Radial gauge card

eaxScadaReferenceStarterView as Markdown

A radial dial that fills the card, drawn by the same engine as the gauge: grey while the value is normal, the alarm colour only in an alarm band, a Bad, Uncertain or stale value hatched and labelled. Without a tag it shows the fixed value marked STATIC, or NO DATA.

Radial gauge card card

Card palette Display Widgets › Radial Industrial Gauge
Card kind radial_gauge (body.widget)
Default size 3 × 3 grid cells

Double-click the card (or select it and press Enter) to open its settings. The settings are stored in the card’s body.params.

Shown as Key (body.params) Type Unit Default Allowed values What it does
Tag tagPath Tag path (read) — The tag shown. A card without a tag shows its fixed value marked STATIC, or a dash. Settings hint: Without a tag the gauge shows the fixed value, marked STATIC.
Unit unit Text "bar" Unit shown after the value. Display only.
Minimum min Number 0 Value at the start of the scale.
Maximum max Number 10 Value at the end of the scale.
Decimals decimals Number — Decimals shown. Empty: automatic from the range. Settings hint: Empty = automatic from the range.
Bands bandsSource Choice — alarms
manual
none
Where the bands come from: alarms (the tag’s LL / L / H / HH alarm limits), manual (the limits below) or none. Settings hint: alarms = the tag’s LL / L / H / HH alarm limits; manual = the limits below.
Band display bandStyle Choice "auto" zones
marks
track
auto
How the bands are drawn: zones (coloured bands to the scale ends), marks (grey scale, colour only beyond a limit), track (thin band track outside the scale) or auto (marks when the bands would cover over 40 % of the scale). Settings hint: zones = coloured bands to the scale ends; marks = grey scale with limit marks, colour only beyond a limit; track = thin band track outside the scale; auto = marks when the bands cover over 40 % of the scale.
Manual LL limitLL Number — Manual low-low limit (bands manual).
Manual L limitL Number — Manual low limit.
Manual H limitH Number — Manual high limit.
Manual HH limitHH Number — Manual high-high limit.
Needle / bar colour (empty = theme grey) needleColor Text — Colour of the needle or bar. Empty: the theme grey; a value in an alarm band takes the band’s colour.
Fixed value (no tag) value Number — A fixed value shown, marked STATIC, when no tag is set.

The card reads its tag live, with its quality, and shows it on the dial’s face as the gauge does: a Bad, Uncertain or stale value is dimmed, hatched and labelled BAD QUALITY, UNCERTAIN or NO LINK - STALE, and before a first value the card shows a dash and NO DATA, never an invented number. A tag the signed-in account may not read shows a dash, a padlock and NOT READABLE on a blue label (NO ACCESS on a small card), with no number and no needle. A card on a screen with parameters takes {Name} in its tag paths.

The compressed-air pressure on 0 to 10 bar with manual limits (L 5, H 8 bar) drawn as marks.

  1. Click Radial Industrial Gauge in the dashboard palette.
  2. Double-click it: Tag Plant/Processing/Utilities/Air/Pressure, Minimum 0, Maximum 10, Unit bar.
  3. Bands manual, Manual L 5, Manual H 8; Band display marks.

Air pressure with manual limits

6.4 bar: normal, grey.