Command-line flags
Command-line flags of the eaxPLC binaries, read from their flag definitions. A flag can be written with one or two dashes (-flag or --flag); -h prints the same list.
eaxsim
Section titled “eaxsim”Source: eaxPLC/cmd/eaxsim
| Flag | Type | Default | Description |
|---|---|---|---|
-http |
string | HTTP API address (default: the scenario’s, 127.0.0.1:8090; “-”: none) | |
-local-users-breakglass |
bool | false |
with --scada-url: let local users sign in and sign while eaxScada is unreachable (audited BREAK_GLASS; default off) |
-mode |
string | override the scenario’s mode: realtime or virtual | |
-nats |
string | NATS broker (default: the scenario’s; “-”: none) | |
-nats-nkey |
string | NKey seed file the UNS prefix guard connects to the broker with (a broker that requires NKeys, as eaxScada’s; the identity must subscribe plc..birth, plc..status and uns.telemetry.>; empty: the broker URL’s credentials); when the guard cannot connect with it, every PLC’s UNS telemetry and commands are refused | |
-report |
string | check the scenario’s expect entries (virtual time) and write the eaxsim.checks/1 report to this file when the run ends; exit 1 unless the verdict is pass | |
-restore |
string | continue from a snapshot file (taken from the same scenario) | |
-save |
string | write a snapshot of the plant to this file when the run ends | |
-scada-url |
string | http://127.0.0.1:8080 |
eaxScada base URL: sign-in, e-signatures and its PLC token key (ignored with --standalone; EAX_DEV_MODE=1 disables auth for development) |
-scenario |
string | scenario file (JSON) | |
-speed |
float | -1 |
virtual mode: speed factor (0: as fast as possible) |
-standalone |
bool | false |
standalone PLC: local users (plc-server user …) are the authority and no eaxScada is contacted |
-stats-file |
string | write the final scheduler counters (scans, time) as JSON when the run ends (metering) | |
-token-key |
string | data/security/plc_token_ed25519.key |
this PLC’s own token signing key (plc-server token keygen); tokens it signs are trusted (standalone use) |
-token-pin |
string | data/security/scada_plc_token.pub |
where eaxScada’s token key is pinned after the first fetch (delete it to accept a new eaxScada key) |
-token-pubkey |
string | eaxScada’s PLC token public key (file or base64); default: fetched once from --scada-url and pinned in --token-pin |
|
-until |
float | 0 |
virtual mode: stop at this simulated time (s; absolute, also after -restore) |
-users-file |
string | data/security/users.json |
local user store: the authority with --standalone; managed with plc-server user … |
eaxsim-cloud
Section titled “eaxsim-cloud”Source: eaxPLC/cmd/eaxsim-cloud
| Flag | Type | Default | Description |
|---|---|---|---|
-config |
string | cloud.json |
configuration file (the former eaxcloud’s loads unchanged) |
eaxsimctl
Section titled “eaxsimctl”Source: eaxPLC/cmd/eaxsimctl
eaxsimctl create
Section titled “eaxsimctl create”Upload a scenario and every file under DIR (its programs, units; paths relative to DIR, default: the scenario’s directory).
Usage:
eaxsimctl create -name NAME [-dir DIR] [-id-only] SCENARIO.jsonSource: eaxPLC/cmd/eaxsimctl/main.go
| Flag | Type | Default | Description |
|---|---|---|---|
-dir |
string | directory of the files the scenario uses (default: the scenario’s) | |
-id-only |
bool | false |
print the new simulation’s id only |
-name |
string | simulation name |
eaxsimctl list
Section titled “eaxsimctl list”Usage:
eaxsimctl listSource: eaxPLC/cmd/eaxsimctl/main.go
No flags.
eaxsimctl report
Section titled “eaxsimctl report”The checks report of the last run (a virtual run of a scenario with expect entries; schema eaxsim.checks/1); exit 0: every check passed, 1: one failed, or no report.
Usage:
eaxsimctl report [-o FILE] SIMSource: eaxPLC/cmd/eaxsimctl/main.go
| Flag | Type | Default | Description |
|---|---|---|---|
-o |
string | also write the report to this file |
eaxsimctl start
Section titled “eaxsimctl start”Usage:
eaxsimctl start [-mode realtime|virtual] [-speed X] [-until S] SIMSource: eaxPLC/cmd/eaxsimctl/main.go
| Flag | Type | Default | Description |
|---|---|---|---|
-mode |
string | realtime or virtual (default: the scenario’s) | |
-speed |
float | 0 |
virtual: speed factor (0: the scenario’s) |
-until |
float | 0 |
virtual: stop at this simulated time, s |
eaxsimctl status, stop, delete
Section titled “eaxsimctl status, stop, delete”Usage:
eaxsimctl status SIMeaxsimctl stop SIMeaxsimctl delete SIMSource: eaxPLC/cmd/eaxsimctl/main.go
No flags.
eaxsimctl test
Section titled “eaxsimctl test”Run the scenario here (no key, no platform, no broker, no API), in virtual time to until_s, and check its “expect” entries; prints the JSON report (schema eaxsim.checks/1); exit 0: every check passed, 1: one failed, 2: error (no run).
Usage:
eaxsimctl test [-until S] [-speed X] [-workers N] [-report FILE] [-timeout D] SCENARIO.jsonSource: eaxPLC/cmd/eaxsimctl/test.go
| Flag | Type | Default | Description |
|---|---|---|---|
-report |
string | also write the JSON report to this file | |
-speed |
float | -1 |
speed factor (0: as fast as possible; default: the scenario’s) |
-timeout |
duration | 0 |
give up after this wall time (exit 2; 0: none) |
-until |
float | 0 |
stop at this simulated time, s (default: the scenario’s until_s) |
-workers |
int | 0 |
scheduler workers (default: the scenario’s, else the CPUs) |
eaxsimctl usage
Section titled “eaxsimctl usage”Usage:
eaxsimctl usage [-month 2026-10]Source: eaxPLC/cmd/eaxsimctl/main.go
| Flag | Type | Default | Description |
|---|---|---|---|
-month |
string | month, 2026-10 (default: this one) |
eaxsimctl wait
Section titled “eaxsimctl wait”Until the run ends; exit 0: ended (stopped), 1: failed, or its checks did not pass, 3: timeout.
Usage:
eaxsimctl wait [-timeout 10m] [-interval 1s] SIMSource: eaxPLC/cmd/eaxsimctl/main.go
| Flag | Type | Default | Description |
|---|---|---|---|
-interval |
duration | time.Second |
poll interval |
-timeout |
duration | 10*time.Minute |
give up after |
ecatsim
Section titled “ecatsim”Source: eaxPLC/cmd/ecatsim
| Flag | Type | Default | Description |
|---|---|---|---|
-i |
string | network interface of the bus (e.g. ecs0) | |
-slaves |
string | di8,do8,aio |
slaves in line: di8, do8, aio |
plc-bench
Section titled “plc-bench”Source: eaxPLC/cmd/plc-bench
| Flag | Type | Default | Description |
|---|---|---|---|
-cpu |
string | all |
CPU tier for PackML benchmark (eaxCPU-700, eaxCPU-900, all) |
-cycles |
int | 10000 |
Number of scan cycles for real-time jitter benchmark |
-freq |
int | 1000 |
Scan loop frequency in Hz (e.g., 1000 for 1ms cycle) |
-packml |
bool | false |
Run dedicated ISA-TR88 PackML industrial benchmark only |
plc-runtime
Section titled “plc-runtime”Source: eaxPLC/cmd/plc-runtime
| Flag | Type | Default | Description |
|---|---|---|---|
-audit-disk |
bool | false |
Persist the cycle recording to disk (closed blocks of cycles; default false for lean edge) |
-audit-recover |
bool | false |
Start over an audit trail (data/plc_audit.jsonl) damaged before its end: copy it to plc_audit.jsonl.corrupt-<time> and start a new chain whose first record names the copy and its sha256. Without it the PLC refuses to start on such a file (a torn last record is recovered without it) |
-cpu |
string | PLC CPU tier: eaxCPU-100 (64KB), eaxCPU-300 (512KB), eaxCPU-500 (4MB), eaxCPU-700 (32MB), eaxCPU-900 (64MB) | |
-dvr-disk-mb |
int | 10 |
Size cap of the on-disk cycle recording in MB (with --audit-disk) |
-dvr-max-mb |
int | 256 |
Memory cap of the cycle recording in MB (the oldest history goes first when the program changes too much to keep --dvr-seconds) |
-dvr-seconds |
int | 600 |
Cycle recorder (DVR) history kept in memory, in seconds |
-eaxtags-scripts |
bool | false |
Run the eaxTags scripts eaxScada pins to this PLC (in this process: their allocations can add GC pauses to the scan) |
-enterprise |
bool | true |
Start the per-cycle flight recorder (DVR) - included in eaxPLC Performance; ignored without that licence |
-executor |
string | auto |
program executor: auto (amd64 machine code; elsewhere a Go plugin where supported, else the VM), jit, native (Go plugin), vm |
-freq |
int | 1000 |
PLC scan frequency in Hz (default: the CPU tier’s rate - eaxCPU-100 100 Hz, eaxCPU-300 500 Hz, others 1000 Hz) |
-gc-memory-limit-mb |
int | 0 |
Go memory limit in MB (0: auto - the live heap measured after start-up and after each program load + the cycle recorder’s --dvr-max-mb + 7 copies of the CPU tier’s process image + 64 MB of garbage, over the 97 % of the limit the Go heap may reach, never below the start-up value, within 3/4 of a container’s memory limit; GOMEMLIMIT, when set, is kept) |
-gc-percent |
string | off |
Go GC target percentage, or off: with off the GC runs only at --gc-memory-limit-mb (the scan allocates nothing; each collection stops the scan goroutine briefly, and Go otherwise forces one every 2 minutes) |
-http |
int | 8085 |
HTTP port for Micro Control API and WebSocket telemetry (0 to disable) |
-http-bind |
string | 127.0.0.1 |
address the HTTP API listens on (0.0.0.0 exposes it to the network; every call still needs an eaxScada session) |
-local-users-breakglass |
bool | false |
with --scada-url: let local users sign in and sign while eaxScada is unreachable (audited BREAK_GLASS; default off) |
-log-format |
string | text |
console log format: text (for people) or json (one JSON object per line, for collectors); the log file is always JSON |
-log-level |
string | info |
log level: debug, info, warn or error |
-mem |
int | 0 |
Custom memory size in MB (e.g. 32, 64) |
-metrics-anonymous-localhost |
bool | false |
serve GET /metrics without a session to scrapers on this machine (loopback only; requests through a proxy, with X-Forwarded-For, still need one). Off: /metrics needs the same session or PLC token as /api/stats |
-modbus |
int | 5020 |
Modbus TCP port (0 to disable) |
-modbus-bind |
string | 127.0.0.1 |
address the Modbus TCP server listens on (Modbus has no authentication: 0.0.0.0 lets anyone on the network read and write the process image) |
-modbus-max-reads |
int | 3000 |
Modbus TCP server: most read requests (FC 1-4) answered per second, all connections together; reads over it wait, none is refused, writes are never limited. It keeps busy clients from taking CPU from the scan. 0: no limit |
-native-module-dir |
string | eaxPLC source tree the binary was built from (the native executor builds Go plugins against it) | |
-nats |
string | Optional external NATS server URL (e.g. nats://localhost:4222) | |
-nats-legacy-telemetry |
bool | false |
Also publish every cycle’s changes as JSON on plc.<id>.telemetry.delta (and .rungs.powerflow) and the whole image once a second on plc.<id>.telemetry.snapshot. Nothing in eaxScada or the Studio reads these (they use telemetry sessions); off, the PLC builds none of it |
-nats-nkey |
string | NKey seed file identifying this PLC to the SCADA broker (eaxScada creates data/security/nkeys/<plc-id>.nk for --edge-plcs) |
|
-nats-pass |
string | Optional NATS password | |
-nats-queue |
string | plc-workers |
NATS system command queue group name |
-nats-token |
string | Optional NATS authentication bearer token | |
-nats-user |
string | Optional NATS username | |
-no-http |
bool | false |
Disable HTTP server entirely (air-gapped fieldbus & IPC only) |
-no-modbus |
bool | false |
Disable Modbus TCP server |
-opcua-anonymous |
bool | false |
allow anonymous read-only OPC UA sessions |
-opcua-bind |
string | 127.0.0.1 |
OPC UA listen address (0.0.0.0 to expose it on the network) |
-opcua-cert-dir |
string | data/opcua |
directory of the OPC UA server certificate (created on first start) |
-opcua-port |
int | 0 |
embedded OPC UA server port, e.g. 4840 (0: off) |
-plc-id |
string | plc-01 |
Unique PLC runtime identifier for NATS subjects (e.g. plc-01) |
-project |
string | data/program.st |
Path to ST program or project file to execute |
-rt-class |
string | Windows process priority class: normal, high or realtime (realtime needs administrator rights; default: high with --rt-priority, else normal) |
|
-rt-cpu |
int | -1 |
pin the scan thread to this CPU (Linux: pair with isolcpus=<cpu>) |
-rt-mlock |
bool | false |
no page faults in the scan: Linux mlockall (needs CAP_IPC_LOCK); Windows VirtualLock of the process image and the JIT code |
-rt-mmcss |
string | Windows: register the scan thread with MMCSS under this task, e.g. “Pro Audio” | |
-rt-priority |
int | 0 |
scan thread priority: Linux SCHED_FIFO 1-99 (needs CAP_SYS_NICE); Windows >0 = TIME_CRITICAL |
-rt-spin-us |
int | 0 |
busy-wait this many microseconds before each deadline (default: 1200 on Windows, 150 on Linux) |
-rt-yield-us |
int | 0 |
yield the scan goroutine to the Go scheduler in the cycle’s slack at least this often (default 2000, and 8000 for a Linux scan pinned with --rt-cpu and SCHED_FIFO; -1 = never). Keeps Go’s forced preemption out of the deadline |
-scada-url |
string | http://127.0.0.1:8080 |
eaxScada base URL: sign-in, e-signatures and its PLC token key (ignored with --standalone; EAX_DEV_MODE=1 disables auth for development) |
-standalone |
bool | false |
standalone PLC: local users (plc-server user …) are the authority and no eaxScada is contacted |
-token-key |
string | data/security/plc_token_ed25519.key |
this PLC’s own token signing key (plc-server token keygen); tokens it signs are trusted (standalone use) |
-token-pin |
string | data/security/scada_plc_token.pub |
where eaxScada’s token key is pinned after the first fetch (delete it to accept a new eaxScada key) |
-token-pubkey |
string | eaxScada’s PLC token public key (file or base64); default: fetched once from --scada-url and pinned in --token-pin |
|
-uns-prefix |
string | UNS path prefix for the PLC’s variables, e.g. Plant/Line2/plc-01 (empty: UNS publishing off; needs --nats) |
|
-uns-writable |
string | comma-separated glob patterns of variables that UNS commands and OPC UA clients may write, e.g. “Setpoint*,Recipe[*]” (empty: read-only) | |
-use-saved-cpu |
bool | false |
Load hardware configuration from data/cpu_config.json |
-users-file |
string | data/security/users.json |
local user store: the authority with --standalone; managed with plc-server user … |
-version |
bool | false |
print the version and exit |
-ws-max-per-ip |
int | 32 |
concurrent telemetry WebSockets per client address; past it a socket is closed with 1008 (0: default 32, negative: no cap) |
-ws-max-per-session |
int | 8 |
concurrent telemetry WebSockets (/api/telemetry) per session; past it a socket is closed with 1008 (0: default 8, negative: no cap) |
plc-runtime token keygen, pubkey, mint
Section titled “plc-runtime token keygen, pubkey, mint”Usage:
plc-runtime token keygen|pubkey|mint [flags]Source: eaxPLC/internal/tokencmd/tokencmd.go
| Flag | Type | Default | Description |
|---|---|---|---|
-key |
string | data/security/plc_token_ed25519.key |
signing key file (base64 Ed25519 seed) |
-level |
int | 0 |
mint: role level (default: the level of -role: Administrator 100, Lead_Engineer 80, Process_Supervisor 60, Shift_Operator 40, Compliance_Auditor 20) |
-role |
string | mint: role, e.g. Lead_Engineer | |
-ttl |
duration | 8*time.Hour |
mint: validity |
-user |
string | mint: user name (sub) |
plc-runtime user add, passwd, role, lock, unlock, del, list
Section titled “plc-runtime user add, passwd, role, lock, unlock, del, list”Local accounts of a PLC started with --standalone.
Usage:
plc-runtime user add|passwd|role|lock|unlock|del|list [-file F] [-user U] [-role R] [-password-stdin]Source: eaxPLC/internal/usercmd/usercmd.go
| Flag | Type | Default | Description |
|---|---|---|---|
-file |
string | data/security/users.json |
local user store |
-password-stdin |
bool | false |
read the password from stdin (one line) instead of prompting |
-role |
string | role: Administrator, Lead_Engineer, Process_Supervisor, Shift_Operator, Compliance_Auditor | |
-user |
string | user name |
plc-server
Section titled “plc-server”Source: eaxPLC/cmd/plc-server
| Flag | Type | Default | Description |
|---|---|---|---|
-attach |
string | Studio only: drive the eaxPLC runtime with this PLC id over NATS (--nats, and --nats-nkey / --nats-user / --nats-token for the broker); no PLC runs in this process |
|
-audit-disk |
bool | false |
Persist the cycle recording to disk (closed blocks of cycles) |
-audit-recover |
bool | false |
Start over an audit trail (data/plc_audit.jsonl) damaged before its end: copy it to plc_audit.jsonl.corrupt-<time> and start a new chain whose first record names the copy and its sha256. Without it the PLC refuses to start on such a file (a torn last record is recovered without it) |
-cpu |
string | PLC CPU tier: eaxCPU-100 (64KB), eaxCPU-300 (512KB), eaxCPU-500 (4MB), eaxCPU-700 (32MB), eaxCPU-900 (64MB) | |
-dvr-disk-mb |
int | 10 |
Size cap of the on-disk cycle recording in MB (with --audit-disk) |
-dvr-max-mb |
int | 256 |
Memory cap of the cycle recording in MB (the oldest history goes first when the program changes too much to keep --dvr-seconds) |
-dvr-seconds |
int | 600 |
Cycle recorder (DVR) history kept in memory, in seconds |
-eaxtags-scripts |
bool | false |
Run the eaxTags scripts eaxScada pins to this PLC (in this process: their allocations can add GC pauses to the scan) |
-enterprise |
bool | true |
Start the per-cycle flight recorder (DVR) - included in eaxPLC Performance; ignored without that licence |
-executor |
string | auto |
program executor: auto (amd64 machine code; elsewhere a Go plugin where supported, else the VM), jit, native (Go plugin), vm |
-freq |
int | 1000 |
PLC scan frequency in Hz (default: the CPU tier’s rate - eaxCPU-100 100 Hz, eaxCPU-300 500 Hz, others 1000 Hz) |
-gc-memory-limit-mb |
int | 0 |
Go memory limit in MB (0: auto - the live heap measured after start-up and after each program load + the cycle recorder’s --dvr-max-mb + 7 copies of the CPU tier’s process image + 64 MB of garbage, over the 97 % of the limit the Go heap may reach, never below the start-up value, within 3/4 of a container’s memory limit; GOMEMLIMIT, when set, is kept) |
-gc-percent |
string | off |
Go GC target percentage, or off: with off the GC runs only at --gc-memory-limit-mb (the scan allocates nothing; each collection stops the scan goroutine briefly, and Go otherwise forces one every 2 minutes) |
-headless |
bool | false |
Run in headless mode without embedded Web Studio assets |
-http |
int | 8085 |
HTTP port for Web IDE and WebSocket telemetry |
-http-bind |
string | 127.0.0.1 |
address the HTTP API listens on (0.0.0.0 exposes it to the network; every call still needs an eaxScada session) |
-local-users-breakglass |
bool | false |
with --scada-url: let local users sign in and sign while eaxScada is unreachable (audited BREAK_GLASS; default off) |
-log-format |
string | text |
console log format: text (for people) or json (one JSON object per line, for collectors); the log file is always JSON |
-log-level |
string | info |
log level: debug, info, warn or error |
-mem |
int | 0 |
Custom memory size in MB (e.g. 32, 64) |
-metrics-anonymous-localhost |
bool | false |
serve GET /metrics without a session to scrapers on this machine (loopback only; requests through a proxy, with X-Forwarded-For, still need one). Off: /metrics needs the same session or PLC token as /api/stats |
-modbus |
int | 5020 |
Modbus TCP port |
-modbus-bind |
string | 127.0.0.1 |
address the Modbus TCP server listens on (Modbus has no authentication: 0.0.0.0 lets anyone on the network read and write the process image) |
-modbus-max-reads |
int | 3000 |
Modbus TCP server: most read requests (FC 1-4) answered per second, all connections together; reads over it wait, none is refused, writes are never limited. It keeps busy clients from taking CPU from the scan. 0: no limit |
-native-module-dir |
string | eaxPLC source tree the binary was built from (the native executor builds Go plugins against it) | |
-nats |
string | Optional external NATS server URL (e.g. nats://localhost:4222) | |
-nats-legacy-telemetry |
bool | false |
Also publish every cycle’s changes as JSON on plc.<id>.telemetry.delta (and .rungs.powerflow) and the whole image once a second on plc.<id>.telemetry.snapshot. Nothing in eaxScada or the Studio reads these (they use telemetry sessions); off, the PLC builds none of it |
-nats-nkey |
string | NKey seed file identifying this PLC to the SCADA broker (the SCADA creates data/security/nkeys/<plc-id>.nk) | |
-nats-pass |
string | Optional NATS password | |
-nats-queue |
string | plc-workers |
NATS system command queue group name |
-nats-token |
string | Optional NATS authentication bearer token | |
-nats-user |
string | Optional NATS username | |
-opcua-anonymous |
bool | false |
allow anonymous read-only OPC UA sessions |
-opcua-bind |
string | 127.0.0.1 |
OPC UA listen address (0.0.0.0 to expose it on the network) |
-opcua-cert-dir |
string | data/opcua |
directory of the OPC UA server certificate (created on first start) |
-opcua-port |
int | 0 |
embedded OPC UA server port, e.g. 4840 (0: off) |
-plc-id |
string | plc-01 |
Unique PLC runtime identifier for NATS subjects (e.g. plc-01) |
-rt-class |
string | Windows process priority class: normal, high or realtime (realtime needs administrator rights; default: high with --rt-priority, else normal) |
|
-rt-cpu |
int | -1 |
pin the scan thread to this CPU (Linux: pair with isolcpus=<cpu>) |
-rt-mlock |
bool | false |
no page faults in the scan: Linux mlockall (needs CAP_IPC_LOCK); Windows VirtualLock of the process image and the JIT code |
-rt-mmcss |
string | Windows: register the scan thread with MMCSS under this task, e.g. “Pro Audio” | |
-rt-priority |
int | 0 |
scan thread priority: Linux SCHED_FIFO 1-99 (needs CAP_SYS_NICE); Windows >0 = TIME_CRITICAL |
-rt-spin-us |
int | 0 |
busy-wait this many microseconds before each deadline (default: 1200 on Windows, 150 on Linux) |
-rt-yield-us |
int | 0 |
yield the scan goroutine to the Go scheduler in the cycle’s slack at least this often (default 2000, and 8000 for a Linux scan pinned with --rt-cpu and SCHED_FIFO; -1 = never). Keeps Go’s forced preemption out of the deadline |
-scada-url |
string | http://127.0.0.1:8080 |
eaxScada base URL: sign-in, e-signatures and its PLC token key (ignored with --standalone; EAX_DEV_MODE=1 disables auth for development) |
-standalone |
bool | false |
standalone PLC: local users (plc-server user …) are the authority and no eaxScada is contacted |
-token-key |
string | data/security/plc_token_ed25519.key |
this PLC’s own token signing key (plc-server token keygen); tokens it signs are trusted (standalone use) |
-token-pin |
string | data/security/scada_plc_token.pub |
where eaxScada’s token key is pinned after the first fetch (delete it to accept a new eaxScada key) |
-token-pubkey |
string | eaxScada’s PLC token public key (file or base64); default: fetched once from --scada-url and pinned in --token-pin |
|
-uns-prefix |
string | UNS path prefix for the PLC’s variables, e.g. Plant/Line2/plc-01 (empty: UNS publishing off; needs --nats) |
|
-uns-writable |
string | comma-separated glob patterns of variables that UNS commands and OPC UA clients may write, e.g. “Setpoint*,Recipe[*]” (empty: read-only) | |
-users-file |
string | data/security/users.json |
local user store: the authority with --standalone; managed with plc-server user … |
-version |
bool | false |
print the version and exit |
-workdir |
string | Directory holding data/ and logs/ (default: current directory; as a Windows service: the executable’s directory) | |
-ws-max-per-ip |
int | 32 |
concurrent telemetry WebSockets per client address; past it a socket is closed with 1008 (0: default 32, negative: no cap) |
-ws-max-per-session |
int | 8 |
concurrent telemetry WebSockets (/api/telemetry) per session; past it a socket is closed with 1008 (0: default 8, negative: no cap) |
plc-server token keygen, pubkey, mint
Section titled “plc-server token keygen, pubkey, mint”Usage:
plc-server token keygen|pubkey|mint [flags]Source: eaxPLC/internal/tokencmd/tokencmd.go
| Flag | Type | Default | Description |
|---|---|---|---|
-key |
string | data/security/plc_token_ed25519.key |
signing key file (base64 Ed25519 seed) |
-level |
int | 0 |
mint: role level (default: the level of -role: Administrator 100, Lead_Engineer 80, Process_Supervisor 60, Shift_Operator 40, Compliance_Auditor 20) |
-role |
string | mint: role, e.g. Lead_Engineer | |
-ttl |
duration | 8*time.Hour |
mint: validity |
-user |
string | mint: user name (sub) |
plc-server user add, passwd, role, lock, unlock, del, list
Section titled “plc-server user add, passwd, role, lock, unlock, del, list”Local accounts of a PLC started with --standalone.
Usage:
plc-server user add|passwd|role|lock|unlock|del|list [-file F] [-user U] [-role R] [-password-stdin]Source: eaxPLC/internal/usercmd/usercmd.go
| Flag | Type | Default | Description |
|---|---|---|---|
-file |
string | data/security/users.json |
local user store |
-password-stdin |
bool | false |
read the password from stdin (one line) instead of prompting |
-role |
string | role: Administrator, Lead_Engineer, Process_Supervisor, Shift_Operator, Compliance_Auditor | |
-user |
string | user name |