Radial gauge card
A radial dial that fills the card, drawn by the same engine as the gauge: grey while the value is normal, the alarm colour only in an alarm band, a Bad, Uncertain or stale value hatched and labelled. Without a tag it shows the fixed value marked STATIC, or NO DATA.

| Card palette | Display Widgets › Radial Industrial Gauge |
| Card kind | radial_gauge (body.widget) |
| Default size | 3 × 3 grid cells |
Settings
Section titled “Settings”Double-click the card (or select it and press Enter) to open its settings. The settings are stored in the card’s body.params.
| Shown as | Key (body.params) |
Type | Unit | Default | Allowed values | What it does |
|---|---|---|---|---|---|---|
| Tag | tagPath |
Tag path (read) | — | The tag shown. A card without a tag shows its fixed value marked STATIC, or a dash. Settings hint: Without a tag the gauge shows the fixed value, marked STATIC. | ||
| Unit | unit |
Text | "bar" |
Unit shown after the value. Display only. | ||
| Minimum | min |
Number | 0 |
Value at the start of the scale. | ||
| Maximum | max |
Number | 10 |
Value at the end of the scale. | ||
| Decimals | decimals |
Number | — | Decimals shown. Empty: automatic from the range. Settings hint: Empty = automatic from the range. | ||
| Bands | bandsSource |
Choice | — | alarms manual none |
Where the bands come from: alarms (the tag’s LL / L / H / HH alarm limits), manual (the limits below) or none. Settings hint: alarms = the tag’s LL / L / H / HH alarm limits; manual = the limits below. | |
| Band display | bandStyle |
Choice | "auto" |
zones marks track auto |
How the bands are drawn: zones (coloured bands to the scale ends), marks (grey scale, colour only beyond a limit), track (thin band track outside the scale) or auto (marks when the bands would cover over 40 % of the scale). Settings hint: zones = coloured bands to the scale ends; marks = grey scale with limit marks, colour only beyond a limit; track = thin band track outside the scale; auto = marks when the bands cover over 40 % of the scale. | |
| Manual LL | limitLL |
Number | — | Manual low-low limit (bands manual). | ||
| Manual L | limitL |
Number | — | Manual low limit. | ||
| Manual H | limitH |
Number | — | Manual high limit. | ||
| Manual HH | limitHH |
Number | — | Manual high-high limit. | ||
| Needle / bar colour (empty = theme grey) | needleColor |
Text | — | Colour of the needle or bar. Empty: the theme grey; a value in an alarm band takes the band’s colour. | ||
| Fixed value (no tag) | value |
Number | — | A fixed value shown, marked STATIC, when no tag is set. |
Quality and parameters
Section titled “Quality and parameters”The card reads its tag live, with its quality, and shows it on the dial’s face as the gauge does: a Bad, Uncertain or stale value is dimmed, hatched and labelled BAD QUALITY, UNCERTAIN or NO LINK - STALE, and before a first value the card shows a dash and NO DATA, never an invented number. A tag the signed-in account may not read shows a dash, a padlock and NOT READABLE on a blue label (NO ACCESS on a small card), with no number and no needle. A card on a screen with parameters takes {Name} in its tag paths.
Examples
Section titled “Examples”Air pressure with manual limits
Section titled “Air pressure with manual limits”The compressed-air pressure on 0 to 10 bar with manual limits (L 5, H 8 bar) drawn as marks.
- Click Radial Industrial Gauge in the dashboard palette.
- Double-click it: Tag
Plant/Processing/Utilities/Air/Pressure, Minimum 0, Maximum 10, Unitbar. - Bands
manual, Manual L 5, Manual H 8; Band displaymarks.