An isometric screen shows the plant as a map seen from above at an angle. In this tutorial you draw one line of it: tank T-101 filled by pump P-101 and drained through valve XV-101. At the end the map runs in the operator runtime, the tank shows its level, and the pump starts and stops after a confirmation, on a desktop and on a phone.

The finished map in the operator runtime: pump P-101, tank T-101 labelled 84 % and valve XV-101 on a dark tile ground, with the turn and zoom buttons. The finished map in the operator runtime: pump P-101, tank T-101 labelled 84 % and valve XV-101 on a dark tile ground, with the turn and zoom buttons.

What you will build: an isometric map with live values, in the runtime.
  • eaxScada is installed and you can open the Studio as an engineer (Lead_Engineer or Administrator). Isometric screens are in every edition.
  • The four tags and the fill script of Build your first 2D screen, step 1 exist. If you skipped that tutorial, create them now (Drivers → Local tags (eaxTags) → + Tag, then + Script): Line1/Tank1/Level, Line1/Tank1/HighSetpoint (writable), Line1/Pump1/Running (writable) and Line1/Valve1/Open (writable).
  • About 15 minutes.

An isometric screen is a screen like the others: it is edited in the same Screens designer, saved, checked and deployed the same way, and its commands go through the same confirmation and server checks. Choose an editor: 2D, 3D or isometric compares the three editors.

  1. Open Screens, then in the Displays panel click New and Isometric Display.
  2. Enter Display name Line 1 plant map and Display id line1_map.
  3. Set Map width (tiles) to 12 and Map depth (tiles) to 10.
  4. Keep Palette on High performance (greys, colour for abnormal states): equipment stays grey and only an abnormal state takes a colour, which is what operator screens need.
  5. Click Create.

The New isometric display dialog: name Line 1 plant map, id line1_map, map 12 by 10 tiles, High performance palette. The New isometric display dialog: name Line 1 plant map, id line1_map, map 12 by 10 tiles, High performance palette.

The map's size can be changed later, with nothing selected.

The empty map opens, and the left Palette tab now lists blocks: connectors first, then vessels, rotating equipment, valves and more.

  1. Type vertical tank in Search blocks, click Vertical tank, then click a tile near the middle of the map. The ghost is green where the block fits and rose where it would overlap another one.
  2. Place Centrifugal pump with motor three tiles to the left of the tank, on the same row.
  3. Place Actuated valve (on/off) two tiles to the right of the tank.

Each block gets an id of its kind: T-101, P-101 and XV-101. R turns the selected block, the arrow keys move it one tile, and Ctrl+Z undoes a step. The zoom buttons of the map’s toolbar (or the mouse wheel) zoom in.

The map in the designer with pump P-101, tank T-101 and valve XV-101 on one row, joined by short pipes. The map in the designer with pump P-101, tank T-101 and valve XV-101 on one row, joined by short pipes.

Three blocks and two pipes.
  1. In the palette’s Connectors, click Pipe (or press C).
  2. Drag over the tiles between the pump and the tank. The pipe follows the tiles, and an end that reaches a block’s port connects to it.
  3. Drag again between the tank and the valve.
  4. Press Escape to leave the tool.

The Pipe connector armed in the palette, with the pipes drawn between the pump, the tank and the valve. The Pipe connector armed in the palette, with the pipes drawn between the pump, the tank and the valve.

Select a pipe to see its open ends and give it a service (water, steam, air...).

Select the tank (click it, or press Tab until it is selected) and open its Bind tab:

  1. Under Level, set Level tag to Line1/Tank1/Level, Empty at 0 and Full at 100. The … button next to a tag field browses the tags.
  2. Under Label value, set Value tag to Line1/Tank1/Level and Format to %.0f %. The label on the map then reads “T-101 84 %”.
  3. Under Alarms, type Line1/Tank1/* in Alarm sources: any alarm on a tag of that folder rings the tank and shows its badge.

The Bind tab of T-101: the State card empty, the Level card with Line1/Tank1/Level, empty at 0 and full at 100. The Bind tab of T-101: the State card empty, the Level card with Line1/Tank1/Level, empty at 0 and full at 100.

A Bad value is drawn grey and dashed with a red marker, never in its last good colour.

Then select the pump and, in its Bind tab, set State tag to Line1/Pump1/Running. The rows below already map 0 to Stopped and 1 to Running. Do the same on the valve with Line1/Valve1/Open: for a valve the rows read Closed and Open.

Commands on blocks are set exactly like on a 2D object:

  1. Select the pump and open its Action tab.
  2. Action Type: Toggle tag value; Target Tag Path: Line1/Pump1/Running.
  3. Require Confirmation, with the question Start or stop pump P-101?
  4. Click Apply Action Configuration.

The Action tab of pump P-101: Toggle tag value on Line1/Pump1/Running with Require Confirmation and the question “Start or stop pump P-101?”. The Action tab of pump P-101: Toggle tag value on Line1/Pump1/Running with Require Confirmation and the question “Start or stop pump P-101?”.

A block without a fully configured command cannot be clicked in the runtime.

Give the valve the same command on Line1/Valve1/Open with the question Open or close valve XV-101?, then save (Ctrl+S).

In the designer, a tap on a block only selects it; it never sends the command. Preview in the inspector shows a state or a level on the map without sending anything.

  1. Click Deploy, type your password and click Sign and deploy (as in the 2D tutorial).
  2. Open http://<server>:8080/runtime/line1_map. The map fits the window; drag to pan and use the wheel to zoom. The turn buttons (or Q and E) turn the view by a quarter.
  3. Click the pump, answer Execute Action: the pump shows Running and the tank label climbs.

Operators can also reach the map without a mouse: the map is one Tab stop, the arrow keys go from block to block and Enter runs the selected block’s command, with the same confirmation.

Open the same address on a phone. The map opens as Cards: one card per block that shows a value or has a command, with a button that says what it does. The Screen tab shows the map itself, with pinch and zoom; a pan or a pinch never sends a command.

The map on a phone: the Cards tab with P-101 Stopped and its “Start or stop pump P-101” button, T-101 with its level, XV-101 Closed; and the Screen tab with the map and only the T-101 label. The map on a phone: the Cards tab with P-101 Stopped and its “Start or stop pump P-101” button, T-101 with its level, XV-101 Closed; and the Screen tab with the map and only the T-101 label.

Cards and the map on a 390 px phone. On a narrow map, plain labels stay on their block or hide; alarm badges and quality markers are always shown.

A plant map with live state, level and alarm bindings and two confirmed commands, deployed and usable with a mouse, the keyboard and a phone.

To go further: