resets the trip and clears both tags itself, and the alarm returns to normal.

Participants

  • Controller (device or controller): TankAlarm
  • eaxScada (product): alarm manager
  • Runtime screen (service or process): signed-in user
  • Operator (person or role)

Steps, in order

  1. Controller: Latches the trip: HighLevel rises: Trip := TRUE; the pump stops
  2. Controller → eaxScada (data or telemetry): Trip reads 1. the alarm's tag
  3. eaxScada: Raises the alarm: unacknowledged (UNACK_ALARM); a new activation
  4. eaxScada → Runtime screen (alarm or event): The alarm, unacknowledged
  5. Runtime screen → eaxScada (data or telemetry): Confirms it was shown. the page was visible; the first confirmation wins
  6. eaxScada → Controller (command to equipment): Writes Shown := 1. only the primary, after the checks of a write
  7. Note: A write that is refused or fails is retried while the alarm stands
  8. Acknowledged on screen:
    1. Operator → Runtime screen (data or telemetry): Acknowledges
    2. Runtime screen → eaxScada (data or telemetry): Acknowledgement. by the operator
  9. Or by the field button:
    1. Controller → eaxScada (data or telemetry): FieldAck goes 0 to 1. AckPB pressed: recorded as PLC:<tag>
  10. eaxScada: Records the acknowledgement: acknowledged (ACK_ALARM); the acknowledged signal is due
  11. eaxScada → Controller (command to equipment): Writes Acked := 1. for either acknowledgement
  12. Controller: Resets the trip: ResetPB, level back, Acked = 1; clears Trip, Shown and Acked
  13. Controller → eaxScada (data or telemetry): Trip reads 0
  14. eaxScada: The alarm returns to normal: the activation has ended
  1. HighLevel rises: Trip latches, the pump stops, eaxScada raises the alarm (unacknowledged).
  2. The operator’s runtime screen shows it: eaxScada writes Shown := 1.
  3. The operator acknowledges in eaxScada, or presses AckPB at the tank (FieldAck goes 0 to 1): eaxScada records the acknowledgement and writes Acked := 1.
  4. The level drops and the operator presses ResetPB: the controller clears Trip, Shown and Acked. The alarm returns to normal in eaxScada.

Treat Shown and Acked as meaningful only while Trip is set. eaxScada does not write a signal after the alarm has ended (see No signal after the alarm has ended), so a 1 does not arrive for a trip you have already reset, except for the one attempt allowed right at the end. The reset in this example needs Acked: if the acknowledged signal cannot be written (see the row warning), the trip stays latched until it is fixed, which is the safe side. If your process must reset without it, base the reset on your own condition instead.

Where Record
Alarm journal (Sequence of Events) SHOWN: shown on the screen of <user>. SIGNAL: shown signal: 1 written to <tag> (for <user>) or acknowledged signal: …, by alarm manager; for a dropped signal, shown signal not written: the alarm returned to normal before the write succeeded (<reason>). ACK by PLC:<tag> for a controller acknowledgement.
Audit trail ALARM_SHOWN by the operator; ALARM_ACKNOWLEDGE by PLC:<tag> (role Controller); MANUAL_OVERRIDE or MANUAL_OVERRIDE_REFUSED by alarm manager (for <user>) or alarm manager (for PLC:<tag>), role Alarm_Manager; a dropped signal is one MANUAL_OVERRIDE_REFUSED row with the code SIGNAL_DROPPED_ALARM_ENDED.
Access audit WRITE_DENIED for a write the alarm manager is not granted.
  1. Save the definition: the editor shows every signal tag as writable by the alarm manager.
  2. Force the alarm’s condition in a test: the row shows Shown not yet shown, then written once a signed-in operator’s runtime screen displays it, and the controller’s shown tag reads 1.
  3. Acknowledge: Ack turns written and the acknowledged tag reads 1.
  4. Toggle the controller acknowledge tag 0 to 1 on a new trip: the alarm is acknowledged by PLC:<tag>.