Skip to content

Transmitter

eaxScadaReferenceStarterView as Markdown

A field transmitter (pressure, temperature, flow) with its live value. Bind its value to the measurement: the readout shows it with the unit and decimals set here, a dash until a value arrives, and the quality marker when the value is Bad or Uncertain.

Transmitter in the operator runtime

Palette Not in the palette
JSON type Transmitter
Name in the inspector Transmitter
Size a resize is stored as a scale (scaleX, scaleY); width and height keep the size it was drawn at
Shown as Key Type Unit Default Allowed values What it does
Decimals shown decimals Number — min 0, max 6, step 1 Decimals of the readout.
Unit unit Text — Unit written after the value (bar, degC, m3/h).
Faceplate command / setpoint tag setpointTag Tag path (written) — The tag the operator faceplate (a click on the object in the runtime) writes. Empty = the faceplate is read-only. Never the measured value: write a setpoint or command tag. Inspector hint: Leave empty for a read-only faceplate. Never the measured value.
Command minimum spMin Number — Lowest value the faceplate may write. The server refuses lower values from every writer of that tag.
Command maximum spMax Number — Highest value the faceplate may write. The server refuses higher values from every writer of that tag.
W width Number px 70 Width of the object’s box. Objects sized by scale keep their drawing and use it only as the selection box.
H height Number px 80 Height of the object’s box.
— fill Colour "#1e293b" Colour of the instrument head.
— stroke Colour "#38bdf8" Colour of the outline.
Stroke width strokeWidth Number px 2 Outline thickness in pixels; 0 draws no outline.
— label Text "TRANSMITTER" The instrument tag (PT101), drawn with it and shown as the faceplate title.
On-screen keyboard keyboard Choice — inherit
auto
numeric
full
numeric_full
none
Shown once a command / setpoint tag is set: which on-screen keyboard the operator faceplate’s entry opens on a touch panel. inherit: the screen’s, then the project’s setting.
X x Number px — Horizontal position of the object’s top-left corner on the screen, in screen pixels from the left edge.
Y y Number px — Vertical position of the object’s top-left corner, in screen pixels from the top edge.
Rotation rotation Number ° — Rotation of the object, clockwise, in degrees.
Opacity opacity Number — 0 (invisible) to 1 (opaque). An object disabled by an interlock is drawn at 0.45 whatever this says.
Scale X scaleX Number — Horizontal scale factor (1 = drawn size). Set by resizing an object that is sized by scale.
Scale Y scaleY Number — Vertical scale factor (1 = drawn size).
States states Object — This object’s own state styles (normal, hover, pressed, on, disabled, bad, locked, unconfigured), edited in the inspector’s States section. Visual only. Empty: the project’s state styles.
State family styleFamily Text — The state family whose project styles apply (button, input, toggle, selector, faceplateButton, default). Empty: the family of the object’s type.

The object reads this tag through its own properties, with their quality: setpointTag. A Bad or Uncertain value is marked on the object (see Quality below), never drawn as good.

The Bind tab ties a property to a tag or an expression: a tag binding takes the tag’s value, an expression binding computes one (see the expression language), optionally through a map, format or script transform. The targets the Bind tab offers for this object:

Bind tab target Key What the bound value does
Fill Color fill Sets the fill colour from the value (a colour text such as #22c55e, or a colour mapped by a map transform).
Stroke / Border Color stroke Sets the outline colour from the value.
Opacity (0.0 - 1.0) opacity Sets the opacity from the value (0 to 1).
Visibility (Boolean) visible Shows the object when the value is true or non-zero, hides it otherwise.
Rotation (°) rotation Rotates the object by the value, in degrees.
Scale / Pulse scale Scales the object by the value (1 = drawn size).
Text / Label text Replaces the text drawn with the value, formatted by the binding’s format. On a Text object a number is followed by the object’s unit, as with the Value target (never a word). A Bad value shows a dash.
Value (Numeric) value Shows the value as the object’s readout (with the unit and decimals). A Bad value shows a dash.

The Cond tab adds rules evaluated on every value change: Visibility (show or hide, by condition or role), Color & Fill (colour bands, alarm blinking), Position and Size & Fill (motion and level mapped from a value), Rotation (angle or continuous spin; an empty input range is 0 to 100 and empty angles are -135° to 135°, while 0 is a value), Security & Touch (the interlock: a disable condition, the role required, what happens when the interlock reads a Bad value) and Text & Value (formatted text). A condition that reads a Bad value is never applied as if the value were good: visibility shows the object marked Bad, colours go neutral grey, motion stays where it is, text shows a dash.

Operator faceplate. In the runtime, a click or tap on this object (without an action of its own) opens the operator faceplate: its name, the value of the tag it shows (the first tag it is bound to) and, only when a Faceplate command / setpoint tag is set, an entry that writes that tag within Command minimum and Command maximum. Without a command tag the faceplate is read-only: the measured value is never offered for writing. The write goes through the same confirmation, limits and interlock checks as every command.

Commands. This object sends commands to equipment. Before it writes:

  • Confirmation and e-signature. Set Confirmation to ask the operator to confirm, or to sign with their password and a reason (electronic signature). The signer is always the signed-in user; the dialog never pre-fills a signer, a reason or a password. The server requires the same confirmation from every writer of the tag.
  • Limits. Minimum, maximum and step (or the tag’s write range) are enforced by the server for every writer; the screen’s own check only saves a round trip. A limit read from a tag that is missing or not Good refuses every write.
  • Interlocks. A Disabled condition (buttons) or the disable condition of the Security & Touch condition dims the object and blocks the press while it is true. When the interlock is a simple tag comparison ({Plant/Processing/Pumps/P101/Interlock} == 1), the server also refuses the write from every writer (409 interlocked); other interlocks are screen only, and the designer says which. If the interlock reads a Bad value the object is disabled, unless If the interlock reads a Bad value is set to Allow (for stop, trip and emergency commands, so a failed sensor never stops an operator stopping a machine). See screen interlocks.
  • Unconfigured means disabled. Without its tag the object is drawn as not configured and sends nothing.
  • Deliberate taps. On touch, only a still, short tap operates it.

A real safety interlock belongs in the PLC: screen and server interlocks only stop writes that go through eaxScada.

Any object can carry a click or tap action (the Action tab, or Full Dialog…). A write action whose tag, value or target is missing is not configured: the inspector says so and the operator’s press does nothing (unconfigured means disabled). Navigation actions write nothing and ask no confirmation. On touch screens only a deliberate tap runs an action: a swipe or a pinch that ends on the object never does. Action types:

Action Key (action.type) What it does
Set tag to 1 set_1 Writes 1 to the action’s tag.
Set tag to 0 set_0 Writes 0 to the action’s tag.
Toggle tag value toggle Writes the opposite of the tag’s LIVE value: 0 when it is not 0, 1 when it is 0. When the live value is unknown, not Good or not a number, nothing is written and the operator is told why; when it changes while the operator confirms or signs, nothing is written either.
Set tag to 1 on press and to 0 on release momentary_1_0 Writes 1 while pressed and 0 on release (hold to run). On touch, the press counts only after the finger is held still; the release is always sent. A held press is also released when the browser window loses focus or the page is hidden, and in the designer when a drag or a resize of the object starts.
Set tag to 0 on press and to 1 on release momentary_0_1 Writes 0 while pressed and 1 on release. Released in the same cases as the 1/0 momentary.
Write custom value write_val Writes the number in write_value.
Run script run_command Runs a client script with the scripting API (system.tag.write, system.nav.openPopup…). Ctrl+Space completes the API.
Navigate to page / screen navigate Opens another screen, optionally with parameters or a parameter set.
Open popup screen open_popup Opens a screen in a popup window: modal or not, centred, next to the object or at a fixed position, with parameters.
Close popup close_popup Closes the popup the object is in, or the popup with the given id.
Open dock open_dock Opens a screen docked to an edge of the runtime (top, bottom, left, right).
Close dock close_dock Closes the dock on that edge.
Open or close dock toggle_dock Opens or closes the dock on that edge.
Back nav_back Goes back to the previous screen.
Forward nav_forward Goes forward again after Back.
Home screen nav_home Opens the project’s home screen.
Open downtime panel open_downtime Opens the operator runtime’s Downtime panel (OEE and downtime, Pro and Enterprise), optionally on one machine (its machine id). Navigation only: nothing is written to a tag or a machine. A machine the operator may not read is not shown; where the panel is not available, a notice says so. Offered in the designer only when the licence includes OEE and downtime.

States. An object’s look follows its state: normal, hover, pressed, on, disabled, bad (quality), locked (role) and unconfigured. The project’s state styles (opened from an object’s States section, or from the Project manager’s Operator runtime section) give each family of objects its colours per state, and the inspector’s States section overrides them for one object (stored in props.states). States are visual only: whether an object can be operated is decided by its interlock, the user’s rights and the server.

This object belongs to the state family default (all other objects): disabled (an interlock dims it to 0.45 opacity), bad (a tag it reads is Bad) and locked (missing role) apply when the object has conditions or an action; the other states apply to objects that are operated.

Screen parameters. On a screen with parameters, {Name} in any text of the object (tag paths of bindings and actions, expressions, conditions, interlocks, the confirmation tag, texts) is replaced by the parameter’s value when the screen opens, so one screen serves many pieces of equipment ({Pump}/Running). See screen parameters.

Quality. When a value the object reads is Bad, not readable, Uncertain or stale, the object is marked: a red x and a grey veil (or hatching, per the project’s quality style) for Bad or no connection, a blue lock for a tag the signed-in account may not read, an amber ? for Uncertain, a dashed outline for stale. A tag that is not readable is greyed as Bad and its value is never shown as good. The lock shows only when every Bad tag of the object is not readable: a device fault keeps the red x. Each object shows one marker, for its worst state, and markers that would overlap merge into one, drawn on the largest object with the worst state of all. The marker’s tooltip lists every tag, its quality and its age. A Bad value is never drawn as a good one. See show bad and stale values.

Comments. In the studio, right-click the object and choose Add comment to start a design-review thread on it; a numbered pin marks objects with open threads (Starter, Pro and Enterprise). Pins are shown in the designer only, never in the runtime. See review screens before deploy.

Flow transmitter FT101 on the transfer line

Section titled “Flow transmitter FT101 on the transfer line”

FT101 shows the flow of pump P-101’s discharge, in m3/h with one decimal.

  1. Place a Sensor Transmitter; label FT101.
  2. Bind tab: target Value (Numeric), tag Plant/Processing/Pumps/P101/Flow.
  3. Inspector: Unit m3/h, Decimals shown 1.

Flow transmitter FT101 on the transfer line

FT101 reads 42.7 m3/h.
The transmitter as saved in the screen (JSON)
{
"type": "Transmitter",
"props": {
"fill": "#1e293b",
"stroke": "#38bdf8",
"strokeWidth": 2,
"unit": "m3/h",
"decimals": 1,
"label": "FT101"
},
"bindings": {
"value": {
"type": "tag",
"tagPath": "Plant/Processing/Pumps/P101/Flow"
}
}
}