Save trend sets
Save the variables you always look at together (a tank’s level, its pump, its valve) as a trend set in the project, so you and your colleagues open them in one click, and the set follows the project’s history.
Before you start
Section titled “Before you start”- The PLC keeps a project. Without one, the view says This PLC keeps no project: trend sets cannot be saved here.
- Anyone signed in can open trend sets. Creating, saving and deleting them needs an engineer (Lead_Engineer or Administrator).
1. Open Trends and pick a set
Section titled “1. Open Trends and pick a set”Click Trends in the toolbar (or View → Trends). Pick a set in Trend set, or click New and give it a name: 1 to 64 letters, digits, spaces, _, . or -, starting with a letter or digit.
2. Add variables
Section titled “2. Add variables”A set holds up to 32 variables: a name, a member or index path (T1.ET, Recipes[2].Temp) or a direct address (%IW4). Add them from:
- Add variable in the Trends view (type the name or address, then Add);
- the Trend row action of the Tag database and of the cross-reference’s variables grid;
- Add to trend set in the editor’s context menu;
- Add to trend on the quick-watch card (Watch a value on hover).
Each variable is a chip under the toolbar; its × removes it.
3. Record and read
Section titled “3. Record and read”Click Start Recording (Pause Recording stops it; Clear drops the samples). The samples are the live values the Studio already receives from the PLC: recording asks nothing more of the PLC and never touches its scan.
The chart and the values share one container with three tabs:
- Chart: a time axis with zoom (mouse wheel and the slider below), a legend that hides or shows each variable, and a tooltip with the values.
- Values: one row per sample time, with a value and a quality column per variable, column filters and CSV.
- Split: both side by side, on screens at least 1400 px wide.
The last tab is remembered in your browser. Zooming the chart filters the values grid to the same time range (Show all clears it).
Quality. A sample the PLC could not read is Bad with no value: the chart shows a gap, never a 0, and the values grid says Bad. A BOOL is drawn as 1 or 0, a timer instance as its elapsed time.
Export. The chart’s toolbar saves a PNG image and a CSV of the plotted data; the values grid has its own CSV.

4. Save, delete
Section titled “4. Save, delete”- Save writes the set into the project (
trendsets.json, next to the POUs). If someone saved the same set since you opened it, the save is refused (409): reload and add your change again. Switching sets with unsaved changes asks before discarding them. - Delete removes the set from the project, after asking. The variables are not affected.
A project holds up to 64 trend sets. Saving, creating and deleting are recorded in the audit trail (TRENDSET_SAVED, TRENDSET_CREATED, TRENDSET_DELETED).
Versions and rollback
Section titled “Versions and rollback”The trend sets are part of the project tree that every deploy records, so each program revision carries the sets as they were saved at that deploy. A rollback puts the revision’s trend sets back with the project; a revision recorded before trend sets existed leaves none. The samples are never saved: only the list of variables is.