Skip to content

Install eaxScada

PlatformHow-to guideStarterProEnterpriseView as Markdown

Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.

This guide deploys eaxScada on physical servers, virtual machines, edge gateways and containers.


eaxScada is a single binary with an embedded NATS messaging core, a web engineering studio and a historian. Every paid edition has unlimited tags, displays and clients.

  • Free: every feature, at no cost, for evaluation and non-production use on a single node. 2D screen design is fully available; 3D digital-twin scenes can be viewed and run, but 3D design (creating or editing scenes, uploading library models, exporting equipment) starts at Pro. The runtime runs in 60-minute sessions: when a session ends, the runtime stops (drivers stop polling, writes stop) and your projects, screens and history are kept. A person restarts it with one click for another 60 minutes. Free does not run as a high-availability pair.
  • Starter: a perpetual licence for production on a single node. It includes the embedded UNS/NATS backbone, all five field drivers, the web screen designer, the 3D digital twin player (view and run scenes with live data), and the columnar historian engine (the embedded database, as in every edition), which also reads Hive-partitioned CSV history (data/historian/year=YYYY/month=MM/day=DD/tag=.../*.csv) in place.
  • Pro and Enterprise: perpetual licences. They add the features built on the historian (part and lot genealogy, Parquet analytics export), the procedural 2D studio, 3D design with the 3D model library, the DVR recorder, the AI assistant, and LDAP/AD and OIDC single sign-on. Enterprise adds hot standby HA, the 21 CFR Part 11 e-signature workflows and historian encryption.
  • The audit trail (its own database, data/audit/audit.duckdb) records in Starter, Pro and Enterprise; Free has none. It has its own system requirements for the disk that holds it.

Every edition runs the same server program, eaxscada (eaxscada.exe on Windows): the licence you activate decides the edition.

See Editions for the prices and the full feature matrix.

To run Starter, Pro or Enterprise in production, activate your licence on the server. See Activate a licence.

Every edition can be deployed in three forms:

  1. Native binary: the lowest latency, for industrial PCs that need real-time thread affinity and direct fieldbus access.
  2. Docker container: no host dependencies and isolated networking, for skid commissioning, edge gateways and CI pipelines.
  3. Linux service (systemd): a headless deployment with process supervision, watchdog recovery, OS hardening and real-time thread priority.

  • Operating system:

    • Linux with systemd and glibc 2.28 or later: Ubuntu 20.04+, Debian 11+, RHEL 8+
    • Windows: Windows 10/11 Enterprise LTSC, Windows Server 2019/2022
  • Architecture: amd64 (x86_64).

  • Runtime dependencies:

    • Every edition, Starter included: the server links in the columnar historian engine. On Linux it needs libstdc++ (installed on these distributions by default). On Windows, install the Microsoft Visual C++ 2015–2022 Redistributable.
  • The audit trail’s disk (Starter, Pro, Enterprise). The audit trail runs on servers and industrial PCs, not on edge devices. Put its folder (security.audit_data_dir, ./data/audit by default) on a local SSD (NVMe or SATA) or a server RAID with a battery- or flash-backed write cache, with 20 GB or more free, and keep the clock synchronised by NTP. The server checks the folder when the trail opens:

    • refused (the server starts with the trail down: actions that must be recorded first are refused until it is fixed): a network share, a RAM disk, less than 10 GB free;
    • warned: removable media, an SD card or eMMC, less than 20 GB free, sync times that are implausibly fast or slow;
    • the server does not start: the audit folder inside or around the historian folder (a Free server, which records nothing, starts).

    While the server runs, the system alarm ALM-SYS-AUDIT-DISK warns when the audit folder’s volume falls under 10 GB free; System Health’s Audit trail card shows the trail’s state.

    See Audit trail system requirements.

On Linux, eaxScada and eaxPLC are installed as systemd services from their release archives, with the installer in each archive: see 5. Linux service (systemd). The archives are for amd64 (x86_64).

To try the server in a console without installing it, extract the archive and start it with a work directory of your own; it keeps config/, data/ and logs/ under it:

Terminal window
tar -xzf eaxscada_<version>_linux_amd64.tar.gz
mkdir -p ~/eaxscada-trial
./eaxscada_<version>_linux_amd64/bin/eaxscada --workdir ~/eaxscada-trial

The web port comes from server.port in config.yaml, or from the SCADA_PORT environment variable.

  1. Extract eaxscada_<version>_windows_amd64.zip. It holds one folder, eaxscada_<version>_windows_amd64\, with:
    • bin\: the server eaxscada.exe and the libraries it loads (duckdb.dll and the historian_ext\ folder; keep them next to eaxscada.exe), plus scada-cli.exe, plc-server.exe and eaxplc-rt.exe;
    • install.ps1, the installer, and a default config.yaml.
  2. In that folder, open PowerShell as an administrator and run the installer. The examples on these pages use C:\eaxware\eaxScada; without -InstallDir the installer uses C:\Program Files\eaxware\eaxScada:
    Terminal window
    .\install.ps1 -InstallDir C:\eaxware\eaxScada
    It copies the programs to C:\eaxware\eaxScada\bin\, writes config\config.yaml, creates data\ and logs\, and adds bin\ to your PATH (-SkipPath leaves the PATH alone). Add -RegisterService to register the eaxScada and eaxPLC Windows services; a service is started with --workdir set to the install folder.
  3. To run eaxScada in a console instead:
    Terminal window
    C:\eaxware\eaxScada\bin\eaxscada.exe --workdir C:\eaxware\eaxScada
    The server reads config\config.yaml under the work directory.

The container exposes port 8080 (web HMI, Studio, REST, WebSocket) and port 4222 (embedded NATS UNS). The container images are published with the early-access release; replace <eaxscada-image> with the image for your edition:

Terminal window
docker run -d \
--name eaxscada \
--restart unless-stopped \
--stop-timeout 120 \
-p 8080:8080 \
-p 127.0.0.1:4222:4222 \
-v eaxscada-data:/var/lib/eaxware/eaxscada/data \
-v eaxscada-logs:/var/lib/eaxware/eaxscada/logs \
-e SCADA_PORT=8080 \
<eaxscada-image>

Starter, Pro and Enterprise use the same options. --stop-timeout 120 gives a stop 2 minutes to close the stores before Docker kills the container (its default is 10 s): see Stopping without cutting a checkpoint short. The image uses the paths of the Linux installation: the server is /opt/eaxware/eaxscada/bin/eaxscada, its configuration /etc/eaxware/eaxscada/config.yaml (mount your own read-only to replace it) and its work directory /var/lib/eaxware/eaxscada. It runs as user eaxscada (uid 10001). The eaxPLC image runs /opt/eaxware/eaxplc/bin/plc-server with the work directory /var/lib/eaxware/eaxplc.

Publish NATS on loopback (127.0.0.1:4222) unless clients on other hosts authenticate with NKeys. See The Unified Namespace.

  • /var/lib/eaxware/eaxscada/data: persistent storage:
    • Every edition: the columnar historian database file, its spool (data/historian/spool/), the nightly snapshots (data/backup/historian/), any Hive-partitioned CSV history written before the columnar store (data/historian/year=YYYY/month=MM/day=DD/tag={tagPath}/data.csv; no new CSV is written), the ISA-18.2 alarm journal, local users and screen definitions.
    • Starter, Pro and Enterprise: the audit trail, audit/audit.duckdb and its .wal (the volume must be a local disk, not a network share or a RAM disk: requirements).
    • Pro and Enterprise: in addition, Parquet partitions (hive_export/) and the daily Parquet export (historian_export/).
  • /var/lib/eaxware/eaxscada/logs: rotating log files.

Images of earlier releases mounted these volumes at /app/data and /app/logs. The volumes keep their contents: mount the same volumes at the new paths (the Compose files of the release do).


4.1 Starter: eaxScada with an eaxPLC runtime

Section titled “4.1 Starter: eaxScada with an eaxPLC runtime”

The early-access release includes a ready-made Compose file. It runs eaxScada and an eaxPLC runtime that connects to it with the NATS identity eaxScada creates.

Network topologyThe Starter Compose file: two containers on one host
The Starter Compose file: two containers on one hostThe Compose file runs eaxScada and an eaxPLC runtime on one host. Browsers on the network reach eaxScada on port 8080. The NATS broker of eaxScada, the eaxPLC Web Studio and the eaxPLC Modbus TCP server are published on the host's loopback address only. Between the containers, the runtime connects to the NATS broker of eaxScada with the identity eaxScada creates in its data volume, which the runtime mounts read-only; eaxScada calls the PLC API, and the runtime asks eaxScada for sign-in and e-signatures.HOST: THE COMPOSE PROJECTBrowserson the networkPrograms on the hostthrough 127.0.0.1eaxScadaweb, API and MCP gateway: 8080NATS broker: 4222eaxPLC runtimeWeb Studio: 8085Modbus TCP server: 5020Data volumeof eaxScada,with the NATSidentity of the PLC8080422280855020NATSsign-in,e-signaturesPLC APIcreates itread-only
Only port 8080 is open to the network. The broker, the eaxPLC Web Studio and Modbus TCP answer on the host itself until you publish them.
  • Product
  • Service or process
  • Data store
  • Person or role
  • Data or telemetry
  • Configuration or deploy
  • Authentication
Read as text

The Compose file runs eaxScada and an eaxPLC runtime on one host. Browsers on the network reach eaxScada on port 8080. The NATS broker of eaxScada, the eaxPLC Web Studio and the eaxPLC Modbus TCP server are published on the host's loopback address only. Between the containers, the runtime connects to the NATS broker of eaxScada with the identity eaxScada creates in its data volume, which the runtime mounts read-only; eaxScada calls the PLC API, and the runtime asks eaxScada for sign-in and e-signatures.

Parts

  • Browsers (person or role): on the network
  • Programs on the host (service or process): through 127.0.0.1
  • eaxScada (product, inside Host: the Compose project): web, API and MCP gateway: 8080 NATS broker: 4222
  • eaxPLC runtime (product, inside Host: the Compose project): Web Studio: 8085 Modbus TCP server: 5020
  • Data volume (data store, inside Host: the Compose project): of eaxScada, with the NATS identity of the PLC

Connections

  • Browsers → eaxScada (data or telemetry): 8080
  • Programs on the host → eaxScada (data or telemetry): 4222. The NATS broker is published on the loopback address of the host only.
  • Programs on the host → eaxPLC runtime (data or telemetry): 8085 5020. The eaxPLC Web Studio and the Modbus TCP server are published on the loopback address of the host only. Modbus TCP has no authentication: open port 5020 to an isolated control network only.
  • eaxPLC runtime ↔ eaxScada (data or telemetry): NATS. The runtime connects to the NATS broker of eaxScada (4222) over the Compose network, with the identity eaxScada created.
  • eaxPLC runtime → eaxScada (authentication): sign-in, e-signatures
  • eaxScada → eaxPLC runtime (data or telemetry): PLC API. eaxScada calls the PLC API of the runtime on port 8085 over the Compose network (--plc-url http://plc:8085).
  • eaxScada → Data volume (data or telemetry): creates it. eaxScada creates the NATS identity of the runtime in its data volume.
  • Data volume → eaxPLC runtime (configuration or deploy): read-only. The runtime mounts the data volume of eaxScada read-only to read its identity.

From the directory that holds it:

Terminal window
docker compose up -d

Endpoints:

  • Web HMI and Dev Studio: http://localhost:8080
  • Unified Namespace (NATS): nats://localhost:4222 (loopback only)
  • MCP gateway: http://localhost:8080/api/mcp/rpc
  • eaxPLC Web Studio: http://localhost:8085 (loopback only)
  • eaxPLC Modbus TCP server: localhost:5020 (loopback only)

The Compose files publish the eaxPLC Web Studio and the Modbus TCP server on the host’s loopback address only. To reach the Modbus TCP server from devices or HMIs on the network, replace the port line "127.0.0.1:5020:5020" of the plc service with "5020:5020" (the Compose file has it as a comment).

Enterprise high availability is two eaxScada nodes and a witness, active-passive. One node holds the primary lease and does the work; the standby takes the lease when the primary’s lease expires (ha.lease_ttl, 3 s by default; the primary renews it every ha.heartbeat_interval, 0.5 s by default). There is no load balancing between the nodes. The early-access release includes a Compose file for the pair, deploy/pro/docker-compose.ha.yml; the plain deploy/pro/docker-compose.yml starts two independent nodes with no high availability. Each node runs with --ha-role primary or --ha-role standby and a unique --node-id; a third, lightweight node started with --witness provides the quorum.

Failover scenarioAn eaxScada pair loses its primary

Step 1 of 3 Normal

An eaxScada pair loses its primary, step 1 of 3: NormalNode A holds the primary lease and does the work: it serves the operator stations and writes to the devices. Node B, the standby, keeps reading its devices and never writes to them.Operator stationseaxScada node Aholds the primary leasePRIMARYeaxScada node Bready to take the leaseSTANDBYWitnessthird replicaPLCs and devicesscreens, writesreplicated stateCMDwritesreadsreadsCMDnever writes

Node A holds the primary lease and does the work: it serves the operator stations and writes to the devices. Node B, the standby, keeps reading its devices and never writes to them.

Step 2 of 3 Primary lost

An eaxScada pair loses its primary, step 2 of 3: Primary lostNode A is lost. Nothing writes to the devices. Node B and the witness still hold two of the three replicas, so node B can take the lease.Operator stationseaxScada node Anot reachableLOSTeaxScada node Bready to take the leaseSTANDBYWitnessthird replicaPLCs and devicesscreens, writesreplicated stateCMDstoppedreadsreadsCMDnot yet

Node A is lost. Nothing writes to the devices. Node B and the witness still hold two of the three replicas, so node B can take the lease.

Step 3 of 3 Standby active

An eaxScada pair loses its primary, step 3 of 3: Standby activeNode B has taken the lease and is primary. It already held the configuration; it reads the whole store again before it accepts changes. For a few seconds the cluster can refuse a save: save again.Operator stationseaxScada node Anot reachableLOSTeaxScada node Bholds the primary leasePRIMARYWitnessthird replicaPLCs and devicesscreens, writesreplicated stateCMDstoppedreadsreadsCMDwrites

Node B has taken the lease and is primary. It already held the configuration; it reads the whole store again before it accepts changes. For a few seconds the cluster can refuse a save: save again.

Active-passive: one node works, the other waits. The witness holds the third replica, so one node and the witness can still agree when the other node is lost.
  • Product
  • Service or process
  • Device or controller
  • Person or role
  • Data or telemetry
  • Command to equipment
  • Replication
Read as text

Two eaxScada nodes and a witness share replicated state. One node holds the primary lease and does the work; the standby reads its devices and never writes. When the primary is lost, the standby takes the lease and becomes primary.

Parts

  • Operator stations (person or role)
  • eaxScada node A (product, primary): holds the primary lease
  • eaxScada node B (product, standby): ready to take the lease
  • Witness (service or process): third replica
  • PLCs and devices (device or controller)

Connections

  • Operator stations → eaxScada node A (data or telemetry): screens, writes
  • eaxScada node A ↔ eaxScada node B (replication): replicated state
  • eaxScada node A ↔ Witness (replication)
  • eaxScada node B ↔ Witness (replication)
  • eaxScada node A → PLCs and devices (command to equipment): writes
  • PLCs and devices → eaxScada node A (data or telemetry): reads
  • PLCs and devices → eaxScada node B (data or telemetry): reads
  • eaxScada node B → PLCs and devices (command to equipment, not active): never writes

Step 1 of 3: Normal

Node A holds the primary lease and does the work: it serves the operator stations and writes to the devices. Node B, the standby, keeps reading its devices and never writes to them.

Step 2 of 3: Primary lost

Node A is lost. Nothing writes to the devices. Node B and the witness still hold two of the three replicas, so node B can take the lease.

  • eaxScada node A: lost, down, not reachable
  • Operator stations → eaxScada node A (data or telemetry, not active): screens, writes
  • eaxScada node A ↔ eaxScada node B (replication, not active): replicated state
  • eaxScada node A ↔ Witness (replication, not active)
  • eaxScada node A → PLCs and devices (command to equipment, not active): stopped
  • PLCs and devices → eaxScada node A (data or telemetry, not active): reads
  • eaxScada node B → PLCs and devices (command to equipment, not active): not yet

Step 3 of 3: Standby active

Node B has taken the lease and is primary. It already held the configuration; it reads the whole store again before it accepts changes. For a few seconds the cluster can refuse a save: save again.

  • eaxScada node A: lost, down, not reachable
  • eaxScada node B: primary, holds the primary lease
  • Operator stations → eaxScada node B (data or telemetry): screens, writes
  • eaxScada node A ↔ eaxScada node B (replication, not active): replicated state
  • eaxScada node A ↔ Witness (replication, not active)
  • eaxScada node A → PLCs and devices (command to equipment, not active): stopped
  • PLCs and devices → eaxScada node A (data or telemetry, not active): reads
  • eaxScada node B → PLCs and devices (command to equipment): writes

The nodes replicate the primary lease, active alarm states and shelves, running batch state, audit records, e-signature tickets and integration nonces, the integration registry, and eaxTags definitions, scripts, written values and script state. They also replicate the engineering configuration: projects, screens, the display tree, components, deploy manifests, driver configuration, alarm definitions, recipes, the 3D asset library and dashboards. The cluster holds the reference copy. Engineering changes are made on the primary; a standby refuses them and names the primary (set ha.public_url on each node to give its address).

Every SCADA node must use the same driver secrets key (EAX_DRIVER_SECRETS_KEY_FILE): the key is not replicated, and a node with a different key keeps channels with credentials stopped. The nodes do not replicate users, roles and passwords, the historian, the licence or key material: keep these identical on both nodes yourself. See What HA replicates, and what you must keep identical on every node.


For production installations on Debian, Ubuntu or RHEL, eaxScada and eaxPLC run as systemd services, installed from their release archives by the installer in each archive. You get automatic recovery on failure, filesystem sandboxing and the console log in journald. Every edition installs the same way: the licence sets the edition.

Archive Programs (bin/) Service
eaxscada_<version>_linux_amd64.tar.gz eaxscada (the server, the studio embedded), scada-cli, historian_ext/ (historian encryption extension) eaxscada
eaxplc_<version>_linux_amd64.tar.gz plc-server (PLC runtime and Web Studio), eaxplc-rt (edge runtime) eaxplc

Each archive also holds install.sh, the unit (systemd/), the default configuration (config/), LICENSE.txt, NOTICE.txt with licenses/, and BUILDINFO.txt. Check an archive against SHA256SUMS.txt before installing it:

Terminal window
sha256sum --check --ignore-missing SHA256SUMS.txt

The installer and the container images use the same paths:

What eaxScada eaxPLC
Service (unit) eaxscada.service eaxplc.service
System user eaxscada eaxplc
Programs (replaced on upgrade) /opt/eaxware/eaxscada/bin/ /opt/eaxware/eaxplc/bin/
Configuration (never replaced) /etc/eaxware/eaxscada/config.yaml, eaxscada.env, secrets/historian_tde.key /etc/eaxware/eaxplc/eaxplc.env
Work directory: data/, logs/ (never removed) /var/lib/eaxware/eaxscada/ /var/lib/eaxware/eaxplc/
Console log journalctl -u eaxscada journalctl -u eaxplc

The PLC’s NATS identity, /etc/eaxware/nkeys/plc-01.nk, is shared by both services through the group eaxware (owner root, group eaxware, mode 0640): eaxScada’s broker trusts it and eaxPLC connects with it. Each server also keeps a rotating file log in logs/ under its work directory: eaxScada writes it where logging.file in config.yaml says (/var/lib/eaxware/eaxscada/logs/eaxScada.log in the package’s configuration; see Log file).

The units are hardened: no new privileges, the whole file system read-only except the work directory, a private /tmp, devices closed except the serial ports. eaxScada runs without any capability. eaxPLC keeps only CAP_NET_RAW (EtherCAT on a raw Ethernet port), CAP_SYS_NICE and CAP_IPC_LOCK (its real-time scan thread, --rt-priority and --rt-mlock). eaxplc.service starts after eaxscada.service but does not stop with it: restarting eaxScada never stops the PLC scan.

On the machine, as root, from the folder where you downloaded the archives. Install eaxScada first: it creates the PLC’s NATS identity.

Terminal window
tar -xzf eaxscada_<version>_linux_amd64.tar.gz
sudo ./eaxscada_<version>_linux_amd64/install.sh
tar -xzf eaxplc_<version>_linux_amd64.tar.gz
sudo ./eaxplc_<version>_linux_amd64/install.sh

The installer:

  • refuses to run without root, or where systemd is not running (--no-start then installs the files only);
  • creates the group eaxware and the users eaxscada / eaxplc (added to dialout for the serial ports);
  • copies the programs, writes the configuration only if there is none, creates the historian encryption key once (/etc/eaxware/eaxscada/secrets/historian_tde.key: back it up, encrypted history cannot be read without it) and the PLC’s NATS identity once;
  • installs, enables and starts the service. If a port the service needs is already in use (eaxScada: server.port and nats.port, by default 8080 and 4222; eaxPLC: 8085 and 5020), it does not start the service, names the port and the program that holds it, and exits with code 3.

Options: --no-start installs and enables without starting, --uninstall (see below), --migrate (see 5.6), --help.

Running the installer again is safe: it replaces the programs and the unit, and keeps the configuration, the keys and the data.

  • eaxScada: server.port, nats.port and the other settings in /etc/eaxware/eaxscada/config.yaml (see Server flags and configuration); extra server flags in EAXSCADA_ARGS in /etc/eaxware/eaxscada/eaxscada.env.
  • eaxPLC: EAXPLC_ID, EAXPLC_NATS, EAXPLC_SCADA_URL, EAXPLC_HTTP_PORT, EAXPLC_MODBUS_PORT and extra flags in EAXPLC_ARGS (for example --rt-priority 80 --rt-mlock) in /etc/eaxware/eaxplc/eaxplc.env. For a PLC on another machine than eaxScada, copy /etc/eaxware/nkeys/<plc id>.nk from the eaxScada server to the PLC machine (owner root, group eaxware, mode 0640) and set EAXPLC_NATS and EAXPLC_SCADA_URL to the eaxScada server.

Never edit the units in /etc/systemd/system: an upgrade replaces them. Use the environment files or a drop-in (sudo systemctl edit eaxscada); for example, to serve eaxScada on a port below 1024, a drop-in with CapabilityBoundingSet=CAP_NET_BIND_SERVICE and AmbientCapabilities=CAP_NET_BIND_SERVICE. Restart after a change:

Terminal window
sudo systemctl restart eaxscada
sudo systemctl status eaxscada eaxplc
journalctl -u eaxscada -f --output=cat

eaxScada writes its JSON log file to logging.file in /etc/eaxware/eaxscada/config.yaml (or EAX_LOG_FILE in eaxscada.env), /var/lib/eaxware/eaxscada/logs/eaxScada.log as installed. logging.file_enabled: false (or EAX_LOG_FILE_ENABLED=false) writes no log file; the journal keeps the console log.

  • The unit lets the server write under /var/lib/eaxware/eaxscada only. For a log folder elsewhere, for example /var/log/eaxscada, create the folder for the user eaxscada and add it in a drop-in (sudo systemctl edit eaxscada):

    Terminal window
    sudo install -d -o eaxscada -g eaxscada -m 0750 /var/log/eaxscada
    [Service]
    ReadWritePaths=/var/log/eaxscada
  • A log file that cannot be written stops the start. The server does not run without the log the configuration asks for: journalctl -u eaxscada shows “cannot write the log file”, the path, and the two fixes (a writable logging.file, or logging.file_enabled: false).

See Log file for every value.

Stopping without cutting a checkpoint short

Section titled “Stopping without cutting a checkpoint short”

When eaxScada stops, it closes its database stores, and each one writes a checkpoint. A process killed in the middle of a checkpoint can leave a store file that does not open (see When a checkpoint was cut short). The packages therefore give a stop time to finish, and every store has a memory cap so that the system does not kill the server for lack of memory:

Package Time to stop before the kill Historian store memory
Linux archive (eaxscada.service) TimeoutStopSec=120s (was 30 s) historian.store.memory_limit: 1GB in the shipped config.yaml
Appliance image’s eaxscada.service TimeoutStopSec=120s (was 30 s) as its configuration sets it
Compose files of the release (Starter, the two-node file, the HA pair) stop_grace_period: 120s on every eaxScada service (was Docker’s 10 s) 1GB in the full-build image’s configuration and the HA sample; the standard-build image has no columnar store
  • The unit is replaced on upgrade, so an upgraded Linux service gets the 120 s. A drop-in of your own that sets TimeoutStopSec still wins: keep it at 120 s or more.

  • As a Windows service, a stop waits for every store to close. The service reports its progress to Windows while it stops, and reports Stopped only once every store is closed, at most 5 minutes later. At an OS shutdown, Windows applies its own time limit. A script that waits for the service to stop must allow for this time.

  • Every store has a cap, even without the key. A configured value always wins. Without historian.store.memory_limit the historian store takes 25% of the machine’s memory, at least 512 MiB and at most 4 GiB (1 GiB when the memory cannot be read; in a container, its memory limit when it is lower); the other stores take fixed caps of 256 MiB to 1 GiB. The Windows package’s configuration does not set the key, so there the historian takes this default. Memory caps of the stores

  • Your config.yaml is never replaced: an install made before this release keeps its own file, and its historian store gets the default above. To pin the cap the Linux and Docker packages ship, add it yourself, then restart:

    historian:
    store:
    memory_limit: 1GB
  • The start log names each store’s cap: one line DuckDB store memory cap per store, with the cap, the threads and where each came from (config or default).

  • With docker run (no Compose file), give the stop the same time: docker run --stop-timeout 120 ..., and docker stop -t 120 for a stop by hand. A Compose file of your own needs stop_grace_period: 120s on the eaxScada service.

  • Before this release, a store without a cap could take up to 80% of the machine’s memory, each store of the process its own share.

To upgrade, extract the new archive and run its install.sh: it stops the service, replaces the programs and the unit, and starts it again. eaxPLC’s scan stops while the PLC restarts.

To uninstall, sudo ./install.sh --uninstall from the archive (or --uninstall --product eaxscada|eaxplc). It stops and removes the service and /opt/eaxware/<product>; the configuration (/etc/eaxware/<product>), the data (/var/lib/eaxware/<product>), the NATS identities and the users are kept. Remove them by hand only if you want them gone for good.

Earlier installs used other names: the units eaxscada-pro or eaxscada-community (or an eaxscada / eaxplc unit running from /opt/eaxscada), one user eaxscada for both products, the programs in /opt/eaxscada, the data in /var/lib/eaxscada (the eaxPLC data in /var/lib/eaxscada/plc) or in /opt/eaxscada/data, and the configuration in /etc/eaxscada or /opt/eaxscada/config.

The installer finds such an installation, lists what it would move, and changes nothing. Run it again with --migrate:

Terminal window
sudo ./eaxscada_<version>_linux_amd64/install.sh --migrate
sudo ./eaxplc_<version>_linux_amd64/install.sh

With --migrate it:

  1. stops and disables the old units (the old eaxPLC unit too: the PLC scan stops until the eaxPLC archive is installed), and keeps the old unit files in /var/lib/eaxware/migration-<time>/;
  2. moves the data to /var/lib/eaxware/eaxscada and /var/lib/eaxware/eaxplc (nothing is deleted, nothing is overwritten: if a destination exists, or two old folders would land in the same place, it stops before changing anything) and leaves /var/lib/eaxscada as a link to the new folder, so absolute paths in an old configuration keep working;
  3. copies the old config.yaml to /etc/eaxware/eaxscada/config.yaml (if there is none yet) and lists its lines that still name the old paths; change them when you can;
  4. keeps the PLC’s NATS identity (data/security/nkeys/plc-01.nk) as /etc/eaxware/nkeys/plc-01.nk, so PLCs that already use it keep connecting;
  5. writes what it did to /var/lib/eaxware/migration-<time>/MIGRATION.txt.

/opt/eaxscada (the old programs) and /etc/eaxscada are left as they were: remove them once the new installation runs. Settings of the old /etc/eaxscada/eaxscada.env are not read any more: move them to the new environment files. Update scripts, monitoring and backups that name eaxscada-pro, /opt/eaxscada or /var/lib/eaxscada.


Terminal window
curl -i http://localhost:8080/api/health

A healthy server answers 200 OK with a JSON body that reports its status, version and tier.

With the nats CLI, check that the embedded broker accepts connections:

Terminal window
nats --server=nats://127.0.0.1:4222 rtt

Open a browser on the server:

  • Dev Studio: http://localhost:8080/
  • Operator runtime: http://localhost:8080/runtime
  • MCP discovery: http://localhost:8080/api/mcp

A new installation has exactly one account, admin (role Administrator). There are no sample users and no sample groups, and no published password.

At its first start the server gives admin a random password of 25 characters (lower-case letters and digits, in groups of five) and writes it to data/security/initial_admin_password under the work directory. The file is readable only by the account the server runs as: mode 0600 on Linux; on Windows, a protected ACL that grants the server’s account, SYSTEM and Administrators and nothing else. The log says once where it is:

WARN first start: the admin password is in data/security/initial_admin_password; you must change it at first sign-in

The password is never logged and never sent by any API.

  1. Read the file on the server: sudo cat /var/lib/eaxware/eaxscada/data/security/initial_admin_password for the Linux service, docker exec eaxscada cat /var/lib/eaxware/eaxscada/data/security/initial_admin_password for the container above, or open C:\eaxware\eaxScada\data\security\initial_admin_password as an administrator on Windows.
  2. Sign in as admin with that password. The sign-in page asks you for a new password before it opens a session.
  3. Choose the new password, at least 12 characters. The server deletes initial_admin_password and logs that it did.

Until the password is changed, it opens no session, even after a restart and even if you delete the file by hand.

Automated installs: set the first password

Section titled “Automated installs: set the first password”

For an unattended install (Docker secrets, configuration management), give the first password to the server instead:

Variable Effect
EAX_ADMIN_PASSWORD_FILE Path of a file holding admin’s first password (one line). Preferred.
EAX_ADMIN_PASSWORD admin’s first password itself. It can be read in the process environment (docker inspect, /proc), so prefer the file. The server removes it from its environment once read.
EAX_ADMIN_PASSWORD_CHANGE_REQUIRED true by default. false lets admin keep a password given by one of the two variables above, without the change at first sign-in. It has no effect on a generated password. The server logs a warning when it is false.

The password must be at least 12 characters. Setting both variables, or giving a shorter password, stops the server at start-up. No initial_admin_password file is written in this case.

These variables act only on a new installation, when the security store has no account. On an existing installation they are ignored (the log says so): no account is ever created, changed or deleted at start-up.

Keep EAX_ADMIN_PASSWORD_CHANGE_REQUIRED at true unless the password stays in a secret store that you rotate. Otherwise, whoever reads the password from the deployment files can sign in as admin.

On an HA pair, each node has its own users. Give every node the same EAX_ADMIN_PASSWORD_FILE, or sign in on each node with its own initial_admin_password. Create the same accounts on every node, and the same viewer identities for view-only stations, with the same usernames: the stations are replicated between the nodes, but each node binds a station to its own viewer identity of that name. Sign-in lockouts are shared by the nodes, matched by username: a lock set on one node holds on every node, and an unlock on one node clears it on all (Lockout parameters).

Create one account per person under Security > Users, with the role they need (Shift_Operator, Process_Supervisor, Lead_Engineer, Compliance_Auditor). A local account’s password must be at least 12 characters, whenever it is set: created, changed or reset by an administrator, or chosen to replace a default or first password. Passwords set before this rule keep working until they are changed. The AI_CoPilot role is for the account of an external AI agent that connects to the MCP gateway. Create that account only if you connect one, and give it its own password.

Earlier versions created sample accounts with published passwords: admin, engineer, supervisor, operator, auditor and ai_copilot. An upgrade keeps every existing account as it is. If any of them still has its published password:

  • the server logs a warning at every start that names them;
  • Security > Users shows them in a red banner above the users table;
  • outside developer mode, they cannot sign in until their password is changed.

Change their passwords, or disable or delete the accounts you do not use.