Driver channels, devices and tags
Driver configuration (data/drivers/config.json): channels, their devices and tag mappings, and the protocol settings object of each channel.
Keys are the JSON keys. Optional marks keys that are omitted when empty, or that may be absent (pointers).
Channel
Section titled “Channel”Channel represents a physical or logical communication channel (eaxDrivers Channel level)
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
id |
string | ||
name |
string | ||
description |
string | ||
protocol |
string | ETHERNET_IP, ISO_ON_TCP, MODBUS_TCP, etc. | |
enabled |
boolean | ||
inter_request_delay_ms |
integer | ms delay between packets | |
connect_timeout_ms |
integer | ||
request_timeout_ms |
integer | ||
retry_count |
integer | ||
settings |
JSON value | Protocol-specific settings JSON | |
status |
ChannelStatus | ||
last_error |
string | yes | |
last_error_at |
timestamp (RFC 3339 string) | yes | in ERROR since (history: diagnostics) |
packets_sent |
integer | ||
packets_recv |
integer | ||
error_count |
integer | ||
last_rtt_ms |
number | ||
last_connected |
timestamp (RFC 3339 string) | yes | |
devices |
list of Device | yes | |
simulated |
boolean | Simulated mirrors the Simulated flag inside Settings so the UI can show it without parsing protocol-specific settings. A simulated channel never touches the network and every tag under it is generated, which is indistinguishable from healthy live data unless it is surfaced. Derived server-side on read; never trust it from a request body. | |
link |
LinkStats | yes | Link is the running driver’s link-level diagnostics (frames, checksum errors, timeouts, node states) for the serial and CAN drivers. Derived on read; absent for drivers that do not report it. |
_rev |
string | yes | Rev is the revision of the channel’s configuration: send it back in the If-Match header of a save (a stale one is refused with 409). Read only. |
Device
Section titled “Device”Device represents a physical PLC, RTU, or endpoint under a channel (eaxDrivers Device level)
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
id |
string | ||
channel_id |
string | ||
name |
string | ||
description |
string | ||
station_id |
string | IP address, node number, slave address, or topic prefix | |
model |
string | e.g. 1769-L33ER, S7-1516-3, Micro850, Generic Modbus | |
scan_rate_ms |
integer | ||
enabled |
boolean | ||
block_read_optimization |
boolean | ||
max_block_size |
integer | ||
status |
ChannelStatus | ||
last_error |
string | yes | |
tag_count |
integer | ||
packets_sent |
integer | ||
packets_recv |
integer | ||
error_count |
integer | ||
tags |
list of TagMapping | yes | |
scan_measured_ms |
number | yes | ScanMeasuredMs (runtime, read only) is the measured time between two polls of the device (averaged), PollCycleMs how long its last poll took; both 0 until it was polled twice. A measured rate well above scan_rate_ms means the line or the controller cannot keep up. |
poll_cycle_ms |
number | yes | |
uns_prefix |
string | yes | UNSPrefix is the ISA-95 path this device sits at, e.g. “Plant/Processing/BlendLoop”. Protocols that carry less hierarchy than the UNS needs (Modbus carries none, CIP and Sparkplug carry equipment and signal) use it to build the suggested UNS path of a browsed tag. Without it the suggestion is only the part the device actually knows. |
plc_id |
string | yes | PLCID, optional, declares the device as the eaxPLC with this id (as configured on this server, e.g. “plc-01”). Active PLC forces are then shown on the device’s tags by address, without guessing which PLC the device is. Empty: the device is not declared as an eaxPLC. |
simulated |
boolean | Simulated is inherited from the parent channel, surfaced here so a device row can be badged without the caller re-resolving the channel. | |
_rev |
string | yes | Rev is the revision of the device’s configuration (If-Match of a save). Read only. |
TagMapping
Section titled “TagMapping”TagMapping maps a device hardware address to a NATS-based Unified Namespace (UNS) tag path
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
id |
string | ||
device_id |
string | ||
channel_id |
string | ||
tag_name |
string | Hardware symbolic name or register | |
address |
string | e.g. “HR:40001”, “DB1.DBD0”, “Program:Main.Speed”, “ns=2;s=Temp” | |
data_type |
string | Float32, Float64, Int16, Int32, UInt16, Bool, String | |
access |
string | “RO” (Read Only: every write refused before it is sent, whoever asks), “RW” (Read / Write; also empty), “WO” (Write Only) | |
deadband |
number | Value delta for publishing trigger | |
eng_unit |
string | RPM, °C, bar, %, kW | |
uns_path |
string | Core UNS path: “Plant/Processing/Reactor1/Temperature” | |
nats_topic |
string | Auto-derived: “uns.telemetry.Plant.Processing.Reactor1.Temperature” | |
live_value |
number | ||
quality |
integer | 192 = Good, 0 = Bad, 64 = Uncertain | |
timestamp |
integer | ||
last_error |
string | yes | runtime: why the last read failed (“” after a good read) |
simulated |
boolean | The mapping’s channel is simulated (derived from the channel; never a fallback for a disconnected device) | |
live_text |
string | yes | LiveText (runtime) is a String mapping’s last text read from the device (FINS, MC protocol: TextReader). Quality and Timestamp are its read’s: a failed read keeps the text with quality BAD, never GOOD. The tag engine holds numbers, so the text is not in it. |
scale |
number | yes | Scale divides the raw value read from the device to produce the engineering value. Modbus transmitters send integers — a level in percent as value100, a pump speed in rpm as value10 — and the factor differs per signal because a single factor overflows a 16-bit register for large spans. Zero and one both mean “no scaling”; zero is the zero value of the field and must not be treated as “divide by zero”. |
eng_min |
number | yes | Engineering range (instrument span), optional. A Good value outside it is published as Uncertain (EU exceeded), never as Good. |
eng_max |
number | yes | |
esign_external |
boolean | yes | ESignExternal: an external writer - a NATS command, a non-session API caller, an AI agent - must sign every write to this tag (a person’s e-signature or a registered integration’s signature). The HMI keeps the screen policy. Founder decision 2026-10-01 (internal/writepolicy). |
write_range |
Range | yes | WriteRange: the values a write to this tag may carry (min, max, step, allowed values; for a String tag max_length and allowed texts). The server refuses a write outside it, whoever sends it. Distinct from the engineering range, which only flags a read value’s quality. |
handed_over |
Handover | yes | HandedOver: the mapping took its path over from a local tag (“Hand over to driver”, handover.go). Set by the server only, never from a request; kept by every save on the same path. It holds the local definition “Return to local tag” puts back. |
_rev |
string | yes | Rev is the revision of the mapping’s configuration (If-Match of a save). Read only. |
EtherNetIPSettings
Section titled “EtherNetIPSettings”EtherNetIPSettings configures a CIP controller reached over EtherNet/IP: tag reads and writes by name over a connected session. A Logix controller in a chassis (or a compact one) is reached through the backplane (“1,<slot>”); a controller with no backplane (the Micro family, controller_type MicroCIP) is reached with an empty route. With controller_type DeviceCIP the connection is an EtherNet/IP device instead (drive, I/O adapter): attributes by class/instance/attribute, unconnected explicit messages, no route. With controller_type MicroLogixPCCC, SLC500PCCC or PLC5PCCC it is a PCCC controller (MicroLogix, SLC 500, PLC-5): data-table addresses, PCCC commands in unconnected messages, no route. Assembly I/O and implicit (Class 1) connections are not supported.
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
host |
string | Controller (or Ethernet module) IP address, e.g. 192.168.1.50 | |
port |
integer | Default 44818 | |
slot |
integer | Controller slot in the chassis (route “1,<slot>”; 0 for a compact controller; not used by a controller with no backplane) | |
cip_path |
string | Optional route that replaces the slot, e.g. “1,0” or a multi-hop “1,2,2,10.0.0.5,1,0” | |
connection_type |
string | Kept for compatibility; not read by the driver (always a connected session) | |
controller_type |
string | Controller family (“CompactCIP”, “ModularCIP”, “MicroCIP”, “GenericCIP”), “DeviceCIP” for an EtherNet/IP device (drive, I/O adapter), or a PCCC controller (“MicroLogixPCCC”, “SLC500PCCC”, “PLC5PCCC”: data-table addresses such as N7:0); selects the route (MicroCIP → empty route, no backplane). Empty is read as a backplane (“1,<slot>”) controller, unchanged from before. | |
auto_discover |
boolean | Kept for compatibility; not read by the driver | |
simulated |
boolean | yes | Explicit simulator mode |
timeout_ms |
integer | yes | TimeoutMs bounds each request to an EtherNet/IP device (DeviceCIP) or a PCCC controller (ms, 100-30000). 0: 2000. Not read for a Logix controller. |
ISOOnTCPSettings
Section titled “ISOOnTCPSettings”ISOOnTCPSettings configures an S7-300/400/1200/1500 PLC over ISO-on-TCP (RFC 1006, port 102): absolute addresses in DB, M, I and Q. An S7-1200/1500 needs PUT/GET access allowed and data blocks without optimized access.
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
host |
string | PLC IP address (e.g. 192.168.1.10) | |
port |
integer | Default 102 | |
rack |
integer | Default 0 | |
slot |
integer | CPU slot: 1 for S7-1200/1500, 2 for S7-300 (0 takes the family default) | |
plc_family |
string | “S7-1500”, “S7-1200”, “S7-300”, “S7-400” (legacy “ISO-1500” etc. are read as these) | |
pdu_size |
integer | Negotiated PDU (240 to 960) | |
auto_reconnect |
boolean | ||
simulated |
boolean | yes | Explicit simulator mode |
ModbusTCPSettings
Section titled “ModbusTCPSettings”ModbusTCPSettings configures Modbus TCP/IP Ethernet
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
host |
string | Gateway/PLC IP address | |
port |
integer | Default 502 | |
unit_id |
integer | Default 1 (Slave address) | |
byte_order |
string | “ABCD” (Big-Endian), “CDAB” (Word-Swap), “BADC”, “DCBA” | |
max_block_size |
integer | Default 125 registers | |
zero_based |
boolean | Address indexing starts at 0 or 1 | |
simulated |
boolean | yes | Explicit simulator mode; the port is never used to infer it |
gateway |
boolean | yes | Gateway: the address is a Modbus TCP gateway with several devices behind it (meters, drives, RTUs on its serial side). Each device is a station whose station_id is its unit id (1-247); its reads and writes carry that unit id over the one connection, and a device without a station id uses UnitID. Off (the default, and every configuration saved before gateways existed): every request goes to UnitID and the station_id is not read. |
timeout_ms |
integer | yes | TimeoutMs bounds each request (ms, 100-30000). 0: 2000, as before; the channel’s request timeout is not used for Modbus TCP. |
block_gap_registers |
integer | yes | BlockGapRegisters: with block reads on a device, the most unmapped holding or input registers one block read spans between two tags. Unset: 16; 0: only adjacent tags are read together. |
block_gap_bits |
integer | yes | BlockGapBits: with block reads on a device, the most unmapped coils or discrete inputs (bits) one block read spans between two tags. Unset: 64; 0: only adjacent tags are read together. |
ModbusRTUSettings
Section titled “ModbusRTUSettings”ModbusRTUSettings configures Modbus Serial RTU
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
serial_port |
string | e.g. “COM3” or “/dev/ttyUSB0” | |
baud_rate |
integer | 9600, 19200, 38400, 57600, 115200 | |
data_bits |
integer | 7, 8 | |
stop_bits |
integer | 1, 2 | |
parity |
string | “N” (None), “E” (Even), “O” (Odd) | |
slave_id |
integer | 1 to 247 | |
byte_order |
string | “ABCD”, “CDAB”, “BADC”, “DCBA” | |
turnaround_delay |
integer | Silence time ms | |
simulated |
boolean | yes | Explicit simulator mode |
rs485 |
boolean | yes | RS485: let the operating system drive RTS for the transmitter direction (Linux only; adapters with automatic direction control need nothing). |
rts_before_send_ms |
integer | yes | RTSBeforeSendMs: with rs485, time the driver is enabled before the first bit is sent. |
rts_after_send_ms |
integer | yes | RTSAfterSendMs: with rs485, time the driver stays enabled after the last bit, before the line is released for the answer. |
inter_frame_us |
integer | yes | InterFrameUs overrides the inter-frame silence; 0 computes 3.5 character times (1750 us above 19200 baud). |
allow_broadcast |
boolean | yes | AllowBroadcast permits writes to unit 0, which every slave on the line executes and none acknowledges. Off by default; reads of unit 0 are always refused. |
block_gap_registers |
integer | yes | BlockGapRegisters: as on Modbus TCP, the most unmapped registers one block read spans between two tags (16 when unset). |
block_gap_bits |
integer | yes | BlockGapBits: as on Modbus TCP, the most unmapped coils or discrete inputs (bits) one block read spans between two tags (64 when unset). |
OPCUASettings
Section titled “OPCUASettings”OPCUASettings configures OPC-UA Client
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
endpoint_url |
string | opc.tcp://192.168.1.100:4840 | |
security_policy |
string | “None”, “Basic256Sha256”, “Aes128_Sha256_RsaOaep” | |
security_mode |
string | “None”, “Sign”, “SignAndEncrypt” | |
auth_mode |
string | “Anonymous”, “Username”, “Certificate” | |
username |
string | yes | |
password |
string | yes | |
publish_interval_ms |
integer | Subscription rate | |
simulated |
boolean | yes | Explicit simulator mode |
MQTTSettings
Section titled “MQTTSettings”MQTTSettings configures MQTT Broker & Sparkplug B bridge
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
broker_url |
string | tcp://broker.example.com:1883 or ssl://… | |
client_id |
string | SCADA-Edge-Gateway-01 | |
username |
string | yes | |
password |
string | yes | |
clean_session |
boolean | ||
keep_alive_sec |
integer | Default 60 | |
qos |
integer | 0, 1, 2 | |
payload_format |
string | “JSON_TELEMETRY”, “SPARKPLUG_B”, “RAW_VALUE” | |
topic_sub_pattern |
string | e.g. “sensors/+/telemetry” or “spBv1.0/#” | |
topic_pub_prefix |
string | e.g. “scada/edge/telemetry” | |
uns_mapper_regex |
string | Pattern to extract UNS path from topic | |
simulated |
boolean | yes | Explicit simulator mode |
ingest_path_prefix |
string | yes | IngestPathPrefix: a received message writes only the tags this channel maps to its topic (a Sparkplug metric: a tag this channel maps). Set, a path under this UNS prefix (e.g. “Plant/Edge”) that no other channel maps is accepted too: the payload’s “path”, else the topic without “sensors/”. Empty (the default): mapped tags only. A wildcard or a bare “/” is no prefix. |
NATSSettings
Section titled “NATSSettings”NATSSettings configures NATS Core UNS & Cluster Bridge
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
broker_url |
string | nats://127.0.0.1:4222 or remote cluster | |
auth_token |
string | yes | |
inbound_prefix |
string | e.g. “uns.telemetry.>” | |
outbound_prefix |
string | e.g. “uns.command.>” | |
jetstream_bucket |
string | e.g. “scada_uns_snapshots” | |
queue_group |
string | Load balancing queue | |
simulated |
boolean | yes | Explicit simulator mode |
own_broker |
boolean | yes | OwnBroker: read this server’s own broker in process, signed in with a reader identity the broker makes for the channel (subscribe its inbound subjects, publish nothing; natsengine.ConnectReader). No credentials: broker_url and auth_token are not used. The inbound subject must lie under uns.telemetry. |
SerialSettings
Section titled “SerialSettings”SerialSettings configures Raw Serial COM
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
port |
string | COM1, /dev/ttyUSB0 | |
baud_rate |
integer | 9600, 115200 | |
data_bits |
integer | 8 | |
stop_bits |
integer | 1 | |
parity |
string | N, E, O | |
flow_control |
string | None, RTS/CTS, XON/XOFF | |
delimiter |
string | “\r\n”, “\n” | |
simulated |
boolean | yes | Explicit simulator mode |
ModbusRTUTCPSettings
Section titled “ModbusRTUTCPSettings”ModbusRTUTCPSettings configures Modbus RTU framing carried over TCP (a serial device server or gateway in transparent mode): the RTU frame with its CRC, not the Modbus TCP header.
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
host |
string | device server address | |
port |
integer | device server TCP port (often 4001 or 950) | |
slave_id |
integer | unit for devices without a station id | |
byte_order |
string | “ABCD”, “CDAB”, “BADC”, “DCBA” | |
allow_broadcast |
boolean | yes | permit writes to unit 0 |
simulated |
boolean | yes | Explicit simulator mode |
block_gap_registers |
integer | yes | BlockGapRegisters: as on Modbus TCP, the most unmapped registers one block read spans between two tags (16 when unset). |
block_gap_bits |
integer | yes | BlockGapBits: as on Modbus TCP, the most unmapped coils or discrete inputs (bits) one block read spans between two tags (64 when unset). |
CANopenSettings
Section titled “CANopenSettings”CANopenSettings configures a CANOPEN (and CAN_RAW) channel. A device’s station_id is its CANopen node id (1-127).
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
interface |
string | Interface: a SocketCAN interface (can0, Linux), or slcan:<port> for an SLCAN adapter on a serial port (slcan:COM5, slcan:/dev/ttyACM0) or a serial device server (slcan:tcp://host:port). | |
bitrate |
integer | yes | Bitrate in bit/s (default 500000). Set on SLCAN adapters; a SocketCAN interface is configured by the system. |
heartbeat_timeout_ms |
integer | yes | HeartbeatTimeoutMs: a node whose heartbeat is older than this is lost and every tag of it is BAD. 0 disables liveness monitoring (not recommended). |
node_guarding_ms |
integer | yes | NodeGuardingMs > 0 polls nodes that have no heartbeat with node guarding requests at this period; lost after life_time_factor misses. |
life_time_factor |
integer | yes | LifeTimeFactor: missed node guarding periods before a guarded node is lost (default 3). |
sdo_timeout_ms |
integer | yes | SDOTimeoutMs bounds every SDO step (default: the channel request timeout, else 500). |
sdo_poll_ms |
integer | yes | SDOPollMs: an SDO tag is read from the node at most this often (default 1000); SDO is a request/response service and polling it at the scan rate loads the bus. |
pdo_stale_ms |
integer | yes | PDOStaleMs > 0: a PDO or frame value older than this is UNCERTAIN. |
nmt_start_on_connect |
boolean | yes | NMTStartOnConnect sends NMT Start to each node when it is first polled. Off by default: an operational node acts on the RPDOs other devices send it. |
sync_period_ms |
integer | yes | SyncPeriodMs > 0 makes this channel the SYNC producer. Off by default: two SYNC producers on one bus break synchronous PDOs. |
allow_broadcast |
boolean | yes | AllowBroadcast permits NMT commands to node 0 (every node). |
simulated |
boolean | yes | Explicit simulator mode |
LinkStats
Section titled “LinkStats”LinkStats are a serial or CAN driver’s link-level counters. They are cumulative since the channel started; a rising CRC or timeout count with GOOD tags is the early sign of a marginal line (termination, biasing, grounding, a wrong baud rate on one device).
Source: eaxScada/internal/drivers/link_stats.go
| Key | Type | Optional | Description |
|---|---|---|---|
medium |
string | e.g. “COM5 19200 8-E-1”, “can0”, “slcan:COM7” | |
connected |
boolean | ||
frames_tx |
integer | ||
frames_rx |
integer | ||
crc_errors |
integer | CRC (RTU) or LRC (ASCII) | |
timeouts |
integer | ||
exceptions |
integer | yes | |
frame_errors |
integer | yes | wrong unit/function, malformed |
retries |
integer | yes | |
sdo_requests |
integer | yes | CANopen |
sdo_aborts |
integer | yes | |
sdo_timeouts |
integer | yes | |
heartbeat_losses |
integer | yes | |
emcy |
integer | yes | |
nmt_sent |
integer | yes | |
bus_errors |
integer | yes | adapter / interface errors |
nodes |
list of NodeLinkState | yes | |
suspended_units |
list of integer | yes | Units on a multi-drop serial line that stopped answering and are polled at a reduced rate so they do not starve the others. |
identity |
CIPIdentity | yes | EtherNet/IP device: its Identity object, read when the connection opened (absent until it answered). |
last_error |
string | yes | |
last_error_at |
integer | yes | When last_error happened (Unix ms). |
previous_error |
string | yes | The error before, kept after it cleared: a serial Modbus link clears last_error once the line, or the unit that failed, answers again. |
previous_error_at |
integer | yes | When previous_error happened (Unix ms). |
recovered_at |
integer | yes | When previous_error cleared (Unix ms). |
unit_errors |
list of UnitLinkError | yes | Every unit (node, station; -1: the medium) in error now, the oldest first; last_error is the first of them. |
ChannelStatus
Section titled “ChannelStatus”ChannelStatus represents current communication state
Source: eaxScada/internal/drivers/types.go
Underlying type: string.
| Value | Name | Description |
|---|---|---|
ONLINE |
StatusOnline |
|
CONNECTING |
StatusConnecting |
|
OFFLINE |
StatusOffline |
|
ERROR |
StatusError |
|
DISABLED |
StatusDisabled |
Range is a tag’s write range. The zero value allows every finite number and, on a string tag, any text of at most DefaultMaxLength characters.
Source: eaxScada/internal/writerange/writerange.go
| Key | Type | Optional | Description |
|---|---|---|---|
min |
number | yes | Min / Max: the lowest and highest value a write may carry (inclusive). |
max |
number | yes | |
step |
number | yes | Step: a written value must be Min + kStep (0 + kStep without Min), within a relative tolerance of 1e-9. |
values |
list of number | yes | Values: the only values a write may carry (a mode selector: 0, 1, 2). |
max_length |
integer | yes | MaxLength: a string tag’s longest text, in characters (default 256). |
texts |
list of string | yes | Texts: the only texts a write to a string tag may carry. |
Handover
Section titled “Handover”Handover records where a mapping’s path came from (handover.go).
Source: eaxScada/internal/drivers/types.go
| Key | Type | Optional | Description |
|---|---|---|---|
from |
string | the producer that held the path (“eaxtags”) | |
at |
integer | Unix ms | |
by |
string | yes | who handed it over |
description |
string | yes | Description: the local tag’s, the tag’s description from then on. |
local_tag |
JSON value | LocalTag: the local definition as it was (its JSON), for “Return to local tag”. |
NodeLinkState
Section titled “NodeLinkState”NodeLinkState is one CANopen node as the master sees it.
Source: eaxScada/internal/drivers/link_stats.go
| Key | Type | Optional | Description |
|---|---|---|---|
node |
integer | ||
state |
string | ||
alive |
boolean | ||
last_seen_ms_ago |
integer | -1: never | |
emcy_code |
string | yes |
CIPIdentity
Section titled “CIPIdentity”CIPIdentity is a device’s Identity object (class 1, instance 1), read with Get Attributes All when the connection opens.
Source: eaxScada/internal/drivers/ethernetip_device.go
| Key | Type | Optional | Description |
|---|---|---|---|
vendor_id |
integer | ||
device_type |
integer | ||
product_code |
integer | ||
revision |
string | major.minor | |
status |
integer | the Identity object’s status word | |
serial |
string | 0x and 8 hex digits | |
product_name |
string | ||
raw |
string | Raw is the whole Get Attributes All reply, hexadecimal: the byte-string view of the object, for diagnostics. |
UnitLinkError
Section titled “UnitLinkError”UnitLinkError is one unit’s current link error (unitTracker).
Source: eaxScada/internal/drivers/link_stats.go
| Key | Type | Optional | Description |
|---|---|---|---|
unit |
integer | ||
error |
string | ||
since |
integer | Unix ms: when the unit went into error | |
last |
integer | Unix ms: its latest failure |