eaxCloud
Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.
eaxCloud is an optional subscription on top of the software you run on site. Your eaxScada and eaxPLC licences stay yours: eaxCloud adds what only makes sense across many sites. Your sites never depend on it: eaxScada and eaxPLC run the plant locally, with or without a cloud connection. Planned plans and prices are listed in Editions; nothing is sold before 2027.
Status
Section titled “Status”| Capability | Status |
|---|---|
| eaxCloud portal. Accounts, organisations, members and roles, sign-in with a second factor or a passkey, sites, licences and downloads, and a shop that runs in test mode. | Early access, invite only |
| Virtual commissioning. Upload Structured Text programs and a plant scenario (tanks, pumps, valves, motors, conveyors, heat exchangers). eaxPLC instances run against it in real time or faster than real time, with injected faults and bit-exact snapshot replay. It runs in our lab, driven through a REST API that a build pipeline can call; it is not yet a hosted service. | Lab-tested, pilots on request |
| Fleet management. Shows every eaxScada and eaxPLC node on one dashboard, across sites: online state and last heartbeat, version and edition, health (with an eaxPLC’s scan time), and active alarms. A node enrols with a one-time token and can be revoked; its details show its heartbeat history and its alarm and event messages, and members get notified when a node needs attention, in the portal or by e-mail. | Built, early access 2027 |
| Remote access without a VPN. View a site from anywhere; operating and engineering need the site’s own switches, sign-in and e-signature. A session opens from the node’s details in Fleet, end-to-end encrypted between your browser and the site, over the site’s outbound connection. The site decides: its switches in Settings > Cloud, accounts marked “May sign in remotely”, a banner on every screen at the site, and local acceptance of operate and engineer sessions. See Allow remote access from eaxCloud. | In final testing, early access 2027 |
| Cloud history. A copy of the tags each site chooses to send, with their quality. | In development, early access 2027 |
| Change tracking for GxP. Each eaxScada already records deploys, screen edits and setpoint changes in its own tamper-evident audit ledger. eaxCloud is designed to bring every site’s ledger into one timeline. | In development, early access 2027 |
| Signed updates (OTA). The cloud offers a signed update to a site; a person at the site accepts it, runs the site’s own checks and applies it. Nothing is applied automatically. | In development, early access 2027 |
| Asset management. A register of controllers, servers and instruments, built from what the nodes report. | Planned |
The two parts of eaxCloud
Section titled “The two parts of eaxCloud”eaxCloud is built from two separate services.
The eaxCloud portal
Section titled “The eaxCloud portal”The portal is the customer site at app.eaxware.com, in early access by invitation. It holds your organisation, its members and their roles, the sites you register, your licences and the downloads. Sign-in supports a password with an authenticator-app code, and passkeys, and asks again before sensitive actions. Its shop runs in test mode: nothing is sold before 2027. Enrolled sites send their status to the portal; remote access to a site opens from the portal only as far as that site allows it. eaxware cannot read your remote sessions; a compromise of eaxware’s servers could still target a session you open.
Language. The portal’s interface is in English, French, German, Italian and Spanish. Choose it from the language picker at the top of the sign-in pages, at the foot of the side menu, or in your account settings; each language is listed in its own name. The choice is remembered in this browser (not yet per account); without one the portal starts in the first of your browser’s languages it has, else English.
A new passkey is named in your portal language when you create it (for example “Clé d’accès” in French, “Llave de acceso” in Spanish), in account settings and in the second-factor setup; the name stays as it was given if you later switch the portal to another language. A remote session opens in the portal’s language too: its start page shows its messages in the language you chose in the portal, in any of the five, and the session remembers nothing of it. The page that explains why a session ended or was lost uses your browser’s language when it has it, else English. Remote access is not yet offered in production (see below), so this applies once it is.
The virtual-commissioning simulation service
Section titled “The virtual-commissioning simulation service”Virtual commissioning runs on a separate simulation service in the eaxPLC repository (eaxPLC/cmd/eaxsim-cloud). Its binary, eaxsim-cloud, was called eaxcloud until October 2026 and was renamed so that it is not confused with the portal; its configuration file loads unchanged. Tenants create plant emulations, each one an eaxsim process that runs as its own Linux user in its own cgroup, reach them through an authenticated proxy, and are metered in scan credits.
It takes two keys. The tenant API key opens the simulation API under /v1/ (for example /v1/sims and /v1/usage), limited to that tenant’s own simulations. The admin key, read from the file named by admin_key_file, opens only the tenant management API under /admin/v1/tenants, through which the portal is designed to create and manage tenants; neither key opens the other’s routes. A simulation runs with no broker at all unless an administrator has configured its tenant with a commissioning_target and acknowledged that simulated values will appear on that eaxScada: only then do its simulated PLCs attach to that eaxScada’s broker. A build pipeline drives the service with the eaxsimctl command-line client (create, start, wait for the run’s end, fetch the checks report, stop, delete). eaxsimctl test runs a scenario locally in virtual time, checks its expect entries and exits 0, 1 or 2; a virtual run on the service checks them too and gets a pass or fail verdict (see eaxsim scenario checks).
Every route is listed in the eaxsim-cloud HTTP API reference, the configuration file in the eaxsim-cloud configuration reference, and the flags of both binaries in the eaxPLC command-line reference. It runs in our lab and is not yet a hosted service: pilots are on request, and its tenants are not yet linked to portal accounts.
How sites connect
Section titled “How sites connect”- Product
- Service or process
- Person or role
- Trust boundary
- Data or telemetry
- Command to equipment
Read as text
An eaxScada node at the plant opens two outbound NATS leaf node connections over TLS to the same eaxCloud address and port: the fleet connection, which sends status out and imports nothing, and a separate remote-access connection that exists only while a remote-access switch at the site is on. A remote user reaches the site through a relay that sees ciphertext only. Commands cannot enter the plant from the cloud.
Parts
- Plant site (trust boundary)
- eaxCloud (trust boundary)
- Remote user (person or role): a browser
- eaxScada node (product, inside Plant site): own device key sign-in, rights, e-signatures, audit, remote-access check
- Plant message broker (service or process, inside Plant site): uns.command.> plc.<id>.api
- Session relay (service or process, inside eaxCloud): relays ciphertext only
- Fleet account (service or process, inside eaxCloud): one NATS account per customer imports nothing from the site link
Connections
- Remote user ↔ Session relay (data or telemetry): session. End-to-end encrypted between the browser and the site.
- eaxScada node ↔ Session relay (data or telemetry): only while a remote-access switch is on. The remote-access connection: a second outbound NATS leaf node connection over TLS, to the same address and port, with its own key, kept in memory and renewed daily.
- eaxScada node → Fleet account (data or telemetry): status out. The fleet connection: an outbound NATS leaf node connection over TLS, authenticated by a key the device generates itself.
- Fleet account → Plant message broker (command to equipment, not active): never imported. Command subjects can never be imported from the cloud.
- eaxScada node → Plant message broker (relation)
Both are outbound NATS leaf connections, same address and port. The remote connection has no route to the plant broker.
- A site connects to eaxCloud with an outbound NATS leaf node connection over TLS, authenticated by a key the device generates itself; the private key never leaves the device. The plant firewall needs no inbound port.
- Each customer gets its own NATS account, so one customer’s data and connections are isolated from another’s.
- The fleet connection carries the node’s status out (its heartbeat) and imports nothing from the cloud. Command subjects (
uns.command.>, which carriesuns.command.write, andplc.<id>.api) can never be imported from the cloud. - Remote access also goes through NATS, over the same outbound path: see below.
One outbound path, two NATS connections
Section titled “One outbound path, two NATS connections”A site that allows remote access opens two connections to eaxCloud. Both are NATS leaf node connections. The site opens both itself, outbound, over TLS, to the same eaxCloud address and port. The site firewall needs one outbound rule and no inbound port. There is no VPN.
| Fleet connection | Remote-access connection | |
|---|---|---|
| When it exists | Always, while the cloud link is on. | Only while one of the site’s remote-access switches is on (Settings > Cloud, a setting the cloud cannot change). |
| What it sends | The node’s heartbeat, alarms and events. | The site’s side of that node’s own remote sessions, encrypted. |
| What it accepts from the cloud | Nothing. | Only the subjects of that node’s own sessions. |
| Key | The key the device generated at enrolment. | Its own key, kept in memory only and renewed daily. |
| When it ends | When the cloud link is turned off or the node is revoked. | Within two seconds of the last switch going off. |
The browser never holds a NATS credential. It talks to eaxCloud over a secure WebSocket (WSS). eaxCloud relays the end-to-end-encrypted traffic onto the remote-access connection, and the site decrypts it.
Why two connections and not one
Section titled “Why two connections and not one”- Separate keys. The key that sends the heartbeat can never carry an operate or engineer request. The remote-access key can never send a heartbeat, an alarm or an event.
- Off means no connection. When remote access is off at the site, the remote-access connection does not exist. Nothing is left open with a permission that refuses requests: there is nothing to reach.
- Fleet monitoring never stops. Turning remote access on or off never interrupts the fleet connection. A failure of the remote-access connection does not affect it either.
- Isolation an auditor can check. The remote-access connection comes from a separate component inside eaxScada. That component has no route to the plant’s own message broker. A remote request becomes an ordinary request to the eaxScada server. It goes through the same sign-in, rights, e-signatures and audit as a local browser, plus a remote-access check of its own.
Remote sessions
Section titled “Remote sessions”- A remote session is end-to-end encrypted between your browser and the site, pinned to the site’s remote key, whose fingerprint is shown in Settings > Cloud and in the portal. eaxCloud relays ciphertext only. Each session opens on its own address, separate from the portal.
- Turning a switch off at the site ends the sessions it no longer allows within a second, and the remote-access connection is gone within two seconds when every switch is off. The sessions’ last messages, with the reason each ended, reach eaxCloud before that connection closes (When the site ends a session). “End remote sessions” at the site ends them all and refuses new ones for 60 minutes.
- Revoking a node revokes its fleet and remote keys and disconnects it from the cloud. Disabling remote access for a node or for the organisation in the portal revokes its remote key and ends its sessions. The site keeps running locally.
Changes
Section titled “Changes”Upcoming, in the next eaxCloud release: a remote page’s live data waits for the site, choose the columns of portal tables
Section titled “Upcoming, in the next eaxCloud release: a remote page’s live data waits for the site, choose the columns of portal tables”These changes are not yet on the eaxCloud service. They come with the next eaxCloud release.
- SAFETY: a remote page’s live data socket opens only once the site has accepted it. This concerns what the person working remotely sees about the link. In a remote session, the page’s live data socket (
/ws) now reads open only when the site’s answer accepting the upgrade arrives through the tunnel. Before, it read open as soon as the request was sent. Over a dead link the session stays open until it is found dead (45 s), so an eaxScada page that had just dropped its silent socket got its next one “open” at once, and its link could read online again until the session ended: GATEWAY OFFLINE hidden while no value arrived. Remote access is not yet offered in production, so this takes effect when remote access is offered. - No answer from the site in 60 s fails the socket. The page’s socket gets an error, then closes with code
1006, and the site’s end of the stream is reset (504, “no response”). The session goes on, and the socket’s place in it is free again. A socket the site has accepted is never timed out this way. - A message from the site before its answer resets the socket. The message is never delivered to the page. A second answer from the site changes nothing.
- eaxScada’s side of this, which reads a reopened socket’s link up only at its first frame, is in A reopened socket that delivers nothing.
- A Columns button next to Export CSV. Every table of the portal gets a Columns menu with a check box per column, by mouse or keyboard, and Reset. Your choice is remembered per table in this browser and wins over the columns a phone or a narrow window hides by default; Reset gives the columns back to those defaults. Pinned columns and the row’s own identity stay (“Always shown”), the actions are not listed, and the last column shown cannot be hidden. The table changes in place: filters, sort and scroll stay.
- Export CSV leaves out the columns you hid. Columns hidden only because the screen is narrow are still exported, as before.
16 November 2026: remote session pages, in effect when remote access is offered
Section titled “16 November 2026: remote session pages, in effect when remote access is offered”The eaxCloud service was updated in production on 16 November 2026 (release eaxcloud-rel-20261116), with the changes below. Remote access is not yet offered in production, so these relay behaviours take effect when remote access is offered.
- An ended session’s page says why it ended. When a remote session ends, its page shows the reason (for example “The session was ended at the site.” or “The session ended after 15 minutes without activity.”) instead of a not-found error. For 10 minutes after the end, the session’s address still serves the files of that page (
open,boot.js,boot.css,frames.js, GET and HEAD only). Everything else on that address, the claim, the tunnel and the session itself included, answers not found as soon as the session ends. These files are part of the release and hold no session data. - Static files are checked, not downloaded again, on every page load. In your browser, the remote session keeps a copy in memory of each
/static/file of the site’s eaxScada (scripts, styles, fonts) that it received with an ETag. On the next load it asks the site whether the file changed (If-None-Match); when it has not (304), the kept copy is used. API answers, pages, answers markedno-storeorprivate, answers that set a cookie and partial answers are never kept. The copies are capped at 64 MB per session (16 MB per file), are never written to disk or browser storage, are never shared between sessions, and are dropped when the session ends. eaxCloud still relays ciphertext only. In our test, the second and later page loads of a session went from 8.2 s and 21.7 MB through the tunnel to 0.8 s and 2.8 MB.
November 2026: enrolment limits follow the Fleet tier
Section titled “November 2026: enrolment limits follow the Fleet tier”- Enrolment limits follow the organisation’s Fleet tier. Creating an enrolment token and enrolling a node are checked against the tier of the organisation’s Fleet account. On Developer, a fourth enrolled node, or a node on a second site, is refused (
409, Developer tier limit: one site and three enrolled nodes per organisation). Fleet and Enterprise are not capped by enrolment. Before, every organisation got the Developer limits, whatever its tier. - Fail closed. An organisation without a Fleet account yet, or whose account has an unknown tier, gets the Developer limits. If the tier cannot be read for another reason, the enrolment is refused.
- A pending Fleet tier is kept. The tier an operator sets with
eaxcloudctl fleet set-tierbefore the organisation has a Fleet account is applied when the account is created. Other changes to the organisation can no longer drop or replace it.