# Screen parameters

> The {Name} syntax of screen parameters, the declaration (types, required, defaults, allowed values and folders), parameter sets, how screens, popups, docks and embedded screens are opened with them, the checks, and how the server enforces write targets with parameters.

Product: eaxScada · Type: Reference · Editions: Starter, Pro, Enterprise
Source: https://eaxware.com/docs/eaxscada/reference/screen-parameters/
Status: migrated page, not yet verified against the current code.

A screen's parameters let one screen stand for many plant stations. How to use them: [Reusable screens with parameters](/docs/eaxscada/how-to/reusable-screens-with-parameters/).

## Syntax

| Written | Is | Replaced by |
|---|---|---|
| `{Pump}` | a parameter | its value, else its declared default; with neither it stays as written |
| `{Pump\|Plant/Processing/Pumps/P100}` | a parameter with a default in place | its value, else `Plant/Processing/Pumps/P100` |
| `{Plant/Processing/Mode}` | a tag reference (expressions) | never replaced |
| `{UDT.Speed}`, `{ return 1 }` | not a screen parameter | never replaced |

- A parameter name is a letter, then letters, digits or `_`, at most 32 characters. It has no `/`: anything with a `/` (that is not a parameter with a default) is a tag reference.
- The default after `|` may hold `/`. It may not start with `|`, so `{a||b}` in an expression is not a parameter.
- There is no logic: no conditions, loops or filters. A value is inserted as text, once; a value is never read as another parameter.

`{Name}` works in every text of a screen: tag paths of bindings and actions, expressions and conditions, interlocks, confirmation tags, input objects' tag, minimum and maximum tags, alarm-object filters, trend pens, texts and the popup title. Scripts (a startup script, **Run script**) are not substituted: they read `system.params.get('Name')` and `system.params.all()`, which are read-only.

The server and the browser use one tokenizer, tested on the same corpus (`web/testdata/screen_params_corpus.json`).

## Declaration

**Display Settings** > **Parameters**, stored in the screen as `screen_params.declared`:

| Field | |
|---|---|
| `name` | The parameter name. |
| `description` | For the engineer. |
| `type` | `tagFolder` (letters, digits, `_ . -` and `/`), `text`, or `number`. |
| `required` | The screen does not open without a value (a default counts). |
| `default` | The value when none is given. |
| `allowed_values` | The only values accepted. |
| `allowed_pattern` | The folders accepted: a tag path where `*` stands for part of one folder name (`Plant/Processing/Pumps/*`, `Plant/Processing/Pumps/P1*`), and a whole `**` segment for one or more folders (`Plant/Processing/**`). |

A declaration with a bad name, a duplicate, an unknown type, a bad pattern, or a default or allowed value with a wildcard is refused on save (400).

## Parameter sets

`screen_params.sets`: named value sets (`{"name": "P-101", "values": {"Pump": "Plant/Processing/Pumps/P101", "Label": "Feed pump P-101"}}`), edited in a grid with CSV import and export. CSV: a `set` column, an optional `description`, one column per declared parameter (comma, semicolon or tab separated).

## Opening a screen with parameters

The values a screen opens with are: the declared defaults, then the set, then the values given beside it.

| From | How |
|---|---|
| A **Navigate** or **Open popup** action | **Parameter set of the target screen** (`param_set`) and / or **Parameters** (`params`, `Name=value` lines). A value may pass the current screen's own `{Name}` down. |
| The runtime address | `/runtime/<screen>?set=P-101`, `/runtime?screen=<screen>&set=P-101`, `?Pump=Plant/Processing/Pumps/P101` |
| A script | `system.nav.navigate(target, params, {set})`, `system.nav.openPopup(screen, {set, params})`, `system.nav.loadInnerDisplay(screen, container, {set, params})`, `system.nav.swapInner(container, screen, {set, params})` |
| A dock, an embedded (inner) screen | It gets the page's values for the parameters it declares (all of them when it declares none), plus its own. |

### Checks

A value:

- has at most 256 characters, no wildcard (`* # + >`), no brace, no control character, no `.` or `..` folder;
- from the address or a script: only letters, digits, spaces and `_ . - / : ,` (nothing that could become code in an expression or markup in a text).

On a screen that declares parameters:

- an undeclared name, a missing required value, a value of the wrong type, and a value outside the allowed values or folders are refused;
- an unknown set is refused.

A refused screen does not open. The runtime shows the reason and buttons for the screen's sets. A popup does not open and the action reports why.

## Server enforcement

The write policy (confirmation, e-signature, limits, interlocks) of a screen that declares parameters is derived:

| The parameter has | The server enforces |
|---|---|
| a set | each set's expanded targets exactly, with that set's interlock, confirmation and limit tags (sources marked `param_set: "set P-101"`) |
| allowed values (every parameter of the screen) | every combination of allowed values exactly (at most 256), and nothing else |
| allowed folders, or nothing | besides the sets, the target as a pattern: `{Name}` matches the allowed folders (`Plant/Processing/Pumps/[A-Za-z0-9_.-]*`), or any text without them (lint `param-target-unbounded`) |

- For a tag a set writes, the same object's pattern is left out: the set's own interlock and confirmation tags decide, not the pattern's unresolved `{Pump}/Fault`.
- For a value in the allowed folders but in no set, the pattern applies: the button's confirmation or signature is required. An interlock that uses `{Name}` is evaluated per value: the server reads the parameters from the tag path being written and fills them in (a write to `Plant/Processing/Pumps/P107/Start` checks `Plant/Processing/Pumps/P107/Fault`). A filled-in interlock tag that does not exist reads as a Bad value and refuses the write. A limit tag that uses `{Name}` refuses every write (fail closed). Define every station as a set.
- A set its own declaration refuses is not derived (the runtime never opens it); it is listed as unresolved in the write-policy listing.
- An interlock with a `{...}` that the command's tag path cannot fill in (a parameter the tag path does not have, or a brace that is not a parameter) fails closed: the server refuses every write of the command, unless **If the interlock reads a Bad value** is **Allow**, where it never blocks. An expression interlock is filled in only when every value is a plain tag path; otherwise it is enforced on the screen only, and it never lets a value past another object's interlock on the same tag. A button that writes an exact tag (`Line/Start`) with a `{Pump}` interlock is decided by the derived sets, each with its own filled-in interlock; the interlock of the screen as designed does not open them. The Studio badge is judged with the tags the object writes. The lint names each case (`interlock-parameter`, `interlock-per-parameter`). See [Interlocks with a parameter](/docs/eaxscada/how-to/enforce-interlocks/#interlocks-with-a-parameter).
- `POST /api/tags/write` takes the screen a write is sent from: `screen`, `param_set` and `params` (all optional). The operator runtime sends them for every write from a screen or popup opened with parameter values. When `screen` is given, the write is refused with `403` `{"status": "parameters_refused", "code": "WRITE_DENIED_SCREEN_PARAMETERS", "reason": ...}`, journaled, when that screen does not exist or does not admit those values. A write without `screen` is checked as before. NATS commands and assistant setpoints carry no screen.

## Designer

- **Preview with**: none, a set, or custom values. Bindings and conditions use them; the resolved-tags grid lists each `{Name}` reference, its resolved tag and live value; **Open in the runtime** opens the screen with them.
- An object whose binding uses a `{Name}` without a value shows a violet `{Name}` chip. A button whose target keeps an unresolved `{Name}` sends nothing.
- Lint: `param-undeclared`, `param-unused`, `param-set-missing-required`, `param-set-value-not-allowed`, `param-target-unbounded` (see the [lint rules](/docs/eaxscada/how-to/check-screens-before-deploy/)).
- **Find where used** on a tag lists the screens that reach it through a set. **Find and replace** (Look in: Tag path, a whole path) lists them too, as "through set P-101" rows that are never applied: change the value in the set.

## Behaviour changes in this version

- New: screen parameter declarations and sets, the runtime address `?set=`, and the per-set write-policy derivation.
- A parameter name is now `[A-Za-z][A-Za-z0-9_]{0,31}`: a popup's parameter named with a `.` or starting with `_` is refused.
- Navigation actions' parameters are applied to the target page (before, they were stored and ignored).
- `{Name}` inside a script is no longer replaced in popups.
- A write target with `{Name}` on a screen that declares allowed folders is enforced as a pattern no wider than those folders; before, `{TagRoot}/Start` gated every `.../Start` tag of the plant.