Skip to content

Watch the licence end date

eaxPLCHow-to guideProView as Markdown

You know ahead of time when this PLC’s licence ends, what it will no longer do after that date, and you install the renewal before it.

Most eaxPLC licences have no end date (perpetual): nothing on this page applies to them. A licence with an end date is, for example, a trial key.

  1. Open Help > Licence (the Licence & edition view).
  2. The Expires row shows the end date and the days left:
    • more than 30 days: the days, no warning;
    • 30 days or fewer: an amber pill, and a notice naming the date, what the PLC loses after it and what keeps running;
    • after the date: a rose pill and notice: the PLC runs eaxPLC Free.
  3. Administrators also see a marker in the status bar from 14 days before the end and once the licence has ended. It opens Licence & edition.

The PLC also raises diagnostic events at 30, 14, 7 and 1 day(s) left (LICENCE_EXPIRING, severity low, medium, high, critical) and once the date has passed (LICENCE_EXPIRED, critical). They appear in the Diagnostics & Events panel, the audit trail (DIAGNOSTIC / <type>) and on NATS plc.<id>.events. A renewal installed after a warning raises LICENCE_EXPIRY_CLEARED. See Diagnostic events.

GET /api/licence (any signed-in user) returns the licence status under licence:

Field Meaning
expires_at The end date. Absent for a perpetual licence.
expiry_state ok (perpetual, or more than 30 days left), expiring (30 days or fewer), expired.
days_left Days left, rounded up. Only for a licence with an end date; 0 once expired.
loses What the licence’s edition adds to eaxPLC Free, so what the PLC loses after the date: masters (new EtherNet/IP scanners, EtherCAT and CANopen masters), mqtt_inputs (new MQTT and Sparkplug B input buses), xref_checks, dvr, rt_tuning.

A perpetual licence answers expiry_state: "ok" with no days_left.

An expired licence keeps its verified id, licensee, edition, nodes and expires_at in the status, so you can see which licence it was. Its state stays invalid and the PLC runs eaxPLC Free: the licence is shown, never granted.

  • Keeps running: the program, the scan, the outputs, the watchdog, and the fieldbus buses already applied (their approval stamps stay). Deploys keep working.
  • Lost at the next configuration change and the next start: what the edition added to eaxPLC Free (the loses list above). After a restart the PLC starts as eaxPLC Free.
  • The support and security-update dates of a licence raise no event: they do not change what the PLC runs.

Install the renewed licence file in Help > Licence before the date (Lead Engineer or Administrator; audited). A warning already raised clears at once (LICENCE_EXPIRY_CLEARED) when the new licence ends more than 30 days from now or has no end date.