A high-performance display shows the operator what is abnormal, and nothing else in colour. eaxScada has five screen objects built for this, in the palette under Widgets › Situational awareness:

Object What it shows Use it for
Moving analog indicator A scale with the normal band, the alarm limits, a pointer for the value and an optional setpoint marker. Any analog value where the distance to its limits matters: levels, pressures, temperatures.
Deviation bar The value minus its setpoint (or a fixed reference), centred at zero, with a tolerance and an alarm deviation. Controlled values: how far is the process from where it should be.
KPI star 3 to 8 values, each over its own range, over the polygon of their normal ranges. A unit or a utility at a glance: one shape that changes when any value leaves its normal range.
Sparkline with limits The last minutes of a tag with its limit lines, the normal band and the current value. Seeing where a value is heading before it reaches a limit.
Mini-trend tile Name, value, unit, quality and a small trend without axes. Rows of KPIs on an overview screen.

The five situational-awareness objects in the operator runtime: moving analog indicators, deviation bars, a KPI star, sparklines with limits and mini-trend tiles. Normal values are grey; a tank level above its high limit and two large deviations are in colour; Bad values are hatched with a red marker; a stale value has a dashed outline. The five situational-awareness objects in the operator runtime: moving analog indicators, deviation bars, a KPI star, sparklines with limits and mini-trend tiles. Normal values are grey; a tank level above its high limit and two large deviations are in colour; Bad values are hatched with a red marker; a stale value has a dashed outline.

Normal values stay grey. Colour appears only for the abnormal ones; Bad and stale values are drawn so they can never be read as good.

Grey by default, colour only when abnormal

Section titled “Grey by default, colour only when abnormal”

On a screen where every value is coloured, the one that matters does not stand out. These objects draw everything that is normal in shades of grey: the scale, the normal operating band (a darker grey), the pointer, the trend line, the star’s polygon. A colour appears only when a value is abnormal:

  • amber when the value is beyond the low or high limit (L, H), outside a KPI star value’s normal range, or beyond a deviation bar’s tolerance;
  • red when the value is beyond the low-low or high-high limit (LL, HH), or beyond a deviation bar’s alarm deviation.

Only the part that is abnormal takes the colour: the zone the pointer is in, the limit line the value has crossed, the readout. When the value comes back, the object is grey again. This colouring is the object’s own drawing: it does not raise, acknowledge or change any alarm, and the alarm engine stays the only place that decides alarms. The objects are display only and never write a tag.

The objects follow the runtime theme (light, dark, and the grey ISA-101 theme of the designer).

The moving analog indicator, the sparkline and the tile draw limits. Alarm limits chooses where they come from:

  • From the value tag’s alarms (the default): the LOW_LOW, LOW, HIGH and HIGH_HIGH alarm definitions of the value tag give LL, L, H and HH. When you change an alarm setpoint, the display follows; you never keep a second copy of a limit. A limit the tag has no alarm for is taken from the hand-set limit of the same kind, when you set one.
  • Set by hand: the four limits you type in the inspector.
  • None: no limits and no zones.

The normal band runs from Normal band from to Normal band to. Left empty, it runs from L to H (or from LL to HH when L or H is missing).

The KPI star has no alarm limits: each of its values has its own Normal from and Normal to, and a value outside that range is marked. The deviation bar compares with its Tolerance and Alarm deviation.

Each object reads its tags itself, through its own fields, with their quality:

  • Value tag (pvTag): the value shown, on every object but the star (the star has one tag per value).
  • Setpoint tag (spTag): on the indicator, the setpoint marker; on the deviation bar, the reference the value is compared with.
  • Without a setpoint tag, a fixed setpoint (indicator) or fixed reference (deviation bar) can be typed instead. A deviation bar with neither has nothing to compare and shows a dash.

The setpoint tag’s quality counts like the value’s. Find where used lists these tags, including each value of a KPI star, so a tag rename or delete warning covers them too.

A value the operator cannot trust is never drawn like a good one:

The value is How it is drawn
Good and current Solid pointer, bar, line or polygon; the readout in the normal text colour, or in amber or red when abnormal.
Uncertain Hollow, with a dashed outline; the readout dimmed and in italics; the amber quality marker.
Not current (stale) Hollow, with a dotted outline; the readout dimmed; the grey “not current” marker.
Bad Hollow and dashed, the object hatched in red, the readout struck through; the red quality marker.
No value yet No pointer, a dash in the readout, the red marker. Trends say No samples yet.

A degraded value never takes the amber or red “abnormal” colour: the object cannot tell whether an untrusted value is beyond a limit. The quality marker’s tooltip names each tag, its quality and how old it is. On a trend (sparkline, tile), Bad and Uncertain samples are drawn apart from good ones, as on every trend. A KPI star leaves a gap where a value has no usable reading instead of drawing it at zero; when every value is Bad, the whole star is hatched.

The general rules for quality on screens are in Show bad and stale values.

On a phone, a screen can open as a list of rows instead of the drawing (see Use the runtime on a phone). Each object becomes one row with its name:

  • the moving analog indicator, the deviation bar and the tile show their value and unit (the deviation bar shows the signed deviation), with the quality marker when the value is not good;
  • the KPI star and the sparkline show a Show trend button.

A phone showing a screen as rows: each indicator, deviation bar and tile is a row with its name and value; the KPI star and the sparklines have a Show trend button; Bad values carry a red marker. A phone showing a screen as rows: each indicator, deviation bar and tile is a row with its name and value; the KPI star and the sparklines have a Show trend button; Bad values carry a red marker.

The same screen as rows on a phone.

The sparkline and the tile show the last minutes of their tag (15 by default, up to 1440). When the screen opens, that window is filled from the historian, then live samples are added, so the trend is never empty just because the screen was just opened. Both have a time zoom; the sparkline also has a slider and PNG and CSV export buttons (the tile has them off by default).