Skip to content

Upgrading a high-availability pair

eaxScadaHow-to guideEnterpriseView as Markdown

Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.

An eaxScada high-availability cluster has three servers: a primary, a standby and a witness. This page explains how to upgrade them to a new build.

  • Plan a maintenance window. While the cluster is stopped, no node accepts control writes.
  • Get the same new build for all three servers.
  • Back up each node’s data directory.
  1. Stop the standby, then the witness, then the primary. Once the standby and the witness are gone, the primary loses quorum and demotes itself, so control writes stop from that point.

  2. Check that no scada-server process of the cluster is still running on any of the three machines.

  3. Replace the scada-server binary on all three machines. Keep the configuration files: the ha: section (role, node_id, cluster_size, lease_ttl, heartbeat_interval) is unchanged. public_url is new and optional; the HA_PUBLIC_URL environment variable sets it per node. If the cluster does not replicate the engineering configuration yet, read Upgrade an existing cluster to replicated configuration before you start the nodes.

  4. Start the witness and the node configured as primary, then the standby.

    On a cluster that has no HA state yet (a new cluster, or one upgraded across commit 6ac5700), no node becomes primary until all three servers are connected. The lease bucket and the term counter are created on three servers from the start. They are never created on one server and moved to three later, because a server restarted after such a move can briefly serve its old copy. Once all three servers are connected, the node configured as primary takes the lease. The standby leaves it free for 8 seconds after it starts.

    Start the configured primary first. The configured role is a preference; one primary at a time is the rule. On a new cluster, a configured standby that starts more than 8 seconds before the configured primary (or while the configured primary is slow to start) takes the lease itself once all three servers are connected: it becomes primary in term 1, and the configured primary then runs as its standby. The term counter hands term 1 out once, so the two nodes are never primary at the same time. /api/ha/status shows which node is primary.

    On a cluster that already has a term counter, a node that cannot find the lease waits before it takes the lease, whatever its configured role. It waits at least the lease TTL plus a sixth of it, and at least 8 seconds after the node starts. A missing lease on such a cluster means unknown, not free.

On each SCADA node, open /api/ha/status and check that:

  • exactly one node reports "is_primary": true;
  • every node reports "has_quorum": true;
  • "lease_replicas" reaches 3 within a few seconds of all three servers being connected. It counts the servers that hold both the lease and the term counter.
  • the "term" of the primary is higher than it was before the upgrade, if the cluster had a term counter before. Terms only increase. They can skip numbers when two nodes try for the lease at the same time.

If two nodes report "is_primary": true, a node is still running an older build. Stop that node and upgrade it.

The new build does not move the state the older build kept in the global account. The lease is taken again when the cluster starts. Replicated alarm and batch state and the shared single-use records start fresh in EAX_HA.

A lease bucket created by an earlier build keeps an expired lease for only three lease TTLs. The new build raises that to 24 hours the first time it runs, and the change applies to the existing bucket. Takeover no longer depends on this setting.

A lease bucket that an earlier build created on one server and later moved to three can still leave a stale copy behind. A new-build node does not take the lease while the lease bucket or the term counter answers as anything other than three servers with an up-to-date follower. A node that reaches only the stale copy waits instead of promoting itself.

Replicated buckets created by an earlier build

Section titled “Replicated buckets created by an earlier build”

The other HA buckets are the alarm snapshot (ha_active_alarms), the integration command nonces (ha_esign_nonces), the e-signature tickets (ha_esign_tickets) and the integration registry (ha_integrations). Newer builds create each of them on three servers from the start, once all three servers are connected, and mark it as created that way. Earlier builds created them on one server and moved them to three later, which leaves the same stale-copy risk as the lease bucket. A stale copy of the ticket bucket could let a signature ticket be redeemed twice, and a stale copy of the nonce bucket could let a signed command be replayed.

A new-build node treats any of these buckets that does not have this mark as an earlier build’s bucket. It does not use that bucket, and the primary replaces it automatically:

  1. Until the primary has replaced a bucket, every node refuses what depends on it. Signature tickets are neither issued nor redeemed, signed integration commands are refused, and integration identities cannot be changed. Each refused ticket or command is written to the audit trail with the reason. The node log shows HA bucket not used for each bucket.
  2. Once the primary has seen a bucket in that state for 10 seconds, and all three servers are connected, it deletes the bucket and creates it again on three servers. The node log shows legacy HA bucket recreated with three replicas.
    • The alarm snapshot and the integration registry are copied into the new bucket. For each alarm, the copy keeps the entry with the highest term. The primary holds its own alarm writes during the copy and writes them afterwards. Every node then reads the whole integration registry again.
    • The ticket and nonce buckets are created empty. Signature tickets issued before the upgrade are refused, so the person signs again. For 65 seconds after the new nonce bucket is created (the nonce lifetime plus 5 seconds of tolerated clock difference), every signed integration command is refused, so a command accepted before the upgrade cannot be replayed.

You do not need to run anything for this. Plan for about a minute after the cluster is up during which signed commands and e-signature tickets are refused.

The primary deletes a bucket only after it has read all of it. If the primary stops after the delete and before the copy is finished:

  • a bucket that was deleted is created again empty;
  • a nonce bucket that is created again while the ticket bucket exists refuses signed commands for the same 65 seconds;
  • an integration registry whose copy did not finish is filled again by the next node that connects, from that node’s own copy of the registry.

Do not delete these buckets by hand.

This replacement assumes every node runs the new build. A node running an earlier build can create a bucket again the earlier way. The new build then treats that bucket as an earlier build’s bucket and replaces it again.

The batch state bucket (ha_batch_state) of earlier builds is no longer used. Batch records now replicate as their chain entries on a stream (see Batch records on a redundant pair). New builds do not create this bucket, read it, write it or replace it. On a cluster upgraded from an earlier build, the bucket stays as it was and is not listed in the HA status. Broker users are still denied it. You can leave it in place.

The primary is the only node that writes batch records. It sends each step’s chain entries to the other nodes on the stream EAX_HA_EBR, in the EAX_HA account, and waits until the cluster has taken them before it answers the step.

  • A forward step or a signature that the cluster does not acknowledge is refused with 503 EBR_NOT_WRITTEN: nothing changes and no setpoint is written. PAUSE, HOLD, STOP and ABORT still take effect; their entries are sent late, and until the cluster takes them the batch takes no forward step and no signature.
  • A step is acknowledged only once another running SCADA node holds its audit record. Before the step’s entries go on EAX_HA_EBR, the primary asks on ha.sync.audit.have; the standby takes what it lacks from the primary and confirms. Not confirmed within 4 s, a forward step is refused (503 EBR_NOT_WRITTEN, REVERTED, as for a stream refusal), and a step toward rest applies and is sent again until it is confirmed. If no other SCADA node runs, steps go on as before. Steps can take up to about 1.5 s longer when the standby lags.
  • After a failover, every acknowledged entry is anchored on the new primary and reads valid once it has caught up. Before, it could stay not_anchored until the old primary came back, or forever if it never did.
  • A running but unhealthy standby (for example one whose audit trail is down) blocks forward batch steps. This is deliberate: record integrity comes before availability. Repair the standby or stop it; see When a forward step is refused because of the standby.
  • A SCADA node that runs but does not answer the confirmation (a node of an earlier build, while the builds are mixed) is not waited for: the step goes on as on a lone primary. The primary logs a warning (“a SCADA node seen running does not answer”) and raises ALM-SYS-HA-AUDIT-UNCONFIRMED until a step is confirmed or it is no longer the primary.
  • The standby applies only entries that link to its own chain, and rebuilds the batch, its phase log and its signatures from that chain. It never saves a batch as it receives it. An entry that does not link stops the replication of that batch on that node.
  • A node that is not the primary refuses every batch step with 409 EBR_NOT_PRIMARY, stops included. Send batch commands to the primary.
  • After a failover, the new primary puts its term marker on the stream and applies every entry up to it before it runs forward steps. Until then it takes steps toward rest only, and its runner does not step.
  • Entries that one node recorded but that never reached the other before a failover are reported as missing in that batch’s EBR (behind_ledger, “recorded in the audit trail on node <node> and missing here”), never invented.
  • Phase logs and signatures now survive a failover. Earlier builds replicated only the batch’s state, without them.
  • Audit records the primary kept to write late (while its audit trail was down) go on EAX_HA_EBR too, subject ebr.late.<batch key>. The standby holds them, and its batch reads not_checked (audit_records_pending) until they are written. After a failover the new primary writes them once, after it has caught up, and the batch reads valid there instead of not_anchored. A node that has run in a cluster waits up to 60 s at start for its replication before it writes such records; records the cluster does not take are sent again after 10 s. See Late audit records on a redundant pair.

The state of this replication is in System Health, HA section, and in GET /api/ha/status under buckets, as EAX_HA_EBR: ok, or what is wrong, such as “batch <id> not replicated here: <reason>” or the number of batches with entries the cluster has not taken yet.

Limits:

  • A STOP on a primary that has not caught up can fork the batch’s record on that node. That batch’s replication then stops there, and the HA status reports it (“the record forked”).
  • A step taken while no other SCADA node was running is anchored on a later primary only once the old primary’s records reach it.
  • With more than two SCADA nodes, the first node to answer confirms. A newly elected node other than that one may lack the anchors until it fetches them from the node that holds them (its audit catch-up).
  • ALM-SYS-HA-AUDIT-UNCONFIRMED takes a node as running for 65 s after it was last seen. A standby stopped on purpose less than 65 s before a batch step can raise it; it clears with the next step the standby confirms once it is back.
  • Batches that ended before the upgrade are reported missing after a failover: their entries were never sent to the other node. Batches still running at the upgrade are sent by the primary.
  • If the old primary writes a late audit record and fails before that record reaches any other node, the new primary writes it too. The audit trail then holds two identical records (same action and version_ref) from two nodes. This is accepted: the batch record still checks valid.

Upgrade both SCADA nodes in the same maintenance window. A node of an earlier build neither sends nor applies these entries, so batch records do not replicate while the builds are mixed.

Details: The batch record’s integrity on redundant pairs.

What HA replicates, and what you must keep identical on every node

Section titled “What HA replicates, and what you must keep identical on every node”

This section describes current behaviour.

An eaxScada cluster is active–passive. One SCADA node holds the primary lease and does the work; the standby takes over when it can take the lease. The nodes do not share the load. The diagram steps through the loss of the primary.

Failover scenarioAn eaxScada pair loses its primary

Step 1 of 3 Normal

An eaxScada pair loses its primary, step 1 of 3: NormalNode A holds the primary lease and does the work: it serves the operator stations and writes to the devices. Node B, the standby, keeps reading its devices and never writes to them.Operator stationseaxScada node Aholds the primary leasePRIMARYeaxScada node Bready to take the leaseSTANDBYWitnessthird replicaPLCs and devicesscreens, writesreplicated stateCMDwritesreadsreadsCMDnever writes

Node A holds the primary lease and does the work: it serves the operator stations and writes to the devices. Node B, the standby, keeps reading its devices and never writes to them.

Step 2 of 3 Primary lost

An eaxScada pair loses its primary, step 2 of 3: Primary lostNode A is lost. Nothing writes to the devices. Node B and the witness still hold two of the three replicas, so node B can take the lease.Operator stationseaxScada node Anot reachableLOSTeaxScada node Bready to take the leaseSTANDBYWitnessthird replicaPLCs and devicesscreens, writesreplicated stateCMDstoppedreadsreadsCMDnot yet

Node A is lost. Nothing writes to the devices. Node B and the witness still hold two of the three replicas, so node B can take the lease.

Step 3 of 3 Standby active

An eaxScada pair loses its primary, step 3 of 3: Standby activeNode B has taken the lease and is primary. It already held the configuration; it reads the whole store again before it accepts changes. For a few seconds the cluster can refuse a save: save again.Operator stationseaxScada node Anot reachableLOSTeaxScada node Bholds the primary leasePRIMARYWitnessthird replicaPLCs and devicesscreens, writesreplicated stateCMDstoppedreadsreadsCMDwrites

Node B has taken the lease and is primary. It already held the configuration; it reads the whole store again before it accepts changes. For a few seconds the cluster can refuse a save: save again.

Active-passive: one node works, the other waits. The witness holds the third replica, so one node and the witness can still agree when the other node is lost.
  • Product
  • Service or process
  • Device or controller
  • Person or role
  • Data or telemetry
  • Command to equipment
  • Replication
Read as text

Two eaxScada nodes and a witness share replicated state. One node holds the primary lease and does the work; the standby reads its devices and never writes. When the primary is lost, the standby takes the lease and becomes primary.

Parts

  • Operator stations (person or role)
  • eaxScada node A (product, primary): holds the primary lease
  • eaxScada node B (product, standby): ready to take the lease
  • Witness (service or process): third replica
  • PLCs and devices (device or controller)

Connections

  • Operator stations → eaxScada node A (data or telemetry): screens, writes
  • eaxScada node A ↔ eaxScada node B (replication): replicated state
  • eaxScada node A ↔ Witness (replication)
  • eaxScada node B ↔ Witness (replication)
  • eaxScada node A → PLCs and devices (command to equipment): writes
  • PLCs and devices → eaxScada node A (data or telemetry): reads
  • PLCs and devices → eaxScada node B (data or telemetry): reads
  • eaxScada node B → PLCs and devices (command to equipment, not active): never writes

Step 1 of 3: Normal

Node A holds the primary lease and does the work: it serves the operator stations and writes to the devices. Node B, the standby, keeps reading its devices and never writes to them.

Step 2 of 3: Primary lost

Node A is lost. Nothing writes to the devices. Node B and the witness still hold two of the three replicas, so node B can take the lease.

  • eaxScada node A: lost, down, not reachable
  • Operator stations → eaxScada node A (data or telemetry, not active): screens, writes
  • eaxScada node A ↔ eaxScada node B (replication, not active): replicated state
  • eaxScada node A ↔ Witness (replication, not active)
  • eaxScada node A → PLCs and devices (command to equipment, not active): stopped
  • PLCs and devices → eaxScada node A (data or telemetry, not active): reads
  • eaxScada node B → PLCs and devices (command to equipment, not active): not yet

Step 3 of 3: Standby active

Node B has taken the lease and is primary. It already held the configuration; it reads the whole store again before it accepts changes. For a few seconds the cluster can refuse a save: save again.

  • eaxScada node A: lost, down, not reachable
  • eaxScada node B: primary, holds the primary lease
  • Operator stations → eaxScada node B (data or telemetry): screens, writes
  • eaxScada node A ↔ eaxScada node B (replication, not active): replicated state
  • eaxScada node A ↔ Witness (replication, not active)
  • eaxScada node A → PLCs and devices (command to equipment, not active): stopped
  • PLCs and devices → eaxScada node A (data or telemetry, not active): reads
  • eaxScada node B → PLCs and devices (command to equipment): writes

The primary renews its lease every ha.heartbeat_interval (0.5 s by default); each renewal sets the lease to expire ha.lease_ttl later (3 s by default). Its renewal deadline is the lease’s expiry minus a sixth of the TTL (0.5 s by default). A renewal that fails for a transient reason (no answer in time, a broker election) is retried until that deadline. Each attempt waits at most one twelfth of the TTL for its answer (at most 500 ms; 250 ms by default). An attempt that timed out is retried at once; a fast error is retried after a short backoff (25 ms, doubling to 200 ms). So during a lease stream leader election the primary tries again every 250 ms or less by default, and renews in the short spells between elections when the stream takes writes. At the deadline the primary demotes with the cause lease_lost and accepts no more control. The deadline always falls before any other node can take the lease. A conflict that is not the primary’s own landed renewal (below) demotes it at once. Before 20 November (eaxScada b4faddea), each attempt waited up to a sixth of the TTL and a timeout was followed by a backoff, so a primary tried about every 700 ms, could miss those short spells, and demoted needlessly.

A renewal can land in the lease store although its reply is lost. The next attempt then finds the lease at a newer revision than the one the primary holds. The primary reads the lease back from the lease stream’s leader, never from a replica that may still be behind, and only reads it: it never writes or extends another node’s lease. It keeps the lease only if it is its own (same node, same term), not expired, at a newer revision; the log says “its earlier renewal landed although its reply was lost … kept”. Another node’s lease or term, a deleted lease, a lease that does not decode or an expired lease demotes the primary at once (cause term_superseded). A read that fails, or that still finds the old revision, is retried until the renewal deadline; then the primary demotes with lease_lost. Before 16 November (eaxScada 48d053dc), the read could be answered by a replica that was behind, and a busy primary demoted with “lease revision conflict on renewal” although no other node had written: needless failovers under CPU load.

This state is kept in the EAX_HA broker account, with three replicas on a cluster of three or more servers. The witness holds the third replica.

  • the primary lease and its term;
  • the states of active alarms, shelves included. A shelve made on the primary is also recorded on the standby, so it survives a restart of the standby;
  • batch records, as their chain entries, synchronously (see Batch records on a redundant pair);
  • audit records: every node keeps every node’s records, primary or standby, and a node that was stopped fetches the ones it missed;
  • e-signature tickets and integration command nonces;
  • the integration registry;
  • the view-only stations (ha_stations, since eaxScada df57e95a): a station paired, changed, disabled or deleted on one node is the same on every node, so paired screens keep working after a failover. See View-only stations on an HA cluster;
  • sign-in lockouts (ha_lockouts, since eaxScada 528843ae): the counts of wrong passwords and the automatic locks, so a lock set on one node holds on every node. See Sign-in lockouts on an HA cluster;
  • eaxTags definitions, scripts, written values and script state;
  • the engineering configuration:
    • projects: pages, docks, shared settings and the plant emergency stop setting, and which project is active;
    • screens, the display tree and reusable components;
    • the deploy manifest of each explicit deploy;
    • driver configuration: channels, devices, tag mappings and register maps. Driver credentials stay sealed. See Driver credentials;
    • alarm definitions and thresholds;
    • master recipes, with their status and signatures;
    • the 3D asset library and dashboards.

How the engineering configuration is replicated

Section titled “How the engineering configuration is replicated”

The cluster holds the engineering configuration in the bucket ha_config and, for large files, the object store ha_config_obj, both in EAX_HA. This copy is the reference. The data folder of each node is that node’s copy of it.

SequenceHow a saved change reaches every node
How a saved change reaches every nodeAn engineering change is saved on the primary of an HA cluster. The primary checks that it may make the change, writes it to the cluster store (the bucket ha_config) first and to its own disk after that, and every node applies it from the store. The diagram also shows the refusals: before anything is written, when the cluster does not take the write (the item changed there meanwhile, or the write was not held), and on a standby. After a failover the new primary reads the whole store again.A CHECK FAILSCLUSTER REFUSESHELD BY THE CLUSTERA SAVE SENT TO A STANDBYAFTER A FAILOVERDev Studioan engineerPrimaryeaxScada nodeStandbyeaxScada nodeCluster storeha_config1Saves a changewith the revision it loadedChecks before it writes anythingit is the primary and has quorumit has read the storethree servers: the bucket has its leader and a current followerthe item is still at the revision Dev Studio loadedRefuses, nothing is written503: no quorum, or not replicated409: changed by someone else, reload2Writes the change to the cluster firstonly over the revision this node last readRefuses the writeanother revision, or not heldRefuses, nothing is saved409: changed elsewhere, reload503: the cluster did not hold itWrites its own disk, applies the changeSaved3Delivers the changeevery node watches the storeApplies itonly changed channels restartwrites nothing to devicesSaves a change409, names the primaryits ha.public_url, when it set one4New primary: reads it all againa save made from an olderreading is refused as a conflict/api/ha/status, under config, on every node: generation, drift, pending
The cluster store is the reference: a change that the cluster does not hold is not saved anywhere.
  • Product
  • Service or process
  • Data store
  • Data or telemetry
  • Replication
  • Configuration or deploy
  • Refusal
Read as text

An engineering change is saved on the primary of an HA cluster. The primary checks that it may make the change, writes it to the cluster store (the bucket ha_config) first and to its own disk after that, and every node applies it from the store. The diagram also shows the refusals: before anything is written, when the cluster does not take the write (the item changed there meanwhile, or the write was not held), and on a standby. After a failover the new primary reads the whole store again.

Participants

  • Dev Studio (service or process): an engineer
  • Primary (product): eaxScada node
  • Standby (product): eaxScada node
  • Cluster store (data store): ha_config

Steps, in order

  1. Dev Studio → Primary (configuration or deploy): Saves a change. with the revision it loaded
  2. Primary: Checks before it writes anything: it is the primary and has quorum; it has read the store; three servers: the bucket has its leader and a current follower; the item is still at the revision Dev Studio loaded
  3. A check fails:
    1. Primary → Dev Studio (refusal): Refuses, nothing is written. 503: no quorum, or not replicated 409: changed by someone else, reload
  4. Primary → Cluster store (replication): Writes the change to the cluster first. only over the revision this node last read
  5. Cluster refuses:
    1. Cluster store → Primary (refusal): Refuses the write. another revision, or not held
    2. Primary → Dev Studio (refusal): Refuses, nothing is saved. 409: changed elsewhere, reload 503: the cluster did not hold it
  6. Held by the cluster:
    1. Primary: Writes its own disk, applies the change
    2. Primary → Dev Studio (reply): Saved
    3. Cluster store → Standby (replication): Delivers the change. every node watches the store
    4. Standby: Applies it: only changed channels restart; writes nothing to devices
  7. A save sent to a standby:
    1. Dev Studio → Standby (configuration or deploy): Saves a change
    2. Standby → Dev Studio (refusal): 409, names the primary. its ha.public_url, when it set one
  8. After a failover:
    1. Standby → Cluster store (data or telemetry): New primary: reads it all again. a save made from an older reading is refused as a conflict
  9. Note: /api/ha/status, under config, on every node: generation, drift, pending
  • Changes are made on the primary. On a standby, every engineering change is refused with HTTP 409 and a message that names the primary. If the primary sets ha.public_url, the message gives that address. A primary that has lost quorum refuses with HTTP 503. You can still open and browse Dev Studio on a standby.
  • A save reaches the cluster first. The primary writes the change to the cluster, then to its own disk. A change is accepted only when the bucket’s leader and at least one other replica hold it. If the cluster cannot keep the change, the save fails with a message, and nothing changes on the primary.
  • Concurrent changes conflict. If an item changed in the cluster after the node read it, the later save is refused. Reload the item and make the change again.
  • Two engineers editing the same item. Screens, projects and their page layouts, components, alarm definitions, recipes, driver channels, devices and tag mappings each carry a revision. Dev Studio sends the revision it loaded with every save. If someone else saved or deleted the item in the meantime, the save is refused with HTTP 409 and Dev Studio shows Changed by someone else — reload. Nothing is overwritten. Reload, then make the change again. This works the same way on a single server and on a cluster. A client that sends no revision (an older script, for example) is still accepted, and the server logs the save.
  • Every node applies each change. Screens, projects, the display tree, alarm definitions and recipes take effect at once on every node. For the drivers, only the channels whose configuration changed are restarted. A standby keeps reading its devices as it did before, and it never writes to them.
  • The plant emergency stop setting moves the signal on every node. While the signal is active, a node keeps the current tag and logs an error. It retries until the signal is clear. Until then the HA status lists the change as not applied.
  • Failover. The standby already holds the configuration when it becomes primary. It reads the whole store again at once. Saves stay accepted during that reading: one made from an older reading is refused as a conflict, never written over a newer change. For a few seconds after a failover, the cluster can refuse saves while it chooses new bucket leaders. Save again.

Each node reports the state of the configuration in /api/ha/status, under config:

  • generation: a hash of every document this node has applied;
  • peers: the generation of each other SCADA node;
  • drift and drift_reason: the nodes do not hold the same configuration, or a change is not applied on this node;
  • pending: the changes this node has not applied yet, with the reason;
  • warnings, for example a driver secrets key that differs from the primary’s;
  • adopted: what this node replaced when it joined the cluster.

accepts_engineering is true on the node where changes can be saved. In Dev Studio, System Health shows the same information in the High availability card. Dev Studio also shows a banner when the configuration drifts (“HA configuration drift: …”), in the language the person chose, with the server’s drift_reason as it is. The standby and quorum-lost banners and the control-status badge follow the chosen language too. After an upgrade, check the Replication card of the System Health HA panel: it lists every replicated store under its own name, those not in use first. A store in use reads replicated; for each store not in use, the note under the rows gives the reason. The System Health HA panel, with the last takeover and why, is described in Metrics, logs and System Health.

Since eaxScada df57e95a the view-only stations are kept in the bucket ha_stations in EAX_HA. A single node keeps its own stations, as before.

  • A station paired, changed, disabled or deleted on one node is the same on every node. A disable or a delete stops the screen on every node within moments and ends its sessions there.
  • Each node binds a station to its own viewer identity of the same username, of the viewer kind. Create the viewer identities on every node, like users. A node without one refuses the station (VIEWONLY_REFUSED, “viewer identity missing, disabled or not of the viewer kind”). Create a missing viewer identity in the Studio of that node: Security > Stations, then Create viewer identity in the toolbar (in the More menu when the window is narrow), with the same name as on the other nodes. The stations that name it and have no viewer there are bound to it at once, each recorded as STATION_REPLICATED. A new viewer identity has no read rule: give it the same read rights as on the other nodes.
  • Or create it with POST /api/security/stations/viewers and {"name": "<username>"} (since eaxScada ca8c23dc): the answer lists the stations bound to it in rebound.
  • On a node where the station has no usable viewer identity, a station change, a new pairing code or a pair-here is refused with 409 viewer_unusable, nothing changed on any node. The message names the viewer identity to create on that node, and the answer carries it as viewer_name. The station dialog explains the refusal and offers Create viewer identity with that name filled in. A change that picks a viewer identity this node has is allowed.
  • A station change is refused with 503 store_unavailable, nothing changed, while the cluster has not confirmed it, or while the node is not yet synchronized or has lost its change feed.
  • Fail closed: a node uses no station credential until it holds the cluster’s stations, a few seconds after it starts or while its change feed is lost. During that time the wall screens show the sign-in page, and VIEWONLY_REFUSED says “stations not synchronized with the HA cluster”.
  • Each change a node applies from the cluster is recorded in its Access audit as STATION_REPLICATED.
  • On upgrade, each node adds the stations it already had to the cluster’s copy, once. After that the cluster’s copy is the reference: a station deleted while a node was stopped does not come back from that node. Check Security > Stations after the upgrade, and delete any station you no longer want.

Pairing codes are redeemed only on the node that issued them. Sign-in lockouts are shared by the nodes (see Sign-in lockouts on an HA cluster). See Set up a view-only station.

Since eaxScada 528843ae the sign-in lockout is shared by the nodes, in the bucket ha_lockouts in EAX_HA. A single node is unchanged.

  • Wrong passwords of sign-ins and of electronic signatures are counted across the cluster. 5 from one address lock the account from that address on every node; 20 from all addresses together lock the account on every node, for 15 minutes.
  • A node that refuses a sign-in because of a lock set by the cluster copies the account lock into its own security store, so its Security > Users shows the account as locked.
  • A correct password clears the count of its address on every node. An administrator’s Unlock or password reset on one node clears the lock and every count of the account on all nodes.
  • Accounts are matched by username: create the same accounts on every node. An administrative lock is still each node’s own.
  • If the bucket does not answer within 500 milliseconds, or cannot be used yet (for example while it is not replicated), that attempt uses the node’s own counts and locks, as on a single node. The node records LOCKOUT_SHARED_UNAVAILABLE at most once a minute, and GET /api/ha/status shows under buckets, as ha_lockouts, that sign-in lockouts are per node until it answers. In System Health, the HA panel’s Replication card shows the Sign-in lockouts row as per node, with the reason under the rows. When it answers again, the node merges its counts and locks into it and records LOCKOUT_SHARED_RESTORED. An unreachable bucket never unlocks anything, and never refuses every sign-in.
  • Limits: while the bucket does not answer, a node does not know about locks that only other nodes set. An unlock made meanwhile applies on that node only, and is recorded; the other nodes keep the lock until it expires, and once the bucket answers the lock applies on that node again: unlock the account again then. Keep the node clocks in sync (NTP): an unlock is compared with the time the lock was set.
  • Broker users are denied the bucket, as every HA bucket.

See Lockout parameters.

Driver credentials: one key for the cluster

Section titled “Driver credentials: one key for the cluster”

Driver credentials, passwords inside broker and endpoint URLs included, are sealed on disk with the driver secrets key, and they stay sealed in the cluster. The key itself is never replicated. Every SCADA node must use the same key: point EAX_DRIVER_SECRETS_KEY_FILE at the same key file on every node, or copy data/security/driver_secrets.key from the primary to the other nodes before you start them.

The key file holds exactly 32 random bytes, stored as raw bytes: not hex, not Base64, and with no trailing newline. A file of any other size is refused at start-up. A node that has no key file creates one of its own, so create the shared file once, before the first start, and never create it again: credentials sealed with one key cannot be opened with another. Back it up.

  • Linux: head -c 32 /dev/urandom > driver_secrets.key, then chmod 400 driver_secrets.key.

  • Windows PowerShell:

    Terminal window
    $b = New-Object byte[] 32
    [System.Security.Cryptography.RandomNumberGenerator]::Create().GetBytes($b)
    [System.IO.File]::WriteAllBytes("driver_secrets.key", $b)

The server reads the file but never changes an existing one. It must be readable by the account that runs the server.

Docker Compose (deploy/pro/docker-compose.ha.yml)

Section titled “Docker Compose (deploy/pro/docker-compose.ha.yml)”

The three nodes of docker-compose.ha.yml share one configuration file, nats-cluster.yaml. The settings that differ per node are set in each service’s environment:

Variable Setting Node 1 Node 2
HA_NODE_ID ha.node_id scada-node-1 scada-node-2
HA_ROLE ha.role primary standby
HA_PUBLIC_URL ha.public_url SCADA_NODE_1_PUBLIC_URL SCADA_NODE_2_PUBLIC_URL
EAX_DRIVER_SECRETS_KEY_FILE driver secrets key /run/secrets/driver_secrets_key /run/secrets/driver_secrets_key

HA_PUBLIC_URL overrides ha.public_url from the configuration file when it is set and not empty. Set the two addresses in a .env file next to the compose file, for example SCADA_NODE_1_PUBLIC_URL=https://scada-a.plant.local:8080.

Both SCADA nodes mount the same host file, secrets/driver_secrets.key, read-only as the Docker secret driver_secrets_key. The witness runs no drivers and does not need it. Create the file once with ./gen-secrets.sh (or gen-secrets.ps1) in deploy/pro. The script keeps an existing key. On Linux, run it as root once so that the container user (uid 10001) can read the file. Then check the file with docker compose -f docker-compose.ha.yml config.

The cluster’s copy of the driver configuration records a fingerprint of the key that sealed it. The fingerprint does not reveal the key. A node whose key differs still applies the configuration, but it keeps every channel that has credentials stopped. The channel shows the reason, and /api/ha/status shows a warning.

This keeps the key out of the broker’s storage. The witness and every backup of the broker data hold only sealed credentials. The key stays only where you install it.

Each node keeps the following on its own disk or volume:

  • users, roles, passwords, sign-in providers and API tokens (a token works on the node that issued it only), and the viewer identities of view-only stations;
  • an administrative lock of an account (the automatic sign-in lockout is shared since eaxScada 528843ae: see Sign-in lockouts on an HA cluster);
  • view-only station pairing codes (a code is redeemed only on the node that issued it) and when and from which address each station was last seen;
  • the historian, its configuration and the alarm journal (the history of alarm events);
  • the licence and the AI assistant settings;
  • key material: the driver secrets key, the PLC token signing key and the NATS NKey seeds (-plc-nkey-seed, -edge-plc-seed-dir). Copy them to every node by hand.
  1. Give every SCADA node the same driver secrets key, the same PLC token signing key and the same NKey seeds.
  2. Create the same users and roles on every node, and the same viewer identities of view-only stations, with the same usernames.
  3. Make engineering changes on the primary.
  4. Before you rely on a failover, check /api/ha/status on every SCADA node: config.drift must be false, config.pending must be empty, and there must be no config.warnings.

Upgrade an existing cluster to replicated configuration

Section titled “Upgrade an existing cluster to replicated configuration”

Builds that replicate the engineering configuration start doing so as soon as the cluster runs them. Upgrade the whole cluster in one maintenance window, as described in Upgrade the cluster. A node running an older build does not read the cluster’s configuration and still accepts changes on its own disk.

  1. Choose the node whose configuration is the reference: projects, screens, drivers, alarm definitions, recipes, 3D assets and dashboards. When the cluster starts for the first time on the new build, the node that becomes primary copies its own configuration into the cluster. Configure that node as primary.
  2. Copy that node’s driver secrets key to the other SCADA node, or point EAX_DRIVER_SECRETS_KEY_FILE at the same file on both nodes. With docker-compose.ha.yml, copy the reference node’s key to deploy/pro/secrets/driver_secrets.key before the first start of the new build. The file is mounted on both nodes. If the reference node’s credentials were sealed with a key you no longer have, create a new file and enter the credentials again after the upgrade.
  3. Optionally, set ha.public_url on each SCADA node to the address users open, for example https://scada-a.plant.local:8080. A standby gives this address when it refuses a change. When the nodes share one configuration file, set HA_PUBLIC_URL in each node’s environment instead.
  4. Start the witness and the reference node, then the standby.

When the standby joins, every item it holds that differs from the cluster is replaced by the cluster’s version. Items the cluster does not have are removed. Before it replaces or removes anything, the node copies its own version to data/ha-config-backup/<timestamp>/, in one folder per kind: studio, drivers, alarms, recipes, assets3d and dashboards. Nothing is deleted without that copy. The node log shows this node adopted the cluster's configuration, and /api/ha/status reports it under config.adopted. A node that was stopped while changes were made adopts them the same way when it starts again.

The witness keeps a replica of the configuration, 3D models included. Give its data volume room for them.