Skip to content

Connect a MicroLogix, SLC 500 or PLC-5 on a serial port (DF1)

eaxScadaHow-to guideStarterProEnterpriseView as Markdown

Read and write the data table of an older Rockwell / Allen-Bradley MicroLogix, SLC 500 or PLC-5 controller through its serial port (channel 0, RS-232), when it has no Ethernet port or you prefer the serial link. eaxScada speaks DF1 full-duplex on that port and sends the same PCCC commands as over EtherNet/IP, so the addresses, data types and write checks are those of Connect to a MicroLogix, SLC 500 or PLC-5.

Supported controllers, on channel 0 set to DF1 full-duplex:

  • MicroLogix 1000, 1100, 1200, 1400 and 1500;
  • SLC 5/03, 5/04 and 5/05;
  • PLC-5.

The PC reaches the port through a COM port (RS-232) or through a serial device server in raw TCP mode (entered as tcp://host:port).

The Drivers workspace with a DF1 serial line selected: the Line tab with identifier, name and Connects to, the communication timing (request timeout, retry count), and the port settings: serial port, controller family, baud rate, data / parity / stop, error check, eaxScada node address, default controller node and ACK timeout. The Drivers workspace with a DF1 serial line selected: the Line tab with identifier, name and Connects to, the communication timing (request timeout, retry count), and the port settings: serial port, controller family, baud rate, data / parity / stop, error check, eaxScada node address, default controller node and ACK timeout.

A DF1 line in the Drivers workspace: the line's timing and its port settings.

Before you start: set up the controller’s port

Section titled “Before you start: set up the controller’s port”

In the controller’s programming software, on the serial port (channel 0) configuration:

  1. Driver: DF1 Full Duplex.
  2. Baud rate, parity and error check (CRC or BCC): note them, eaxScada must use the same. The controllers’ default is 19200 baud, no parity, CRC.
  3. Node address (the controller’s own DF1 address, 0-254; 1 unless changed): note it, it becomes the station’s node address in eaxScada.
  4. Duplicate packet detection: keep it on (the default). The controller then discards a message it receives twice: an extra protection, on the controller’s side, against a write being applied twice.

Then:

  • Connect the PC (or the serial device server) to the port with a null-modem cable, or the controller’s own programming cable.
  • Only one program can use a serial port at a time: close the programming software’s serial driver on that port before eaxScada opens it.
  1. In the Studio, Drivers → Add line or gateway (the + button), and in Connects to choose Rockwell / Allen-Bradley MicroLogix, SLC 500, PLC-5 on a serial port (DF1).
  2. Fill in the port settings:
Field Default What to enter
Serial Port empty COM5 on Windows, /dev/ttyUSB0 on Linux, or tcp://192.168.1.200:4001 for a serial device server in raw TCP mode.
Controller family MicroLogix 1000 / 1100 / 1200 / 1400 / 1500 MicroLogix, SLC 5/03, 5/04, 5/05, or PLC-5. It decides the commands sent and the address rules.
Baud Rate 19200 1200 to 38400, as on the controller’s port.
Data / Parity / Stop 8-N-1 8-N-1, 8-E-1 or 8-O-1, as on the controller’s port. DF1 always uses 8 data bits.
Error check CRC CRC or BCC, as on the controller’s port.
eaxScada node address 0 eaxScada’s own DF1 address (0-254), different from the controller’s.
Default controller node 1 Used only by a station without its own node address.
ACK timeout (ms) 1000 How long a message waits for the controller’s ACK or NAK before an ENQ asks again (20-10000 ms).
  1. Create line. A line with no serial port, a family that is not MicroLogix, SLC 500 or PLC-5, another data-bit count than 8, a node address outside 0-254 or an ACK timeout outside 20-10000 ms is refused before the port is opened.
  2. In the line’s Communication Timing section:
    • Request Timeout is the wait for the controller’s reply after it has acknowledged the message (2000 ms when unset).
    • Retry Count is how many times a message answered NAK is sent again, and how many ENQs ask for a lost ACK (0-10).

The DF1 port settings with the notes below them (full-duplex only, request timeout and retry count, the write rule, the address format), and the Link diagnostics card: medium, messages sent and received, BCC / CRC errors, ACK and reply timeouts. The DF1 port settings with the notes below them (full-duplex only, request timeout and retry count, the write rule, the address format), and the Link diagnostics card: medium, messages sent and received, BCC / CRC errors, ACK and reply timeouts.

The port settings, the notes on timing and writes, and the line's link diagnostics.

Drivers → Add station, choose the DF1 line, and enter the controller’s Node address (0-254), the one set on its port. On a DF1 line the stations grid shows a Node address column instead of Unit id. Test connection reads the status-file word S:0 at that node: a success names the family and the node that answered.

Tag Mappings → + Map New Tag, with the data-table address and the data type exactly as for an Ethernet controller: N7:0, F8:3, B3:0/5 or B3/37, T4:2.ACC, T4:2.PRE, T4:2.DN, C5:0.ACC, S:1, I:1.0/3 (PLC-5: I:012/07, octal), L9:0 (MicroLogix). Int16 (or UInt16) for a word, Float32 for an F element, Int32 for an L element, Bool for a bit. The rules are in Addresses; the server checks them against the line’s controller family when the mapping is saved, and the driver again before any request.

Each tag is read with its own request: there is no batching on a serial line yet. Count about 25 ms per tag at 19200 baud when you choose the poll rate.

A write goes through the same path as every other write: the server’s write policy and e-signature, the mapping’s read only flag and write range, then the same driver checks as over EtherNet/IP (status, input and output files, timer and counter status bits, and values the type cannot hold are refused before anything is sent). Then:

  • One message per write. The write is one PCCC command with one transaction number, to exactly the mapped address.
  • Re-sent only after a NAK. If the controller answers NAK (it discarded the frame), the very same message, with the same transaction number, is sent again, up to the retry count. If the controller’s ACK is lost, an ENQ asks for it again; the message itself is not re-sent unless the answer is a NAK.
  • Never re-sent after the controller’s ACK. Once the controller has acknowledged the message, it is not sent again, whatever happens next.
  • Confirmed only by the reply. The write succeeds only on the controller’s reply to that transaction number with a good status. A reply with an error status (for example processor is in program mode) is a refusal, reported with its words.
  • NOT CONFIRMED, never repeated. A write whose reply does not come (no ACK, a NAK to every copy up to the retry count, no reply, an unusable reply) is reported NOT CONFIRMED: the controller may or may not have applied it. eaxScada never sends it again on its own; check the value and write again yourself if needed.
SequenceHow one write is sent and confirmed over DF1
How one write is sent and confirmed over DF1After the server's write checks and the driver's checks, eaxScada sends one PCCC command with one transaction number. The controller answers the frame with ACK or NAK. Only a NAK makes eaxScada send the very same message again; a lost ACK is asked for with ENQ. After the ACK the message is never sent again. The write succeeds only on the controller's reply to that transaction number with a good status; an error status is a refusal, and every other ending is NOT CONFIRMED and is not repeated.A CHECK FAILSNAK: FRAME DISCARDEDNO ACK IN TIMEGOOD STATUSERROR STATUSNO REPLY IN TIMEANYTHING ELSEeaxScadaDF1 lineControllerchannel 0, DF1Checks the write firstwrite policy, signature, read only, rangeaddress, file and value typeRefused, nothing is sent1One PCCC commandone transaction numberCMDNAKThe very same message againup to the retry countCMDACKACK timeoutENQ: asks for the answerthe message is not sent again2ACKfrom here on, never sent again3Reply to that transactionstatus goodWrite confirmedReply with an error statusreported with its wordsReplyrequest timeoutNOT CONFIRMED, not repeatedno ACK after the last ENQNAK past the retry countno reply after the ACK, or unusable
A write is sent again only when the controller said NAK, and never after its ACK: anything that is not a reply ends as NOT CONFIRMED, so check the value before you write again.
  • Product
  • Device or controller
  • Data or telemetry
  • Command to equipment
  • Refusal
Read as text

After the server's write checks and the driver's checks, eaxScada sends one PCCC command with one transaction number. The controller answers the frame with ACK or NAK. Only a NAK makes eaxScada send the very same message again; a lost ACK is asked for with ENQ. After the ACK the message is never sent again. The write succeeds only on the controller's reply to that transaction number with a good status; an error status is a refusal, and every other ending is NOT CONFIRMED and is not repeated.

Participants

  • eaxScada (product): DF1 line
  • Controller (device or controller): channel 0, DF1

Steps, in order

  1. eaxScada: Checks the write first: write policy, signature, read only, range; address, file and value type
  2. A check fails:
    1. eaxScada: Refused, nothing is sent
  3. eaxScada → Controller (command to equipment): One PCCC command. one transaction number
  4. NAK: frame discarded:
    1. Controller → eaxScada (refusal): NAK
    2. eaxScada → Controller (command to equipment): The very same message again. up to the retry count
  5. No ACK in time:
    1. Controller → eaxScada (reply, lost: it does not arrive): ACK. ACK timeout
    2. eaxScada → Controller (data or telemetry): ENQ: asks for the answer. the message is not sent again
  6. Controller → eaxScada (reply): ACK. from here on, never sent again
  7. Good status:
    1. Controller → eaxScada (reply): Reply to that transaction. status good
    2. eaxScada: Write confirmed
  8. Error status:
    1. Controller → eaxScada (refusal): Reply with an error status. reported with its words
  9. No reply in time:
    1. Controller → eaxScada (reply, lost: it does not arrive): Reply. request timeout
  10. Anything else:
    1. eaxScada: NOT CONFIRMED, not repeated: no ACK after the last ENQ; NAK past the retry count; no reply after the ACK, or unusable

The line’s Link diagnostics card (under its settings) and the driver diagnostics show:

Counter Means
Medium port and framing, DF1 full-duplex, error check, family and eaxScada’s node address
Messages sent / received DF1 messages sent (re-sends included) and received with a correct check
BCC / CRC errors (answered NAK) received frames with a wrong check or broken framing
ACK and reply timeouts waits for ACK/NAK that ended with nothing, and acknowledged messages whose reply did not come
Error statuses answered replies with a PCCC error status
Unexpected or unusable replies replies that could not be read, or that answered no request in flight
Re-sent after NAK messages sent again because the controller answered NAK

Rising check errors or NAK re-sends while tags stay GOOD point to the line: cable, baud rate or parity, or noise.

  • DF1 half-duplex (a polled multi-drop line, one master polling several slaves): a line set to half-duplex is refused. Set the controller’s port to DF1 full-duplex.
  • DH-485 and DH+ links, and a controller reached through another one.
  • Browsing: the controller holds no tag names. Map each address.
  • Reading several addresses in one request: each tag is one request.
  • String (ST), ASCII (A), BCD (D), control (R), message, PID and block-transfer files; indirect and indexed addresses.

Any line can run in simulated mode ("simulated": true in its settings): no port is opened and values are generated, so you can build screens and mappings before the controller is connected.