Alarm classes, history and counts API

eaxScadaReferenceStarterProEnterpriseView as Markdown

Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.

Three server APIs sit behind the alarm objects on screens:

  • /api/alarms/classes: how each alarm looks and sounds;
  • /api/alarms/history and /api/alarms/history.csv: the ISA-18.2 journal;
  • /api/alarms/counts: the standing alarms, counted for counters and annunciator tiles;
  • /api/alarms/active: the standing alarms, with the alarm list card’s filters.

Every route needs a signed-in user. Each user sees only the alarms they are allowed to see (see Visibility).


An alarm is drawn according to three things:

Dimension Values
Class The alarm’s category: Safety, Process, Environmental, Equipment, Diagnostic, or any category of your own. An unknown category uses the document’s default_class.
Priority CRITICAL, HIGH, MEDIUM, LOW, INFO.
Display state UNACK_ALARM, ACK_ALARM, RTN_UNACK, SHELVED, SUPPRESSED (alarm evaluation is stopped), NORMAL (history rows only).

An alarm definition can hold a priority that is not one of the five, for example from an older project or an import. Every surface reads such a priority the same way, and never lower than an earlier release showed it:

Priority in the definition Shown, counted and filtered as
CRITICAL, HIGH, MEDIUM, LOW, INFO (any case, spaces trimmed) itself
HIGHEST, URGENT CRITICAL
any other name (WARNING, WARN, MINOR, NOTICE, an unknown name), empty or missing HIGH

The rule is the server’s, and every display follows it: the alarm counts (GET /api/alarms/counts) and the counters and annunciator tiles built on them, the alarm classes’ colours and sounds, the priority filter of GET /api/alarms/active, the dashboard alarm list card, the alarm banner and summary objects (their priority filter, order and counters), the classic dashboard alarm summary, the phone view’s alarm list and status level, the colour of an object in the 3D and isometric views, and the System Health alarm counts with the eaxscada_alarms metric.

Each class × priority × state cell gives:

  • the text, background and border colours;
  • a blink background, used for the “off” phase;
  • blink: none, slow (0.5 Hz) or fast (2 Hz);
  • bold and italic;
  • an icon and a short label;
  • for the unacknowledged states only, a sound (none, horn, chime, beep or siren), its repeat (once, until_silenced or until_ack) and its volume (0 to 1).

A sound plays only if the alarm definition has sound_alert on.

The classes only control how alarms look. They never change which alarms are listed, their order, or how they are acknowledged.

The project’s document overrides one of two built-in profiles:

Base Look Used by
isa101 ISA-101 colours: CRITICAL red #B91C1C, HIGH orange #C2410C, MEDIUM amber #CA8A04, LOW blue #0369A1, INFO slate #475569. A returned, unacknowledged alarm has a light background with a border in its priority colour. Sounds: horn for CRITICAL (until acknowledged) and HIGH (until silenced), chime for MEDIUM, beep for LOW, none for INFO. new projects
legacy The alarm banner’s colours before classes existed: CRITICAL dark red, other priorities dark amber, a returned alarm cyan. One horn for every priority. projects that already had alarms when they were upgraded

The first start after the upgrade writes data/alarms/classes.json with the chosen base, so the look never changes by itself afterwards.

In both profiles, an unacknowledged alarm blinks fast and a returned unacknowledged alarm blinks slowly; INFO alarms do not blink. Every text colour has a contrast of at least 4.5:1 against its background.

The document is stored in data/alarms/classes.json. On an HA cluster it is replicated with the alarm definitions.

{
"version": 1,
"base": "isa101",
"priorities": {
"HIGH": { "*": { "label": "P2" }, "UNACK_ALARM": { "bg": "#C2410C" }, "sound": { "sound": "horn", "repeat": "until_silenced" } }
},
"states": { "SHELVED": { "bg": "#64748B", "fg": "#FFFFFF" } },
"classes": {
"Environmental": {
"label": "Environment",
"overrides": { "*": { "UNACK_ALARM": { "bg": "#065F46", "fg": "#FFFFFF" } } },
"sound": { "*": { "sound": "chime" } }
}
},
"default_class": "Process",
"blink_respects_reduced_motion": false,
"safety_critical_steady_allowed": false
}
  • "*" stands for every priority or every state.
  • states styles only SHELVED, SUPPRESSED and NORMAL.
  • blink_respects_reduced_motion: when it is true and the operator’s system asks for reduced motion, a blinking cell is shown steady with a high-contrast marker. By default alarms always blink.
  • safety_critical_steady_allowed: see Built-in safety alarms.

Resolution. For each cell, these layers are applied in order. A later layer overrides an earlier one, member by member:

  1. the base profile;
  2. priorities[priority]["*"], then priorities[priority][state];
  3. states[state];
  4. the class overrides ["*"]["*"], ["*"][state], [priority]["*"], then [priority][state].

The sound is resolved the same way: the class’s sound for the priority, otherwise the class’s "*" sound, otherwise the priority’s sound, otherwise the base profile’s.

The resolver never returns an unreadable cell. Invalid colours, or a text colour equal to its background, fall back to the base profile’s colours.

Layered stackHow the look of an alarm is resolved
How the look of an alarm is resolvedeaxScada builds the look of one alarm from five layers, top to bottom: the base profile, the priority, the state, the alarm class, and the readability floor. Each layer overrides the one above it member by member; a member it leaves empty keeps the earlier value. The sound is resolved apart, for the unacknowledged states only.1Base profileisa101, or legacy forupgraded projects2Prioritypriorities: the priority's"*", then its state3Statestates: three statesonly4Alarm classthe class overrides,from the widest to thenarrowest5Never unreadableapplied last, whateverthe document saysBase cellfor the priority and the statepriorities[priority]"*" first, then [state]states[state]SHELVED, SUPPRESSED, NORMALClass overrides, in order["*"]["*"], ["*"][state],[priority]["*"],[priority][state]Readable colourselse the base coloursThe alarmits class, priorityand display state;unknown: the defaultsSound, in orderunacknowledged only:base, priority sound,class "*" sound,class priority soundAlarm as drawncolours, blink, label,icon, soundunacknowledgedsound, repeat, volume
The more specific setting wins, but the result is never unreadable: the floor at the bottom applies whatever the document says.
  • Service or process
  • Check or decision
  • Data or telemetry
Read as text

eaxScada builds the look of one alarm from five layers, top to bottom: the base profile, the priority, the state, the alarm class, and the readability floor. Each layer overrides the one above it member by member; a member it leaves empty keeps the earlier value. The sound is resolved apart, for the unacknowledged states only.

Parts

  • Base profile (layer 1): isa101, or legacy for upgraded projects
  • Priority (layer 2): priorities: the priority's "*", then its state
  • State (layer 3): states: three states only
  • Alarm class (layer 4): the class overrides, from the widest to the narrowest
  • Never unreadable (layer 5): applied last, whatever the document says
  • Base cell (service or process): for the priority and the state
  • priorities[priority] (service or process): "*" first, then [state]
  • states[state] (service or process): SHELVED, SUPPRESSED, NORMAL
  • Class overrides, in order (service or process): ["*"]["*"], ["*"][state], [priority]["*"], [priority][state]
  • Readable colours (check or decision): else the base colours
  • The alarm (service or process): its class, priority and display state; unknown: the defaults
  • Sound, in order (service or process): unacknowledged only: base, priority sound, class "*" sound, class priority sound
  • Alarm as drawn (service or process): colours, blink, label, icon, sound

Connections

  • The alarm → Base cell (data or telemetry). An unknown class is the document's default_class (else Process), an unknown priority is HIGH and an unknown state is UNACK_ALARM.
  • Base cell → priorities[priority] (data or telemetry). Each layer overrides the layer above member by member; a member it leaves empty keeps the earlier value.
  • priorities[priority] → states[state] (data or telemetry). The state layer styles only SHELVED, SUPPRESSED and NORMAL; for the other states it is skipped.
  • states[state] → Class overrides, in order (data or telemetry)
  • Class overrides, in order → Readable colours (data or telemetry). Colours that are not valid, or a text colour equal to its background, take the base cell's colours. For the built-in safety alarms, text below 3:1 contrast takes the base colours, and a CRITICAL unacknowledged alarm made steady keeps the base blink unless safety_critical_steady_allowed is on.
  • Readable colours → Alarm as drawn (data or telemetry)
  • The alarm → Sound, in order (data or telemetry): unacknowledged. The sound is resolved only for UNACK_ALARM and RTN_UNACK; every other state has no sound.
  • Sound, in order → Alarm as drawn (data or telemetry): sound, repeat, volume

Validation (on save). These are refused:

  • an unknown member, priority, state, blink, icon, sound or repeat;
  • a colour that is not #RGB or #RRGGBB. Named, transparent and alpha colours are not accepted;
  • a label longer than 8 characters;
  • a resolved cell whose text colour equals its background;
  • a blinking cell whose blink colour equals its text colour.

Text contrast below 4.5:1 is accepted, with a warning.

The product’s own safety alarms are the plant emergency stop and the PLC fault alarms. Their class and priority is Safety, CRITICAL, and they cannot be made invisible:

  • a document that gives that class and priority a text contrast below 3:1, in any state, is refused;
  • a document that makes it steady (blink: none) while unacknowledged (UNACK_ALARM, RTN_UNACK) is refused, unless safety_critical_steady_allowed is true;
  • when these alarms are drawn, the same floor applies again, even if the document was edited by hand.
Route Who
GET /api/alarms/classes any signed-in role The effective classes: doc, the resolved matrix (class → priority → state → cell), builtin_safety, the allowed blink_hz, sounds, repeats and icons, the warnings, and from_default and load_error. The revision is in _rev and in the ETag header.
PUT /api/alarms/classes Lead_Engineer, Administrator Replaces the document. The body is the doc object; a _rev member is ignored. Send the revision you edited in If-Match.

Answers to PUT:

  • 409 {"status":"stale"}: the document changed since you loaded it. Nothing was saved.
  • 400 {"status":"invalid","problems":[...]}: the document did not pass validation.
  • 409 or 503: on an HA cluster, the node is a standby or has no quorum.
  • 200: the document was saved. The answer is the same as GET, with the warnings.

Every save is written to the audit trail as ALARM_CLASSES UPDATE before it is made, with the old and new documents and the SHA-256 of each in the reason (“sha256 before …, after …”). When the record cannot be written the save is refused with 503 and the code AUDIT_NOT_WRITTEN, and the classes are unchanged. A checkpoint revert or a server backup restore that changes the classes is recorded the same way first (ALARM_CLASSES CREATE, UPDATE or DELETE, the reason naming the checkpoint or backup).


GET /api/alarms/history returns one page of the ISA-18.2 journal. GET /api/alarms/history.csv exports every row the same filters select.

Parameter Meaning
from, to Inclusive bounds: an RFC 3339 time, Unix milliseconds (nanoseconds from 10¹⁵ up), or a duration back from now such as -24h.
class Categories, as a comma-separated list, case-insensitive. Alias: category.
priority CRITICAL,HIGH,MEDIUM,LOW,INFO. Alias: severity.
state Events (TRIP, ACK, RTN, SHELVE, UNSHELVE) and/or the states they led to (NORMAL, UNACK_ALARM, ACK_ALARM, RTN_UNACK, SHELVED). Alias: event.
tag A tag path pattern. With * or ? it must match the whole path; otherwise it matches any part. Alias: tag_path.
area A tag path prefix, matched by whole segments: Plant/Line1 matches Plant/Line1/... but not Plant/Line10.
user Who acknowledged, shelved or unshelved, case-insensitive.
q Text in the message (name, description), alarm id, tag, reason or user. Alias: search.
alarm_id One alarm.
sort time, alarm_id, name, tag, class, priority, event, state, previous_state, value, setpoint, user or reason. Prefix with - (or add :desc) to sort descending. The default is -time. priority sorts by urgency: ascending puts CRITICAL first.
limit 1 to 1000. The default is 100.
cursor The X-Next-Cursor of the previous page. Pages stay stable while new events arrive.
offset The number of rows to skip. Ignored when cursor is set.
envelope=1 Answer {"rows","total","next_cursor","limit","sort"} instead of an array.

The answer is a JSON array of journal events. Each row also carries:

  • class, the class the alarm is shown as;
  • display_state;
  • user and reason, the actor of the event.

These headers come with it:

  • X-Total-Count: the rows that match, across all pages;
  • X-Next-Cursor: the cursor of the next page; absent on the last page;
  • X-Limit;
  • X-Sort.

A bad parameter is answered 400 with the reason.

CSV. columns= chooses and orders the columns. The default is all of them: time (UTC, ns), event_id, alarm_id, name, description, tag, class, priority, event, previous_state, state, value, setpoint, user and reason.

The rows are streamed in the requested sort order. An export holds at most 100 000 rows; max_rows sets a lower cap. When more rows match, nothing is exported. The answer is 413 {"status":"too_many_rows","total":…,"max":…}, asking you to narrow the time range or the filters.

A text cell that a spreadsheet would run as a formula (one starting with =, +, -, @, a tab or a carriage return) is prefixed with an apostrophe.

Rows journaled by an earlier release do not have a message in the columnar store. Those rows show the alarm’s current name and description.

Performance was measured on a 1 000 000-event journal (2 000 alarms, 30 days) on a development workstation.

Query Columnar store (full build) Journal file (standard build)
Newest 100 rows, all rows, role filter applied 20–207 ms 1.4 s
Last 24 h, priority and class filter 35 ms 0.6 s
Text search over 30 days 98 ms 0.6 s
Page 2 by cursor, sorted by tag, 1000 rows 102 ms
Offset 500 000, sorted by priority 339 ms
CSV stream of 66 000 rows 370 ms

The columnar store needs no extra index. The journal is written in time order, so time ranges are pruned without one.


GET /api/alarms/counts counts the standing alarms the caller sees, the same list as GET /api/alarms/active. Optional filters: class, priority, area.

Each alarm is counted under its priority as read in Priority names, so by_priority and the cells hold only the five priorities: an alarm with HIGHEST or URGENT counts as CRITICAL, one with any other name as HIGH. The priority filter takes the five names (priority=CRITICAL,HIGH).

{
"counts": {
"total": 6, "unacked": 4,
"cells": [ { "class": "Safety", "priority": "CRITICAL", "state": "UNACK_ALARM", "count": 2 } ],
"by_priority": { "CRITICAL": { "total": 3, "unacked": 2 } },
"by_class": { "Safety": { "total": 3, "unacked": 2 } },
"by_state": { "UNACK_ALARM": 3 }
},
"builtin_safety_active": 1,
"classes_rev": "…"
}

An alarm counts as unacknowledged in UNACK_ALARM and RTN_UNACK, whether or not its evaluation is suspended.

The System Health tags System/Health/<node>/Alarms/Active, Alarms/Unacked and Alarms/Shelved use the same priority rule. They count the whole server, while /api/alarms/counts counts what its caller may see. See System Health history.


GET /api/alarms/active answers the standing alarms the caller sees, as a JSON array. It takes the same filters as the dashboard’s alarm list card, so the card gets only the rows it shows. Without a parameter it answers every standing alarm the caller sees, as before.

Parameter Alias Keeps the alarms
area path whose tag path is the folder or under it, by whole path segments: Boiler matches Boiler and Boiler/Drum/Level, never Boiler2/Level. A trailing * or / is dropped.
priority severity of one of the priorities given: CRITICAL, HIGH, MEDIUM, LOW, INFO. The alarm’s priority, and each value given, are read as in Priority names: HIGHEST and URGENT are CRITICAL; any other name, empty or missing is HIGH.
class category of one of the classes given, case-insensitive.
state in one of the states given: active (standing, acknowledged or not), unack (unacknowledged, standing or returned), shelved, returned (returned to normal, not yet acknowledged), or a display state by name (UNACK_ALARM, ACK_ALARM, RTN_UNACK, SHELVED, SUPPRESSED, NORMAL). An unknown state matches nothing, never everything.
text q where every word given appears in the alarm’s name, description, tag path, id or class, case-insensitive.
  • priority, class and state take a list: comma-separated (priority=CRITICAL,HIGH) or the parameter repeated. ALL and empty entries in a list are no filter.
  • Several parameters: an alarm must match all of them.
  • A parameter the route does not know is ignored, as before.
  • The filters run after the caller’s read rights and the alarm visibility (see Visibility). They only take rows away: no filter ever returns an alarm the caller may not see.
GET /api/alarms/active?area=Plant/Boiler&priority=CRITICAL,HIGH&state=unack&text=drum%20level

Every route here filters alarms by the same rule as the other alarm reads (/api/alarms/active, /api/alarms/journal, the WebSocket):

  • the caller must have read rights on the alarm’s tag;
  • the alarm definition’s target_roles must name one of the caller’s roles. Administrators see every alarm.

The built-in safety alarms (the plant emergency stop and the PLC fault alarms) are shown to every signed-in role, whatever their target_roles and whatever the read rights on their tag. An operator who may not read a PLC’s fault tag still sees that the PLC faulted. The alarm row carries its trip value; the tag itself stays unreadable (/api/tags, trends and the tag stream still refuse it).

The filter is applied before counting and paging. Neither the total, the pages nor the CSV export include a row the caller may not see. A row that is written while a query runs is shown only if it was checked against the caller’s rights.

  • Projects that already had alarms get the legacy look, which keeps the former banner colours. Unacknowledged alarms now blink fast, and alarms that returned to normal but are not yet acknowledged blink slowly (decision D3).
  • Built-in safety alarms are now visible to every signed-in role, even without read rights on their tag. This applies to every alarm read: /api/alarms, /api/alarms/active, /api/alarms/journal, /api/alarms/history and its CSV, /api/alarms/counts, and the WebSocket alarm list and events. Before, an operator without read rights on a PLC fault tag did not see that PLC’s fault alarm.
  • /api/alarms/history now accepts GET only (any other method gets 405). It still answers a JSON array, with new fields and paging headers.
  • GET /api/alarms/active now applies area, priority, class, state and text (and their aliases) on the server, after the read rights. Before, it ignored every parameter. A client that sent one of these parameters and expected every standing alarm now gets fewer rows; a state value the server does not know now returns no rows.
  • A priority that is not one of the five is now read one way everywhere (Priority names), never lower than before. GET /api/alarms/counts and the alarm class colours and sounds now count and show HIGHEST and URGENT as CRITICAL (they were HIGH). In the alarm list card and the priority filter of GET /api/alarms/active, an unknown or empty priority, WARNING and WARN are now HIGH (were MEDIUM), MINOR is HIGH (was LOW) and NOTICE is HIGH (was INFO). The alarm banner and summary objects no longer hide an alarm with an older or unknown priority from their priority filter. The classic dashboard alarm summary shows an unknown priority as HIGH (was LOW) and INFO as INFO (was LOW); the phone view shows an unknown or missing priority as HIGH (was LOW); the 3D and isometric views colour an object by such an alarm as HIGH (it ranked below INFO).
  • SAFETY: the System Health alarm counts and the eaxscada_alarms metric now count every priority name, read by the same rule. Before, an alarm with a priority name other than the five was missing from them.