Skip to content

Publish to an MQTT broker

eaxPLCHow-to guideFreeProView as Markdown

Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.

The PLC’s variables reach the plant’s MQTT broker with the same paths, values and quality as on the NATS Unified Namespace, directly from the PLC.

  • You are a Lead Engineer or Administrator: every change of these settings is signed with your password and recorded in the PLC’s audit trail.
  • You know the broker’s URL (tcp://, ssl://, ws:// or wss://), and, if it asks for them, a user name and password or a client certificate.
  • Publishing is off until you switch it on. A simulated PLC never opens an MQTT connection.
  1. Open File > MQTT Publishing.
  2. Under Broker, tick Publish to an MQTT broker and enter one broker URL per line. Enter the user name and password if the broker needs them. The password is never shown again: the page says Set or Not set, and an empty field keeps it.
  3. For ssl:// or wss://, paste the broker’s CA certificates under TLS (empty: the system’s), and a client certificate with its private key if the broker identifies clients by certificate.
  4. Under Topics, choose JSON topics or Sparkplug B. The topic root defaults to the PLC’s UNS prefix. Variables published takes patterns such as Tank*, Line2.*; empty publishes every variable the NATS UNS publishes (strings are not published).
  5. Click Test connection. The PLC connects to the broker and disconnects; nothing is published.
  6. Click Sign and save…, give a reason and your password. The PLC connects with the new settings at once.

The settings are kept in data/mqtt.json; the password and the client key in data/mqtt/secrets.json, readable by the PLC’s account only. A headless eaxPLC runtime reads the same files.

JSON topics:

Topic Payload
<root>/<variable> {"path","value","quality","timestamp","device_id","address"}, the NATS UNS payload. FB members and array elements are levels: Timer1.Q is <root>/Timer1/Q, Recipe[3] is <root>/Recipe/3.
<root>/system/Fault 1 while the PLC is in a fault state, 0 otherwise.
<root>/system/online true while the PLC is connected; the broker publishes false when the connection breaks (last will).

Values are published when they change and every 30 seconds (setting Republish every value every), retained by default so a new subscriber gets the current state at once.

  • The PLC is one edge node (group id and edge node id: by default the first level of the topic root and the PLC id), with its variables as node metrics. There are no devices.
  • Metric names are the UNS paths (<root>/<variable>). The NBIRTH gives each an alias and a datatype from the PLC type (BOOL Boolean, INT Int16, DINT Int32, REAL Float, LREAL Double, and so on); NDATA carries aliases only.
  • Every metric carries the property Quality (Int32: 192 Good, 64 Uncertain while the PLC is stopped or faulted, or before its first cycle).
  • The NDEATH registered as the connection’s will carries the bdSeq of the NBIRTH it ends. seq runs from 0 (NBIRTH) to 255 and wraps.
  • After every reconnection an NBIRTH comes before any NDATA. Values buffered while the broker was away follow it as NDATA marked historical.
  • Node Control/Rebirth in an NCMD always republishes the NBIRTH, whether commands are on or off. A download that adds or removes variables also rebirths.
  • With a primary host id, the PLC publishes nothing until that host’s STATE says online, and ends the session (NDEATH) when it says offline.
  • In eaxScada, an MQTT channel’s browse offers each metric by its full address, spBv1.0/<group>/NDATA/<edge node>/<metric>. A write by that address goes to this edge node only, never to a metric of the same name on another node. Writes are refused after the node’s NDEATH until its next NBIRTH, and a metric no longer in the latest NBIRTH reads Bad and cannot be written.

Publishing runs beside the scan, never in it: a slow or unreachable broker never lengthens a cycle. Values that change while the broker is away wait in a buffer of Buffer while the broker is away messages (default 10 000); when it is full the oldest go first, and the page counts them under Dropped. The diagnostics (state, last error, messages sent, buffer, drops, bdSeq and seq) refresh on the page while it is open.

Commands are off by default. When they are on:

  • JSON: publish a number, true/false, a string, or {"value": x} on <root>/command/<variable>. Sparkplug B: an NCMD with the metric’s name or alias.
  • Each write is checked like a UNS command: only the variables the writable patterns (--uns-writable) allow, with read/write access, not a CONSTANT, within the write range. A variable on the safety-target list (Project Settings), or any variable sharing its storage, is never written over MQTT.
  • An accepted write is applied at the next cycle boundary, never forced. Accepted and refused writes are recorded in the PLC’s audit trail (as MQTT) and in the log.
  • A retained command message is ignored, so a write never replays when the PLC reconnects.

The page shows Connected and the messages sent grow. A subscriber to <root>/# (JSON) or spBv1.0/<group>/# (Sparkplug B) sees the PLC’s values.