Export and import the tag database as CSV

eaxPLCHow-to guideFreeProView as Markdown

You edit many variables at once in a spreadsheet (documentation, access, write ranges, new globals) and bring the result back into the project, seeing exactly what will change before anything does.

  • Exporting needs any signed-in user; importing needs an engineer.
  • An import never saves a revision and never deploys. Declaration changes go to the drafts of the POUs you have checked out; documentation goes straight to the documentation files. To run declaration changes you save the drafts, then Test edits or Build & Deploy.
  1. Click Tags, then Export CSV (at narrow widths: More (⋯) → Export CSV).
  2. Pick the Separator and click Export. Use a semicolon for a spreadsheet set to a decimal comma.
  3. The file holds the current revision’s saved declarations (never a draft) and their documentation.

Use Export CSV for a file you will import again. The small CSV button next to the grid’s row count exports the rows as shown, with display texts, and is meant for reading.

The file is UTF-8 with a byte-order mark (spreadsheets then read accents right), CRLF line ends, RFC 4180 quoting. A cell that starts with =, +, -, @, a tab, a carriage return or ' gets a leading ', so a spreadsheet never runs it as a formula; the import removes that ' again. The route is GET /api/project/tags/export?format=csv&sep=; (sep: comma, semicolon or tab).

Column Meaning Kept in
scope GLOBAL:<list>, PROGRAM:<program> or MAIN
pou the declaring POU (a GVL or a PRG)
name the variable’s name
type the declared type as written (REAL, ARRAY[1..20] OF ST_Recipe) declaration
address a direct address (%QX0.1), an alias target (Motors[3].Run, Status.3), or empty for automatic declaration
initial the initial value as written declaration
constant, retain TRUE or FALSE declaration
access none, read, read_write, or empty for the default declaration
write_range low..high, or empty declaration
description, unit, display, notes documentation; description and notes may hold line breaks documentation file

Rules for your edits:

  • Columns can be in any order and are found by their header. A column you delete means “leave as it is”. Unknown columns are ignored and listed.
  • A present but empty cell clears the value: no initial value, automatic address, default access, no write range, empty description. The exception is type: an empty type leaves it unchanged.
  • A row needs its scope or its pou. A new name is a new variable; a new variable without an access gets read.
  • The separator (comma, semicolon or tab) is detected from the header row. The byte-order mark is optional.
  • At most 4 MB and 50,000 rows.
  1. Click Import CSV and choose the file. Click Preview.

  2. The preview lists each row with its status in the row:

    Status Meaning
    Add a new variable
    Change a variable that changes; the changed columns are listed
    Same nothing changes
    Error (rose) the row cannot be applied; the message says why and gives the line
    Needs lock (amber) the row is valid, but its POU is not checked out by you
  3. Fix errors in the file and preview again.

  4. Click Apply N changes. When rows need POUs you have not checked out, the Studio offers Check out and apply. The import is all or nothing: it is refused while any row is an error (400) or needs a lock you do not hold (423, listing the POUs).

  • Declaration changes are in the drafts of their POUs, with draft marks in the tag database. Open each POU (Go to), check it and save it, then test or deploy.
  • Documentation changes are saved at once (no deploy).
  • The PLC’s audit trail holds PROJECT_EXPORT and PROJECT_IMPORT.
Message Fix
N cells, the header has M A row has more cells than the header. Check quoting around commas.
column N is not UTF-8 text (save the file as CSV UTF-8) Save as “CSV UTF-8” in your spreadsheet.
the row needs its scope or pou Fill in one of them.
scope X and pou Y disagree The two columns name different POUs.
access “rw” is none, read or read_write Use one of the three values.
a CONSTANT is never written from outside: its access is read or none Leave access empty or set read on constants.
address “…” is neither a direct address nor an alias target Use %IX0.0, %QW4, %MD8, or a target like Motors[3].Run.
X is already on line N The file declares the variable twice.