Runtime metrics and health snapshot
Migrated page, not yet verified against the current code. Treat values, paths and examples as indicative until this notice is removed.
The eaxPLC runtime (plc-server, plc-runtime) reports its health in two forms that carry the same values:
GET /metrics: the Prometheus text format (version 0.0.4), for a Prometheus server or any compatible scraper.GET /api/metrics/snapshot: a compact JSON snapshot with a versioned schema. Like every/api/route, it is also served on the PLC’s NATS API (plc.<id>.api). eaxScada’s System Health workspace reads it there, so it needs no HTTP path to the PLC.
Both are in every edition.
Counters count from the runtime’s start. They restart at 0 when the runtime restarts; Prometheus rate() and increase() handle that. Fieldbus device counters also restart when a fieldbus configuration is applied.
Cost to the scan
Section titled “Cost to the scan”Neither endpoint adds work, a lock or an allocation to the scan:
- The values the scan produces are read with atomic loads: the latency histogram, the cycle, overrun and force counts. They are never read under the lock the scan records its statistics with.
- Go runtime values come from
runtime/metrics, which does not stop the world.runtime.ReadMemStats, which does, is not used.
A scrape takes about 70 µs on another goroutine and allocates about 15 KB.
Access
Section titled “Access”| Endpoint | Who may call it |
|---|---|
GET /metrics |
Any valid session or PLC token: the same rule as GET /api/stats. Anonymous only with --metrics-anonymous-localhost, and only from the loopback interface. |
GET /api/metrics/snapshot |
Any valid session or PLC token, over HTTP or NATS. Never anonymous. |
/metrics sits outside /api/ by Prometheus convention, but the runtime guards it like an /api/ read. Any other method than GET or HEAD is refused: 403 below the engineer level, 405 for an engineer.
--metrics-anonymous-localhost (off by default) lets a scraper on the same machine read /metrics without a token:
- A request whose remote address is not loopback still needs a token.
- A request carrying
X-Forwarded-For(relayed by a local proxy) still needs a token. - The option never opens
/api/metrics/snapshotor any other route.
For a remote Prometheus, mint a token at the lowest role and give it to the scraper as a bearer credential. PLC tokens are valid for 720 hours at most, so renew it before it expires.
plc-server token mint -user prometheus -role Compliance_Auditor -ttl 720h > /etc/prometheus/eaxplc.tokenscrape_configs: - job_name: eaxplc scrape_interval: 15s authorization: type: Bearer credentials_file: /etc/prometheus/eaxplc.token static_configs: - targets: ['plc-01.plant.local:8085']Prometheus metrics
Section titled “Prometheus metrics”Every eaxplc_ series carries the label plc_id (--plc-id). The other labels are bounded: no tag or user names. Units are seconds and bytes.
Runtime and scan
Section titled “Runtime and scan”| Metric | Type | Labels | Meaning |
|---|---|---|---|
eaxplc_build_info |
gauge | version, goversion |
Always 1; the labels carry the build. |
eaxplc_start_time_seconds |
gauge | Unix time the runtime started. | |
eaxplc_uptime_seconds |
gauge | Seconds since start. | |
eaxplc_running |
gauge | 1 when the PLC scans its program (not stopped, not faulted). | |
eaxplc_paused |
gauge | 1 when the PLC is in STOP. | |
eaxplc_faulted |
gauge | 1 when a program fault or a watchdog trip put the PLC in STOP. | |
eaxplc_target_frequency_hz |
gauge | Target scan frequency. | |
eaxplc_program_version |
gauge | Version number of the running program (+1 per deploy since start). | |
eaxplc_scan_cycles_total |
counter | Scan cycles run. | |
eaxplc_scan_overruns_total |
counter | task |
Cycles longer than 110 % of the period. |
eaxplc_watchdog_trips_total |
counter | Overrun watchdog trips. | |
eaxplc_scan_duration_seconds |
histogram | task |
Program execution time per cycle. |
eaxplc_scan_jitter_seconds |
histogram | task |
Period error per cycle: |actual period − target|. |
eaxplc_scan_jitter_quantile_seconds |
gauge | task, quantile (0.5, 0.95, 0.99) |
Jitter quantiles over the last 10 s. NaN when no cycle ran in the window. |
eaxplc_scan_duration_quantile_seconds |
gauge | task, quantile (0.5, 0.95, 0.99) |
Execution time quantiles over the last 10 s. |
eaxplc_scan_jitter_max_seconds |
gauge | task |
Largest jitter since start. |
eaxplc_scan_duration_max_seconds |
gauge | task |
Longest execution since start. |
task is main: the real-time loop.
The two histograms have buckets at 1, 2, 5, 10, 20, 50, 100, 200 and 500 µs, then 1, 2, 5 and 10 ms. Their _sum is exact.
The histograms only grow. POST /api/stats/latency/reset clears what /api/stats/latency shows, but not these.
The quantile gauges are estimated from the bucket counts of the last 10 s, by linear interpolation inside a bucket. For quantiles over another window, use histogram_quantile() on the histograms.
Cycle recorder (DVR)
Section titled “Cycle recorder (DVR)”| Metric | Type | Meaning |
|---|---|---|
eaxplc_dvr_enabled |
gauge | 1 when the recorder is enabled (--enterprise). |
eaxplc_dvr_recording |
gauge | 1 while it records. |
eaxplc_dvr_epoch |
gauge | Cycle counter epoch of the newest recorded cycle: +1 each time the cycle counter restarts. |
eaxplc_dvr_recorded_cycles_total |
counter | Cycles recorded. |
eaxplc_dvr_lost_cycles_total |
counter | Cycles missing from the recording (gaps). Alert on any increase. |
eaxplc_dvr_disk_blocks_dropped_total |
counter | Closed blocks not written to disk because the writer was behind (--audit-disk). |
eaxplc_dvr_memory_bytes |
gauge | Memory the recording holds. |
eaxplc_dvr_memory_limit_bytes |
gauge | Its cap (--dvr-max-mb). |
eaxplc_dvr_retained_seconds |
gauge | History the recording holds. |
eaxplc_telemetry_queue_dropped_total |
counter | Cycles the scan could not queue to the recorder because the queue was full. |
eaxplc_websocket_open |
gauge | Telemetry WebSockets (/api/telemetry) open now. |
eaxplc_websocket_refused_total |
counter | Telemetry WebSockets closed with 1008 by a concurrent socket cap, by reason: per_session (--ws-max-per-session) or per_ip (--ws-max-per-ip). |
Operator actions and program changes
Section titled “Operator actions and program changes”| Metric | Type | Labels | Meaning |
|---|---|---|---|
eaxplc_forces_active |
gauge | Forced locations. | |
eaxplc_writes_total |
counter | result |
One-shot write requests (POST /api/write, over HTTP or NATS). |
eaxplc_deploys_total |
counter | result (ok, compile_error) |
Program deploys. |
eaxplc_rollbacks_total |
counter | result (ok, failed) |
Program rollbacks. |
Each result of eaxplc_writes_total counts one request, whatever the number of entries in it:
result |
Meaning |
|---|---|
ok |
Queued for the next scan. |
rejected |
Invalid request (400). |
denied |
The caller lacks the plc.write right (403). |
refused_forced |
A target is forced (409). |
failed |
Could not be queued. |
Requests refused before authentication (401) are not counted.
| Metric | Type | Meaning |
|---|---|---|
eaxplc_nats_configured |
gauge | 1 when the runtime serves its API on a broker (--nats). |
eaxplc_nats_connected |
gauge | 1 while the broker connection is up. |
eaxplc_nats_reconnects_total |
counter | Broker reconnections. |
Fieldbus
Section titled “Fieldbus”There is one series per configured device. The labels are bus (bus id), type (modbus_tcp, ethernet_ip, ethercat) and device (device id). The series exist only when a fieldbus is configured.
| Metric | Type | Meaning |
|---|---|---|
eaxplc_fieldbus_device_up |
gauge | 1 while the device exchanges I/O. |
eaxplc_fieldbus_cycles_total |
counter | Good I/O cycles. |
eaxplc_fieldbus_bad_cycles_total |
counter | Failed I/O cycles that had not yet faulted the device (see below). |
eaxplc_fieldbus_faults_total |
counter | Transitions of the device to fault. |
eaxplc_fieldbus_last_cycle_seconds |
gauge | Duration of the device’s last measured I/O cycle. |
What counts as a bad cycle depends on the bus type:
- EtherCAT: no frame came back, or the working counter was wrong.
- Modbus TCP: an exception or error answer.
- EtherNet/IP: input data more than half the watchdog late.
Modbus TCP server
Section titled “Modbus TCP server”These series exist only while the server runs (not with --no-modbus).
| Metric | Type | Labels | Meaning |
|---|---|---|---|
eaxplc_modbus_server_up |
gauge | 1 while the server listens. | |
eaxplc_modbus_server_requests_total |
counter | kind (read: FC 1–4, write: FC 5, 6, 15, 16, other) |
Requests served. |
eaxplc_modbus_server_snapshot_reads_total |
counter | Of the reads, those answered from the last cycle’s copy, without waiting for a scan. | |
eaxplc_modbus_server_exceptions_total |
counter | Requests answered with an exception. | |
eaxplc_modbus_server_connections |
gauge | Open connections. | |
eaxplc_modbus_server_connections_total |
counter | Connections accepted. |
Go runtime
Section titled “Go runtime”These use the usual Prometheus Go names, without plc_id.
| Metric | Type | Meaning |
|---|---|---|
go_info |
gauge | Go version (version label). |
go_goroutines |
gauge | Goroutines. |
go_memstats_heap_alloc_bytes |
gauge | Heap bytes in live and unswept objects. |
go_memstats_sys_bytes |
gauge | Memory mapped by the Go runtime. |
go_gc_cycles_total |
counter | Completed garbage collections. |
go_sched_gomaxprocs_threads |
gauge | GOMAXPROCS. |
eaxplc_gc_pause_seconds |
histogram | Stop-the-world GC pauses. The scan stops during them too. |
eaxplc_gc_pause_seconds has buckets from 10 µs to 100 ms. It is folded from the runtime’s own histogram, so its _sum is estimated from bucket midpoints.
JSON snapshot on the NATS API
Section titled “JSON snapshot on the NATS API”The snapshot is the request GET /api/metrics/snapshot on the PLC API subject:
| Subject | plc.<plc-id>.api (request/reply) |
| Envelope | shared/plcapi: {"m":"GET","p":"/api/metrics/snapshot","h":{"Authorization":["Bearer <PLC token>"]}} |
| Reply | {"s":200,"h":{...},"b":"<base64 JSON body>"} |
| Over HTTP | GET /api/metrics/snapshot with the same credential |
From Go, plcapi.Do(requester, plcID, plcapi.Request{Method: "GET", Path: "/api/metrics/snapshot", Header: ...}, timeout) returns the decoded response.
The body is about 1.5 KB with two fieldbus devices.
A caller may send X-Request-ID (1 to 64 characters of A-Z a-z 0-9 . _ : -). The runtime then logs the request under that id and echoes it in the reply header. Without one, the runtime makes an id: r- over HTTP, n- over NATS.
Schema eaxplc.metrics.v1
Section titled “Schema eaxplc.metrics.v1”Every field is always present. Adding a field keeps the schema name. A field renamed, removed or changing meaning gives a new name (eaxplc.metrics.v2). Readers must ignore fields they do not know.
| Field | Type | Meaning |
|---|---|---|
schema |
string | eaxplc.metrics.v1 |
plc_id |
string | --plc-id |
version |
string | Runtime build version. |
ts_ms |
integer | Unix time of the snapshot, ms. |
uptime_s |
number | Seconds since start. |
scan.state |
string | running, stopped or faulted. |
scan.target_hz |
integer | Target scan frequency. |
scan.program_version |
integer | Running program’s version number. |
scan.cycles_total |
integer | Cycles since start. |
scan.overruns_total |
integer | Overrun cycles since start. |
scan.watchdog_trips_total |
integer | Overrun watchdog trips. |
scan.window_s |
number | Length of the quantile window, normally 10 s (shorter just after start). |
scan.window_cycles |
integer | Cycles in the window. |
scan.jitter_p50_us, scan.jitter_p95_us, scan.jitter_p99_us |
number or null | Jitter quantiles over the window. Null when no cycle ran in it. |
scan.exec_p50_us, scan.exec_p99_us |
number or null | Execution time quantiles over the window. |
scan.jitter_max_us, scan.exec_max_us |
number | Maxima since start. |
dvr.enabled, dvr.recording |
boolean | Recorder state. |
dvr.epoch, dvr.last_cycle |
integer | Newest recorded cycle: epoch and cycle number. Together they name a cycle in the DVR timeline. |
dvr.recorded_total, dvr.lost_total |
integer | Cycles recorded and lost. |
dvr.memory_bytes, dvr.memory_limit_bytes |
integer | Recording memory and its cap. |
dvr.retained_s |
number | History held. |
dvr.disk_blocks_dropped_total |
integer | Blocks not written to disk. |
forces_active |
integer | Forced locations. |
writes.ok, .rejected, .denied, .refused_forced, .failed |
integer | One-shot write requests by result. |
deploys.ok, .failed, .rollback_ok, .rollback_failed |
integer | Deploys and rollbacks by result. |
nats.configured, nats.connected |
boolean | Broker connection. |
nats.reconnects_total |
integer | Broker reconnections. |
fieldbus[] |
array | One entry per bus, its devices summed. Empty when no fieldbus is configured. |
fieldbus[].bus, .type |
string | Bus id and type. |
fieldbus[].devices, .healthy |
integer | Devices, and those exchanging I/O. |
fieldbus[].cycles_total, .bad_cycles_total, .faults_total |
integer | Good and bad I/O cycles, transitions to fault. |
fieldbus[].last_cycle_max_us |
number | Longest last-measured I/O cycle among the devices. |
modbus_server |
object or null | Null when the Modbus TCP server is off. |
modbus_server.read_requests_total, .write_requests_total, .other_requests_total, .exceptions_total |
integer | Requests by class, and exceptions. |
modbus_server.snapshot_read_requests_total |
integer | Of read_requests_total, the reads answered from the last cycle’s copy, without waiting for a scan. |
modbus_server.connections |
integer | Open connections. |
go.goroutines, go.heap_bytes, go.total_bytes, go.gc_cycles_total |
integer | Go runtime. |
go.gc_pause_max_us |
number | Upper bound of the largest GC pause bucket reached since start. |
telemetry.queue_dropped_total |
integer | Cycles not queued to the recorder. |
telemetry.ws_open, telemetry.ws_refused_per_session_total, telemetry.ws_refused_per_ip_total |
integer | Telemetry WebSockets open, and refused by each socket cap since start. |
Example (plc-server, two fieldbus devices not reachable):
{ "schema": "eaxplc.metrics.v1", "plc_id": "obs-test", "version": "0.0.0-dev", "ts_ms": 1790922524585, "uptime_s": 60.35, "scan": {"state": "running", "target_hz": 1000, "program_version": 1, "cycles_total": 60158, "overruns_total": 27, "watchdog_trips_total": 0, "window_s": 10.95, "window_cycles": 10949, "jitter_p50_us": 0.52, "jitter_p95_us": 0.98, "jitter_p99_us": 4.96, "exec_p50_us": 3.05, "exec_p99_us": 8.98, "jitter_max_us": 1557.3, "exec_max_us": 421.7}, "dvr": {"enabled": true, "recording": true, "epoch": 0, "last_cycle": 60158, "recorded_total": 60158, "lost_total": 0, "memory_bytes": 1120240, "memory_limit_bytes": 268435456, "retained_s": 60.16, "disk_blocks_dropped_total": 0}, "forces_active": 0, "writes": {"ok": 0, "rejected": 0, "denied": 0, "refused_forced": 0, "failed": 0}, "deploys": {"ok": 0, "failed": 0, "rollback_ok": 0, "rollback_failed": 0}, "nats": {"configured": false, "connected": false, "reconnects_total": 0}, "fieldbus": [ {"bus": "mb-plant", "type": "modbus_tcp", "devices": 1, "healthy": 0, "cycles_total": 0, "bad_cycles_total": 0, "faults_total": 11, "last_cycle_max_us": 0}, {"bus": "eip-drives", "type": "ethernet_ip", "devices": 1, "healthy": 0, "cycles_total": 0, "bad_cycles_total": 0, "faults_total": 0, "last_cycle_max_us": 0} ], "modbus_server": {"read_requests_total": 0, "snapshot_read_requests_total": 0, "write_requests_total": 0, "other_requests_total": 0, "exceptions_total": 0, "connections": 0}, "go": {"goroutines": 52, "heap_bytes": 3738648, "total_bytes": 14585856, "gc_cycles_total": 3, "gc_pause_max_us": 0.064}, "telemetry": {"queue_dropped_total": 0, "ws_open": 1, "ws_refused_per_session_total": 0, "ws_refused_per_ip_total": 0}}Structured logs
Section titled “Structured logs”The runtime logs through one structured logger, Go’s log/slog:
- Console (stderr): text by default, or JSON lines with
--log-format json(for a container log collector). - Log file: always JSON lines.
plc-serverwriteslogs/eaxPLC.logandplc-runtimewriteslogs/eaxPLC-rt.log. The file rotates at 20 MB and five files are kept. - Level:
--log-level debug|info|warn|error(defaultinfo).
Every line carries time, level, msg, plc_id and component. The components are main, runtime, http, deploy, executor, codestore, gitstore, nats, fieldbus, watchdog, auth, dvr, modbus, opcua, uns, telemetry, eaxtags, attach and metrics.
These correlation fields are added where they apply:
| Field | Where |
|---|---|
request_id |
Lines logged for an API request, over HTTP or NATS: deploys, rollbacks, fieldbus changes, authentication errors. The same id is in the X-Request-ID response header. |
deploy_id |
Deploy and rollback lines. It is also returned in the deploy or rollback response (deploy_id). |
cycle, dvr_epoch |
Program swaps, scan faults and watchdog trips. They name the cycle in the DVR timeline. |
audit_seq |
Lines saying that an audit record was written. The log refers to the audit record by its sequence number and never copies its content. |
The logger never writes secrets:
- Attributes whose name means a secret are replaced by
[REDACTED]: token, password, secret, signature, seed, NKey, authorization, cookie, API key. - Free text is scrubbed before it is written: messages, errors, URLs and JSON bodies. The scrubber removes PLC tokens (
v1.…), JWTs, NKey seeds,Bearercredentials,user:password@in URLs and secret query parameters.