Build your first isometric plant map
An isometric screen shows the plant as a map seen from above at an angle. In this tutorial you draw one line of it: tank T-101 filled by pump P-101 and drained through valve XV-101. At the end the map runs in the operator runtime, the tank shows its level, and the pump starts and stops after a confirmation, on a desktop and on a phone.

Before you start
Section titled “Before you start”- eaxScada is installed and you can open the Studio as an engineer (Lead_Engineer or Administrator). Isometric screens are in every edition.
- The four tags and the fill script of Build your first 2D screen, step 1 exist. If you skipped that tutorial, create them now (Drivers → Local tags (eaxTags) → + Tag, then + Script):
Line1/Tank1/Level,Line1/Tank1/HighSetpoint(writable),Line1/Pump1/Running(writable) andLine1/Valve1/Open(writable). - About 15 minutes.
An isometric screen is a screen like the others: it is edited in the same Screens designer, saved, checked and deployed the same way, and its commands go through the same confirmation and server checks. Choose an editor: 2D, 3D or isometric compares the three editors.
1. Create the map
Section titled “1. Create the map”- Open Screens, then in the Displays panel click New and Isometric Display.
- Enter Display name
Line 1 plant mapand Display idline1_map. - Set Map width (tiles) to
12and Map depth (tiles) to10. - Keep Palette on High performance (greys, colour for abnormal states): equipment stays grey and only an abnormal state takes a colour, which is what operator screens need.
- Click Create.

The empty map opens, and the left Palette tab now lists blocks: connectors first, then vessels, rotating equipment, valves and more.
2. Place the equipment
Section titled “2. Place the equipment”- Type
vertical tankin Search blocks, click Vertical tank, then click a tile near the middle of the map. The ghost is green where the block fits and rose where it would overlap another one. - Place Centrifugal pump with motor three tiles to the left of the tank, on the same row.
- Place Actuated valve (on/off) two tiles to the right of the tank.
Each block gets an id of its kind: T-101, P-101 and XV-101. R turns the selected block, the arrow keys move it one tile, and Ctrl+Z undoes a step. The zoom buttons of the map’s toolbar (or the mouse wheel) zoom in.

3. Join them with pipes
Section titled “3. Join them with pipes”- In the palette’s Connectors, click Pipe (or press C).
- Drag over the tiles between the pump and the tank. The pipe follows the tiles, and an end that reaches a block’s port connects to it.
- Drag again between the tank and the valve.
- Press Escape to leave the tool.

4. Bind the blocks to the tags
Section titled “4. Bind the blocks to the tags”Select the tank (click it, or press Tab until it is selected) and open its Bind tab:
- Under Level, set Level tag to
Line1/Tank1/Level, Empty at0and Full at100. The … button next to a tag field browses the tags. - Under Label value, set Value tag to
Line1/Tank1/Leveland Format to%.0f %. The label on the map then reads “T-101 84 %”. - Under Alarms, type
Line1/Tank1/*in Alarm sources: any alarm on a tag of that folder rings the tank and shows its badge.

Then select the pump and, in its Bind tab, set State tag to Line1/Pump1/Running. The rows below already map 0 to Stopped and 1 to Running. Do the same on the valve with Line1/Valve1/Open: for a valve the rows read Closed and Open.
5. Give the pump a command
Section titled “5. Give the pump a command”Commands on blocks are set exactly like on a 2D object:
- Select the pump and open its Action tab.
- Action Type: Toggle tag value; Target Tag Path:
Line1/Pump1/Running. - Require Confirmation, with the question
Start or stop pump P-101? - Click Apply Action Configuration.

Give the valve the same command on Line1/Valve1/Open with the question Open or close valve XV-101?, then save (Ctrl+S).
In the designer, a tap on a block only selects it; it never sends the command. Preview in the inspector shows a state or a level on the map without sending anything.
6. Deploy and use it
Section titled “6. Deploy and use it”- Click Deploy, type your password and click Sign and deploy (as in the 2D tutorial).
- Open
http://<server>:8080/runtime/line1_map. The map fits the window; drag to pan and use the wheel to zoom. The turn buttons (or Q and E) turn the view by a quarter. - Click the pump, answer Execute Action: the pump shows Running and the tank label climbs.
Operators can also reach the map without a mouse: the map is one Tab stop, the arrow keys go from block to block and Enter runs the selected block’s command, with the same confirmation.
7. Open it on a phone
Section titled “7. Open it on a phone”Open the same address on a phone. The map opens as Cards: one card per block that shows a value or has a command, with a button that says what it does. The Screen tab shows the map itself, with pinch and zoom; a pan or a pinch never sends a command.

What you built
Section titled “What you built”A plant map with live state, level and alarm bindings and two confirmed commands, deployed and usable with a mouse, the keyboard and a phone.
To go further:
- Every block, connector, level and key: Build an isometric screen.
- Open a faceplate from a block: Popups, docks and navigation.
- The checks the map gets before deploy: Check screens before deploy.
- The same line as a 2D screen: Build your first 2D screen, or in 3D: Build your first 3D scene.