MQTT input quality and limits

eaxPLCReferenceProView as Markdown

MQTT inputs are network I/O, not for safety functions. This page lists what the program sees of each entry. How to set up a bus, its sources and entries is in Connect MQTT and Sparkplug B inputs.

The codes are OPC quality codes, as everywhere in eaxware. The label is the text the IDE and GET /api/fieldbus show.

Code Label When
192 (and 192 to 255 from the source) Good A value accepted from a live source.
64 to 127 Uncertain The source says Uncertain; a Sparkplug B sequence gap (until the next NBIRTH); a retained JSON value not proven recent; a timestamp more than 5 s in the future; a JSON quality that is not an integer.
68 Stale No update within max_age_ms (decided in the scan), or an update whose own timestamp was older than max_source_age_ms on arrival.
24 Bad (comm failure) The connection to the broker is lost, NDEATH, DDEATH, or the JSON online topic is false.
8 Bad (not connected) No value yet, no birth (or the birth does not name the metric), bus off, stopped or not started, or a simulated PLC.
4 Bad (config error) A value that does not convert exactly, a malformed payload, or a source that says it is simulated.
0 to 63, other Bad A Bad code the source sent.

A code is Good when its two top bits are set (192 to 255). Uncertain and Stale are never Good.

Downstream quality (UNS, MQTT publisher, OPC UA)

Section titled “Downstream quality (UNS, MQTT publisher, OPC UA)”

A variable wholly inside an MQTT entry’s value is served with the worse of the PLC’s quality (Good while the scan runs, Uncertain while it is stopped) and the entry’s code. The NATS UNS and the MQTT publisher send that code (JSON quality, Sparkplug B Quality property). The OPC UA server gives it as the value’s status:

Code OPC UA status
192 to 255 Good
68 (Stale) UncertainLastUsableValue
64 to 127, other than 68 Uncertain
24 (comm failure) BadCommunicationError
8 (not connected) BadNotConnected
4 (config error) BadConfigurationError
any other code Bad

When only the entry’s quality changes (its value does not), the UNS and the MQTT publisher republish the variable, and the OPC UA server notifies its subscriptions; the OPC UA server looks for such a change every 250 ms. Variables no MQTT entry drives keep the PLC’s quality.

OPC UA Read: value and status from the same cycle

Section titled “OPC UA Read: value and status from the same cycle”

An OPC UA Read of many variables is served from one copy of the process image, shared by the reads of the last 20 ms. The scan writes an MQTT input’s value and decides its quality in the same cycle, so the value and the status a Read returns must come from the same cycle:

  • the image copy is reused only while no input’s quality has changed since it was taken; after a change, the next Read takes a fresh copy;
  • a quality that changes while a Read is being served is read again with a new copy; after 3 tries, the worst quality seen is served;
  • an entry’s quality generation changes before its new quality is stored, so a Read never pairs the new quality with a copy from before the change.

Before, a Read within 20 ms of an earlier one could return an input’s last Bad value with Good status, just after the input turned Good. A Read now costs a fresh image copy whenever an input’s quality changed since the last copy.

Each entry needs a quality signal: its quality bit, or its source’s status bit. The other outputs are optional. All are in %I.

Output Address Value
quality_address %IX TRUE only while the code is Good.
status_address %IB The quality code (USINT).
timestamp_address %IL The source’s timestamp, Unix ms (LINT). The receive time when the source sent none.
age_address %ID ms since the last accepted update (UDINT); 4 294 967 295 before the first value.
Source status_address %IX TRUE while the source is alive: connected and, for Sparkplug B, after its birth and before its death; for JSON with an online topic, after the topic said true and until it says false.
on_bad Value
hold (default) The last accepted value. Before any value: the substitute, or 0 without one.
substitute The substitute literal of the entry’s type (required).
zero 0.

Before the first value, every entry has code 8 and shows its substitute (0 with zero or without a substitute). An entry’s on_bad defaults to its source’s, which defaults to hold.

max_age_ms is checked in the scan, on the monotonic receive time: a Good value older than that turns Stale (68) even if the network side has stopped. An entry’s own max_age_ms overrides its source’s; 0 turns the check off. On a JSON source, max_age_ms (on the source or on every entry) or an online_topic is required. On a Sparkplug B source the default is 0.

GET /api/fieldbus shows, per MQTT source, whether it is connected and alive, seq_gap and no_bdseq, each entry’s code, label, value and age, and these counters. They are not exported as Prometheus metrics.

Counter Counts
received Messages on the source’s topics.
accepted Values accepted.
dropped_rate, dropped_size Messages dropped by a rate limit, or by the payload or metric limit.
malformed Payloads that could not be decoded.
historical, retained Historical Sparkplug metrics ignored; retained messages (Sparkplug: ignored; JSON: taken as Uncertain).
conversion Values refused because they do not convert exactly.
seq_gaps Sparkplug B sequence gaps or repeats.
births, deaths Births and deaths applied.
old_deaths NDEATH messages ignored because their bdSeq differs from the birth’s.
births_without_bdseq NBIRTH messages without bdSeq.
clock_skew Timestamps more than 5 s in the future.
unknown_alias Metrics with an alias the last birth did not define.
simulated Values refused from a source that says it is simulated.
rebirth_requests Rebirth requests sent.

Per bus: bus_dropped_rate (over the bus limit) and bus_unmapped_topics (messages on a topic no source maps).

Setting Default Range
keepalive_sec 5 2 to 60
bus_max_msgs_per_sec (whole bus) 10 000 1 to 1 000 000
max_msgs_per_sec (per source) 1000 1 to 100 000
max_payload_bytes 262 144 (256 KiB) 1024 to 4 194 304 (4 MiB)
max_metrics (per Sparkplug B payload) 10 000 1 to 100 000
max_age_ms, max_source_age_ms 0 (off) 0 to 86 400 000
client_id eaxPLC-<plc id>-in (at most 23 characters) at most 128 characters, no /, +, #
plaintext_reason at least 8 characters
  • Rates are token buckets that allow a burst of twice the rate. The source’s limit is checked before the bus’s. Sparkplug B NBIRTH, NDEATH, DBIRTH and DDEATH are never dropped for rate; the size limits apply to every message.
  • Rebirth requests: at most one per node every 30 s.
  • Clock skew: a timestamp more than 5 s ahead of the PLC’s clock is accepted as Uncertain.
  • Test connection times out after 15 s. Browse listens 5 s by default (wait_ms, 500 to 9000 ms), connection included, and lists at most 5000 metrics or topics.
Route Role Does
PUT /api/fieldbus engineer, e-signed Saves and applies the configuration; secrets in secrets and clear_secrets, write-only. 422 SAFETY_TARGET when an entry covers a safety target.
POST /api/fieldbus/validate engineer Checks a configuration; nothing is applied.
POST /api/fieldbus/mqtt/test engineer Connects once with a bus’s settings and disconnects.
POST /api/fieldbus/mqtt/browse engineer Listens for a source’s births or topics; nothing is sent.

The AI co-pilot is refused on all of them, and a simulated PLC answers 409 on test and browse. All routes: Runtime HTTP API.