One use of a reusable component (a set of objects saved once in the project, in data/studio/components). A component declares parameters ({Pump}, {Name}); each instance gives them values, so one pump tile serves every pump. Place an instance from the component library, fill in its parameters in Configure Component Instance, and the designer compiles the component’s objects into the instance (its children). A component can also be bound to a UDT: the instance then takes a UDT root path instead of parameters. In the designer the instance has a dashed border and a TEMPLATE or UDT badge; operators see only the component’s own objects.

A new installation has no component: components are the engineer’s own.

Component instance in the operator runtime

Palette Placed from the component library (Reusable Faceplates), not from the object palette.
JSON type CustomWidgetInstance
Name in the inspector Component
Size drawn from width and height; a resize changes them
Shown as Key Type Unit Default Allowed values What it does
— width Number 260 Width of the instance, from the component.
— height Number 200 Height of the instance, from the component.
— label Text "COMPONENT INSTANCE" The instance’s name in the layers list; also shown in the designer badge when no TagPrefix parameter is set.
Component templateId Text — The id of the component this instance uses.
Mode instanceMode Text "manual" manual
udt
manual: parameters typed per instance. udt: the component is bound to a UDT and the instance takes a UDT root path.
Parameters instanceParams Object object, see below The values of the component’s parameters for this instance, for example {“Pump”: “Plant/Processing/Pumps/P101”, “Name”: “P-101”}. A parameter without a value takes the component’s default.
UDT udtId Text — UDT mode: the UDT the component is bound to (from the component).
UDT root path udtRootPath Text — UDT mode: the tag folder of this instance’s UDT (Plant/Processing/Pumps/P101); the component’s members read under it.
— fill Colour "transparent" Kept on the instance, not drawn: the component’s own objects draw it.
— stroke Colour "transparent" Kept on the instance, not drawn.
X x Number px — Horizontal position of the object’s top-left corner on the screen, in screen pixels from the left edge.
Y y Number px — Vertical position of the object’s top-left corner, in screen pixels from the top edge.
Rotation rotation Number ° — Rotation of the object, clockwise, in degrees.
Opacity opacity Number — 0 (invisible) to 1 (opaque). An object disabled by an interlock is drawn at 0.45 whatever this says.
States states Object — This object’s own state styles (normal, hover, pressed, on, disabled, bad, locked, unconfigured), edited in the inspector’s States section. Visual only. Empty: the project’s state styles.
State family styleFamily Text — The state family whose project styles apply (button, input, toggle, selector, faceplateButton, default). Empty: the family of the object’s type.

Bindings, conditions, actions and interlocks of the component’s objects work in every instance, with the parameters replaced. Screen interlocks and write limits on buttons and inputs inside instances are found and enforced by the server like those on the screen itself. When the component changes, its instances are compiled again from it.

The Bind tab ties a property to a tag or an expression: a tag binding takes the tag’s value, an expression binding computes one (see the expression language), optionally through a map, format or script transform. The targets the Bind tab offers for this object:

Bind tab target Key What the bound value does
Fill Color fill Sets the fill colour from the value (a colour text such as #22c55e, or a colour mapped by a map transform).
Stroke / Border Color stroke Sets the outline colour from the value.
Opacity (0.0 - 1.0) opacity Sets the opacity from the value (0 to 1).
Visibility (Boolean) visible Shows the object when the value is true or non-zero, hides it otherwise.
Rotation (°) rotation Rotates the object by the value, in degrees.
Scale / Pulse scale Scales the object by the value (1 = drawn size).
Text / Label text Replaces the text drawn with the value, formatted by the binding’s format. On a Text object a number is followed by the object’s unit, as with the Value target (never a word). A Bad value shows a dash.
Value (Numeric) value Shows the value as the object’s readout (with the unit and decimals). A Bad value shows a dash.

The Cond tab adds rules evaluated on every value change: Visibility (show or hide, by condition or role), Color & Fill (colour bands, alarm blinking), Position and Size & Fill (motion and level mapped from a value), Rotation (angle or continuous spin; an empty input range is 0 to 100 and empty angles are -135° to 135°, while 0 is a value), Security & Touch (the interlock: a disable condition, the role required, what happens when the interlock reads a Bad value) and Text & Value (formatted text). A condition that reads a Bad value is never applied as if the value were good: visibility shows the object marked Bad, colours go neutral grey, motion stays where it is, text shows a dash.

Any object can carry a click or tap action (the Action tab, or Full Dialog…). A write action whose tag, value or target is missing is not configured: the inspector says so and the operator’s press does nothing (unconfigured means disabled). Navigation actions write nothing and ask no confirmation. On touch screens only a deliberate tap runs an action: a swipe or a pinch that ends on the object never does. Action types:

Action Key (action.type) What it does
Set tag to 1 set_1 Writes 1 to the action’s tag.
Set tag to 0 set_0 Writes 0 to the action’s tag.
Toggle tag value toggle Writes the opposite of the tag’s LIVE value: 0 when it is not 0, 1 when it is 0. When the live value is unknown, not Good or not a number, nothing is written and the operator is told why; when it changes while the operator confirms or signs, nothing is written either.
Set tag to 1 on press and to 0 on release momentary_1_0 Writes 1 while pressed and 0 on release (hold to run). On touch, the press counts only after the finger is held still; the release is always sent. A held press is also released when the browser window loses focus or the page is hidden, and in the designer when a drag or a resize of the object starts.
Set tag to 0 on press and to 1 on release momentary_0_1 Writes 0 while pressed and 1 on release. Released in the same cases as the 1/0 momentary.
Write custom value write_val Writes the number in write_value.
Run script run_command Runs a client script with the scripting API (system.tag.write, system.nav.openPopup…). Ctrl+Space completes the API.
Navigate to page / screen navigate Opens another screen, optionally with parameters or a parameter set.
Open popup screen open_popup Opens a screen in a popup window: modal or not, centred, next to the object or at a fixed position, with parameters.
Close popup close_popup Closes the popup the object is in, or the popup with the given id.
Open dock open_dock Opens a screen docked to an edge of the runtime (top, bottom, left, right).
Close dock close_dock Closes the dock on that edge.
Open or close dock toggle_dock Opens or closes the dock on that edge.
Back nav_back Goes back to the previous screen.
Forward nav_forward Goes forward again after Back.
Home screen nav_home Opens the project’s home screen.
Open downtime panel open_downtime Opens the operator runtime’s Downtime panel (OEE and downtime, Pro and Enterprise), optionally on one machine (its machine id). Navigation only: nothing is written to a tag or a machine. A machine the operator may not read is not shown; where the panel is not available, a notice says so. Offered in the designer only when the licence includes OEE and downtime.

States. An object’s look follows its state: normal, hover, pressed, on, disabled, bad (quality), locked (role) and unconfigured. The project’s state styles (opened from an object’s States section, or from the Project manager’s Operator runtime section) give each family of objects its colours per state, and the inspector’s States section overrides them for one object (stored in props.states). States are visual only: whether an object can be operated is decided by its interlock, the user’s rights and the server.

This object belongs to the state family default (all other objects): disabled (an interlock dims it to 0.45 opacity), bad (a tag it reads is Bad) and locked (missing role) apply when the object has conditions or an action; the other states apply to objects that are operated.

Screen parameters. On a screen with parameters, {Name} in any text of the object (tag paths of bindings and actions, expressions, conditions, interlocks, the confirmation tag, texts) is replaced by the parameter’s value when the screen opens, so one screen serves many pieces of equipment ({Pump}/Running). See screen parameters.

Quality. When a value the object reads is Bad, not readable, Uncertain or stale, the object is marked: a red x and a grey veil (or hatching, per the project’s quality style) for Bad or no connection, a blue lock for a tag the signed-in account may not read, an amber ? for Uncertain, a dashed outline for stale. A tag that is not readable is greyed as Bad and its value is never shown as good. The lock shows only when every Bad tag of the object is not readable: a device fault keeps the red x. Each object shows one marker, for its worst state, and markers that would overlap merge into one, drawn on the largest object with the worst state of all. The marker’s tooltip lists every tag, its quality and its age. A Bad value is never drawn as a good one. See show bad and stale values.

Comments. In the studio, right-click the object and choose Add comment to start a design-review thread on it; a numbered pin marks objects with open threads (Starter, Pro and Enterprise). Pins are shown in the designer only, never in the runtime. See review screens before deploy.

The component Pump tile (parameters Pump and Name) shows a pump’s name, running lamp and speed. Two instances show P-101 (running, 78 %) and P-102 (stopped).

  1. Build the tile once (a rectangle, a text {Name}, a lamp with a condition on tag('{Pump}/Running'), a text bound to {Pump}/Speed), select it and save it as a component with the parameters Pump and Name.
  2. Place it twice from the component library.
  3. Instance 1: Pump = Plant/Processing/Pumps/P101, Name = P-101. Instance 2: Plant/Processing/Pumps/P102, P-102.

One pump tile, two pumps

Two instances of the same component.
The component instance as saved in the screen (JSON)
{
"type": "CustomWidgetInstance",
"props": {
"templateId": "docs_pump_tile",
"instanceMode": "manual",
"instanceParams": {
"Pump": "Plant/Processing/Pumps/P101",
"Name": "P-101"
},
"label": "P101_TILE"
}
}