Moving analog indicator

eaxScadaReferenceStarterView as Markdown

A horizontal or vertical scale that shows where a value sits against its limits: the scale in grey, the normal operating band in a darker grey, the zones beyond the low and high limits (L, H) and beyond the low-low and high-high limits (LL, HH), a pointer for the value and, when you give one, a marker for the setpoint. The readout at the top right shows the value and its unit.

It stays grey while the value is normal. Only when the value is beyond a limit does the zone it is in, the pointer and the readout take a colour: amber beyond L or H, red beyond LL or HH. This is the indicator’s own drawing: the alarm engine decides the alarms.

A Bad, Uncertain or stale value is never drawn as good: the pointer is drawn hollow (dashed for Bad and Uncertain, dotted for a value that is not current), a Bad value hatches the object and strikes through the readout, and the quality marker names the tag, its quality and its age. Before the first value there is no pointer and the readout shows a dash. Display only: it writes nothing. See High-performance displays.

A moving analog indicator: Air header pressure 6.85 bar, the pointer inside the grey normal band, the setpoint marker just above it.

Palette Not in the palette
JSON type AnalogIndicator
Name in the inspector Moving analog indicator
Size drawn from width and height; a resize changes them
Added by designer_sa_widgets.js
Shown as Key Type Unit Default Allowed values What it does
Name label Text "Indicator" The name drawn at the top left of the object (and shown in the layers list and on a phone row).
Value tag pvTag Tag path (read) — The tag whose value the pointer and the readout show, with its quality. The object reads it itself (it is not a Bind tab binding).
Setpoint tag spTag Tag path (read) — Optional: a tag drawn as the setpoint marker. Its quality counts like the value’s: a Bad setpoint makes the object look degraded.
Fixed setpoint (without a setpoint tag) setpoint Number — Optional: a fixed setpoint marker, used when no setpoint tag is set.
Orientation orientation Choice "horizontal" horizontal
vertical
Horizontal (low on the left) or vertical (low at the bottom).
Scale minimum min Number — Value at the start of the scale. Empty = 0. Inspector hint: Empty = 0
Scale maximum max Number — Value at the end of the scale. Empty = 100. Inspector hint: Empty = 100
Decimals shown decimals Number — min 0, max 6, step 1 Decimals of the readout, 0 to 6. Empty: chosen from the span of the scale (2 up to a span of 10, 1 up to 100, else 0).
Unit unit Text — Engineering unit shown after the value (%, bar, degC). Display only: it does not convert anything.
Alarm limits limitsSource Choice "alarms" alarms
manual
none
Where the limits come from. alarms (default): the value tag’s alarm definitions (LOW_LOW, LOW, HIGH, HIGH_HIGH); a limit the tag has no alarm for is taken from the hand-set limit of the same kind. manual: the four hand-set limits. none: no limits, no zones.
Low-low limit (LL) limitLL Number — Hand-set low-low limit (manual), or the fallback when the tag has no LOW_LOW alarm (alarms).
Low limit (L) limitL Number — Hand-set low limit (manual), or the fallback when the tag has no LOW alarm (alarms).
High limit (H) limitH Number — Hand-set high limit (manual), or the fallback when the tag has no HIGH alarm (alarms).
High-high limit (HH) limitHH Number — Hand-set high-high limit (manual), or the fallback when the tag has no HIGH_HIGH alarm (alarms).
Normal band from normalLow Number — Start of the normal operating band. Empty: the low limit (L), else LL. Inspector hint: Empty: the low limit (L).
Normal band to normalHigh Number — End of the normal operating band. Empty: the high limit (H), else HH. Inspector hint: Empty: the high limit (H).
— width Number 280 Width of the object. Default 280.
— height Number 90 Height of the object. Default 90.
X x Number px — Horizontal position of the object’s top-left corner on the screen, in screen pixels from the left edge.
Y y Number px — Vertical position of the object’s top-left corner, in screen pixels from the top edge.
Rotation rotation Number ° — Rotation of the object, clockwise, in degrees.
Opacity opacity Number — 0 (invisible) to 1 (opaque). An object disabled by an interlock is drawn at 0.45 whatever this says.
States states Object — This object’s own state styles (normal, hover, pressed, on, disabled, bad, locked, unconfigured), edited in the inspector’s States section. Visual only. Empty: the project’s state styles.
State family styleFamily Text — The state family whose project styles apply (button, input, toggle, selector, faceplateButton, default). Empty: the family of the object’s type.

The object reads these tags through its own properties, with their quality: pvTag, spTag. A Bad or Uncertain value is marked on the object (see Quality below), never drawn as good.

The Bind tab ties a property to a tag or an expression: a tag binding takes the tag’s value, an expression binding computes one (see the expression language), optionally through a map, format or script transform. The targets the Bind tab offers for this object:

Bind tab target Key What the bound value does
Fill Color fill Sets the fill colour from the value (a colour text such as #22c55e, or a colour mapped by a map transform).
Stroke / Border Color stroke Sets the outline colour from the value.
Opacity (0.0 - 1.0) opacity Sets the opacity from the value (0 to 1).
Visibility (Boolean) visible Shows the object when the value is true or non-zero, hides it otherwise.
Rotation (°) rotation Rotates the object by the value, in degrees.
Scale / Pulse scale Scales the object by the value (1 = drawn size).
Text / Label text Replaces the text drawn with the value, formatted by the binding’s format. On a Text object a number is followed by the object’s unit, as with the Value target (never a word). A Bad value shows a dash.
Value (Numeric) value Shows the value as the object’s readout (with the unit and decimals). A Bad value shows a dash.

The Cond tab adds rules evaluated on every value change: Visibility (show or hide, by condition or role), Color & Fill (colour bands, alarm blinking), Position and Size & Fill (motion and level mapped from a value), Rotation (angle or continuous spin; an empty input range is 0 to 100 and empty angles are -135° to 135°, while 0 is a value), Security & Touch (the interlock: a disable condition, the role required, what happens when the interlock reads a Bad value) and Text & Value (formatted text). A condition that reads a Bad value is never applied as if the value were good: visibility shows the object marked Bad, colours go neutral grey, motion stays where it is, text shows a dash.

Any object can carry a click or tap action (the Action tab, or Full Dialog…). A write action whose tag, value or target is missing is not configured: the inspector says so and the operator’s press does nothing (unconfigured means disabled). Navigation actions write nothing and ask no confirmation. On touch screens only a deliberate tap runs an action: a swipe or a pinch that ends on the object never does. Action types:

Action Key (action.type) What it does
Set tag to 1 set_1 Writes 1 to the action’s tag.
Set tag to 0 set_0 Writes 0 to the action’s tag.
Toggle tag value toggle Writes the opposite of the tag’s LIVE value: 0 when it is not 0, 1 when it is 0. When the live value is unknown, not Good or not a number, nothing is written and the operator is told why; when it changes while the operator confirms or signs, nothing is written either.
Set tag to 1 on press and to 0 on release momentary_1_0 Writes 1 while pressed and 0 on release (hold to run). On touch, the press counts only after the finger is held still; the release is always sent. A held press is also released when the browser window loses focus or the page is hidden, and in the designer when a drag or a resize of the object starts.
Set tag to 0 on press and to 1 on release momentary_0_1 Writes 0 while pressed and 1 on release. Released in the same cases as the 1/0 momentary.
Write custom value write_val Writes the number in write_value.
Run script run_command Runs a client script with the scripting API (system.tag.write, system.nav.openPopup…). Ctrl+Space completes the API.
Navigate to page / screen navigate Opens another screen, optionally with parameters or a parameter set.
Open popup screen open_popup Opens a screen in a popup window: modal or not, centred, next to the object or at a fixed position, with parameters.
Close popup close_popup Closes the popup the object is in, or the popup with the given id.
Open dock open_dock Opens a screen docked to an edge of the runtime (top, bottom, left, right).
Close dock close_dock Closes the dock on that edge.
Open or close dock toggle_dock Opens or closes the dock on that edge.
Back nav_back Goes back to the previous screen.
Forward nav_forward Goes forward again after Back.
Home screen nav_home Opens the project’s home screen.
Open downtime panel open_downtime Opens the operator runtime’s Downtime panel (OEE and downtime, Pro and Enterprise), optionally on one machine (its machine id). Navigation only: nothing is written to a tag or a machine. A machine the operator may not read is not shown; where the panel is not available, a notice says so. Offered in the designer only when the licence includes OEE and downtime.

States. An object’s look follows its state: normal, hover, pressed, on, disabled, bad (quality), locked (role) and unconfigured. The project’s state styles (opened from an object’s States section, or from the Project manager’s Operator runtime section) give each family of objects its colours per state, and the inspector’s States section overrides them for one object (stored in props.states). States are visual only: whether an object can be operated is decided by its interlock, the user’s rights and the server.

This object belongs to the state family default (all other objects): disabled (an interlock dims it to 0.45 opacity), bad (a tag it reads is Bad) and locked (missing role) apply when the object has conditions or an action; the other states apply to objects that are operated.

Screen parameters. On a screen with parameters, {Name} in any text of the object (tag paths of bindings and actions, expressions, conditions, interlocks, the confirmation tag, texts) is replaced by the parameter’s value when the screen opens, so one screen serves many pieces of equipment ({Pump}/Running). See screen parameters.

Quality. This high-performance object draws its own quality marker, at the top next to its name, in the colours of every other marker: a red x for a Bad value or no value yet, a blue lock for a tag the signed-in account may not read, an amber ? for Uncertain, a grey marker for stale. The lock shows only when every Bad tag of the object is not readable: a device fault keeps the red x. The object shows one marker, for the worst state of its value and setpoint tags, and the marker’s tooltip lists every tag, its quality and its age, with Not readable for this account for a refused tag. A value that is not readable is never shown as a number: there is no pointer and the readout shows a dash. See show bad and stale values.

Comments. In the studio, right-click the object and choose Add comment to start a design-review thread on it; a numbered pin marks objects with open threads (Starter, Pro and Enterprise). Pins are shown in the designer only, never in the runtime. See review screens before deploy.

Tank TK-103’s level on 0 to 100 %, with the limits taken from the tag’s own alarms: when the level passes the high alarm, the high zone, the pointer and the readout turn amber.

  1. Place a Moving analog indicator from Widgets (Situational awareness); Name TK-103 level.
  2. Value tag Plant/Processing/Tanks/TK103/Level; unit %; scale 0 to 100.
  3. Alarm limits: From the value tag’s alarms. The tag has HIGH and HIGH_HIGH alarms at 90 and 95 %; set Low limit (L) 10 by hand for the side without an alarm.

A tank level against its alarm limits

91.6 %: the pointer is in the amber high zone; below 90 % the object is grey again.
The moving analog indicator as saved in the screen (JSON)
{
"type": "AnalogIndicator",
"props": {
"label": "TK-103 level",
"pvTag": "Plant/Processing/Tanks/TK103/Level",
"min": 0,
"max": 100,
"unit": "%",
"limitsSource": "alarms",
"limitL": 10
}
}