Skip to content

Text entry

eaxScadaReferenceStarterView as Markdown

A text field for a String tag: a batch name, a product code, an operator note to a device. Sent with Enter or OK. Only tags that take text accept it (a String driver tag mapping on OPC UA, MQTT with JSON, or the NATS bridge); the server checks the length and the allowed texts. Text values are not read back: after a write the field shows Sent.

Text entry in the operator runtime

Palette Not in the palette
JSON type TextEntry
Name in the inspector Text entry
Size drawn from width and height; a resize changes them
Added by designer_inputs.js
Shown as Key Type Unit Default Allowed values What it does
Tag written tagPath Tag path (written) — The tag the object writes. Required: without a tag the object is disabled on the operator’s screen (unconfigured means disabled). Inspector hint: Required: without a tag the object is disabled.
Caption caption Text — The caption above the field. Empty: the last part of the tag path. Translatable with a t: key.
Maximum length maxLength Number 64 min 1, max 256, step 1 The longest text accepted. The server also applies the tag’s own limit (default 256).
Placeholder placeholder Text — Grey hint text shown while the field is empty.
Confirmation confirmation Choice "none" none None
require Confirm (dialog)
esignature Electronic signature
variable Ask for confirmation when a tag is not 0
none: send at once (a large change still asks). require: the operator confirms in a dialog. esignature: the signed-in operator signs with their password; the dialog shows what is signed (“Operator input: <caption>”) and pre-fills nothing. variable (Ask for confirmation when a tag is not 0): a confirmation is asked while the tag in confirmation_var is not 0. The server requires the same of every writer of this tag. Inspector hint: The server requires the same from every writer of this tag.
Ask for confirmation when this tag is not 0 confirmation_var Tag path (read) — With Ask for confirmation when this tag is not 0: the tag that decides whether a confirmation is asked. It does NOT block the write: after a yes the value is sent. To block a write, use an interlock (Cond tab, Security & Touch, disable condition), which the server enforces. Inspector hint: Only asks: after a yes the value is sent. It does NOT block the write. To block it, use an interlock: the interaction condition’s Disable condition (Conditioning tab), enforced by the server.
Confirmation message confirmMessage Text — The confirmation question, also shown above the signature prompt. Empty: a sentence naming the tag and the value. Translatable with a t: key.
Read-only (shows the value, sends nothing) readOnly Yes / no — Shows the value with its quality and sends nothing: the field cannot be edited.
Send when leaving the field (not recommended) writeOnBlur Yes / no — Sends the typed value when the field loses focus. Not recommended: a value can then be sent by a tap elsewhere. Off: the operator presses Enter or Set.
Background fill Colour — Background colour of the field. Empty: the theme’s.
Text colour textColor Colour — Text colour. Empty: the theme’s.
Border stroke Colour — Border colour. Empty: the theme’s.
Display mode tag themeTag Tag path (read) — Optional: the tag of the screen’s own display mode (a vehicle display, a control room with a day and a night mode). 1 draws the object’s dark look, 0 its light look; a missing or Bad value keeps the current look. Empty: the runtime theme. Inspector hint: A screen with its own display mode (1 dark, 0 light). Empty: the runtime look.
— width Number 240 Width of the field.
— height Number 52 Height of the field.
— keyboard Text "inherit" Which on-screen keyboard opens on a touch panel: inherit (the screen’s, then the project’s setting), auto (on touch only), numeric, keypad with letters, full keyboard, or never (the system keyboard).
X x Number px — Horizontal position of the object’s top-left corner on the screen, in screen pixels from the left edge.
Y y Number px — Vertical position of the object’s top-left corner, in screen pixels from the top edge.
Rotation rotation Number ° — Rotation of the object, clockwise, in degrees.
Opacity opacity Number — 0 (invisible) to 1 (opaque). An object disabled by an interlock is drawn at 0.45 whatever this says.
States states Object — This object’s own state styles (normal, hover, pressed, on, disabled, bad, locked, unconfigured), edited in the inspector’s States section. Visual only. Empty: the project’s state styles.
State family styleFamily Text — The state family whose project styles apply (button, input, toggle, selector, faceplateButton, default). Empty: the family of the object’s type.

The object reads these tags through its own properties, with their quality: tagPath, confirmation_var, themeTag. A Bad or Uncertain value is marked on the object (see Quality below), never drawn as good.

The Bind tab ties a property to a tag or an expression: a tag binding takes the tag’s value, an expression binding computes one (see the expression language), optionally through a map, format or script transform. The targets the Bind tab offers for this object:

Bind tab target Key What the bound value does
Display Text / Value text Replaces the text drawn with the value, formatted by the binding’s format. On a Text object a number is followed by the object’s unit, as with the Value target (never a word). A Bad value shows a dash.
Font Size (px) fontSize Sets the text size from the value, in pixels (text objects).
Text Color fill Sets the fill colour from the value (a colour text such as #22c55e, or a colour mapped by a map transform).
Stroke / Border Color stroke Sets the outline colour from the value.
Opacity (0.0 - 1.0) opacity Sets the opacity from the value (0 to 1).
Visibility (Boolean) visible Shows the object when the value is true or non-zero, hides it otherwise.
Rotation (°) rotation Rotates the object by the value, in degrees.
Scale / Pulse scale Scales the object by the value (1 = drawn size).
Value (Numeric) value Shows the value as the object’s readout (with the unit and decimals). A Bad value shows a dash.

The Cond tab adds rules evaluated on every value change: Visibility (show or hide, by condition or role), Color & Fill (colour bands, alarm blinking), Position and Size & Fill (motion and level mapped from a value), Rotation (angle or continuous spin; an empty input range is 0 to 100 and empty angles are -135° to 135°, while 0 is a value), Security & Touch (the interlock: a disable condition, the role required, what happens when the interlock reads a Bad value) and Text & Value (formatted text). A condition that reads a Bad value is never applied as if the value were good: visibility shows the object marked Bad, colours go neutral grey, motion stays where it is, text shows a dash.

Commands. This object sends commands to equipment. Before it writes:

  • Confirmation and e-signature. Set Confirmation to ask the operator to confirm, or to sign with their password and a reason (electronic signature). The signer is always the signed-in user; the dialog never pre-fills a signer, a reason or a password. The server requires the same confirmation from every writer of the tag.
  • Limits. Minimum, maximum and step (or the tag’s write range) are enforced by the server for every writer; the screen’s own check only saves a round trip. A limit read from a tag that is missing or not Good refuses every write.
  • Interlocks. A Disabled condition (buttons) or the disable condition of the Security & Touch condition dims the object and blocks the press while it is true. When the interlock is a simple tag comparison ({Plant/Processing/Pumps/P101/Interlock} == 1), the server also refuses the write from every writer (409 interlocked); other interlocks are screen only, and the designer says which. If the interlock reads a Bad value the object is disabled, unless If the interlock reads a Bad value is set to Allow (for stop, trip and emergency commands, so a failed sensor never stops an operator stopping a machine). See screen interlocks.
  • Unconfigured means disabled. Without its tag the object is drawn as not configured and sends nothing.
  • Deliberate taps. On touch, only a still, short tap operates it.

A real safety interlock belongs in the PLC: screen and server interlocks only stop writes that go through eaxScada.

Any object can carry a click or tap action (the Action tab, or Full Dialog…). A write action whose tag, value or target is missing is not configured: the inspector says so and the operator’s press does nothing (unconfigured means disabled). Navigation actions write nothing and ask no confirmation. On touch screens only a deliberate tap runs an action: a swipe or a pinch that ends on the object never does. Action types:

Action Key (action.type) What it does
Set tag to 1 set_1 Writes 1 to the action’s tag.
Set tag to 0 set_0 Writes 0 to the action’s tag.
Toggle tag value toggle Writes the opposite of the tag’s LIVE value: 0 when it is not 0, 1 when it is 0. When the live value is unknown, not Good or not a number, nothing is written and the operator is told why; when it changes while the operator confirms or signs, nothing is written either.
Set tag to 1 on press and to 0 on release momentary_1_0 Writes 1 while pressed and 0 on release (hold to run). On touch, the press counts only after the finger is held still; the release is always sent. A held press is also released when the browser window loses focus or the page is hidden, and in the designer when a drag or a resize of the object starts.
Set tag to 0 on press and to 1 on release momentary_0_1 Writes 0 while pressed and 1 on release. Released in the same cases as the 1/0 momentary.
Write custom value write_val Writes the number in write_value.
Run script run_command Runs a client script with the scripting API (system.tag.write, system.nav.openPopup…). Ctrl+Space completes the API.
Navigate to page / screen navigate Opens another screen, optionally with parameters or a parameter set.
Open popup screen open_popup Opens a screen in a popup window: modal or not, centred, next to the object or at a fixed position, with parameters.
Close popup close_popup Closes the popup the object is in, or the popup with the given id.
Open dock open_dock Opens a screen docked to an edge of the runtime (top, bottom, left, right).
Close dock close_dock Closes the dock on that edge.
Open or close dock toggle_dock Opens or closes the dock on that edge.
Back nav_back Goes back to the previous screen.
Forward nav_forward Goes forward again after Back.
Home screen nav_home Opens the project’s home screen.
Open downtime panel open_downtime Opens the operator runtime’s Downtime panel (OEE and downtime, Pro and Enterprise), optionally on one machine (its machine id). Navigation only: nothing is written to a tag or a machine. A machine the operator may not read is not shown; where the panel is not available, a notice says so. Offered in the designer only when the licence includes OEE and downtime.

States. An object’s look follows its state: normal, hover, pressed, on, disabled, bad (quality), locked (role) and unconfigured. The project’s state styles (opened from an object’s States section, or from the Project manager’s Operator runtime section) give each family of objects its colours per state, and the inspector’s States section overrides them for one object (stored in props.states). States are visual only: whether an object can be operated is decided by its interlock, the user’s rights and the server.

This object belongs to the state family input (inputs): normal, hover, pressed, disabled (interlock or read-only), bad (the value or an interlock is Bad), locked (missing role), unconfigured (no tag).

Text style and fonts. Choose a project text style (Text style in the inspector of a text, button, input or alarm object) instead of fonts and sizes per object, so a change in one place restyles every screen; font settings on the object still apply on top of the style. Fonts come from the font picker: the built-in fonts and the fonts uploaded to the project. See fonts and text styles.

Languages. A text written as a key, t:pump.start|Start pump, is shown in the operator’s language, with the text after | as the fallback. Project > Translations > Make translatable turns the literal texts of your screens into keys. See translate your project.

Screen parameters. On a screen with parameters, {Name} in any text of the object (tag paths of bindings and actions, expressions, conditions, interlocks, the confirmation tag, texts) is replaced by the parameter’s value when the screen opens, so one screen serves many pieces of equipment ({Pump}/Running). See screen parameters.

Quality. When a value the object reads is Bad, not readable, Uncertain or stale, the object is marked: a red x and a grey veil (or hatching, per the project’s quality style) for Bad or no connection, a blue lock for a tag the signed-in account may not read, an amber ? for Uncertain, a dashed outline for stale. A tag that is not readable is greyed as Bad and its value is never shown as good. The lock shows only when every Bad tag of the object is not readable: a device fault keeps the red x. Each object shows one marker, for its worst state, and markers that would overlap merge into one, drawn on the largest object with the worst state of all. The marker’s tooltip lists every tag, its quality and its age. A Bad value is never drawn as a good one. See show bad and stale values.

On-screen keyboard. On a touch panel, a field opens the on-screen keypad or keyboard (object setting On-screen keyboard, then the screen’s and the project’s). The keypad refuses values out of range, off-step or malformed before anything is sent, never writes per keystroke and never pre-fills anything; the write still goes through the confirmation and the server checks.

Comments. In the studio, right-click the object and choose Add comment to start a design-review thread on it; a numbered pin marks objects with open threads (Starter, Pro and Enterprise). Pins are shown in the designer only, never in the runtime. See review screens before deploy.

The batch name of line 1, at most 32 characters, signed by the operator (electronic signature) because it ends up in the batch record.

  1. Place Text entry from Operator inputs.
  2. Tag written the String tag of the line’s batch name; Maximum length 32; Placeholder e.g. B-2026-001.
  3. Confirmation Electronic signature; Confirmation message Batch name for line 1: the meaning recorded with the signature.

A batch name with an e-signature

The text field with its placeholder. The test server has no String tag (eaxTags hold numbers), so the field has no current value and shows the quality marker.
The text entry as saved in the screen (JSON)
{
"type": "TextEntry",
"props": {
"tagPath": "Plant/Processing/Lines/L1/BatchName",
"caption": "Batch name",
"maxLength": 32,
"placeholder": "e.g. B-2026-001",
"confirmation": "esignature",
"confirmMessage": "Batch name for line 1"
}
}