Skip to content

eaxsim scenario

PlatformReferenceCloudView as Markdown

An eaxsim scenario file (-scenario) and the model, link and I/O specifications of a simulated system.

Keys are the JSON keys. Optional marks keys that are omitted when empty, or that may be absent (pointers).

Scenario is a scenario file.

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
name string
mode string realtime (default) | virtual
speed number virtual: 0 = as fast as possible
until_s number yes virtual: stop after this simulated time
base_tick_ms number yes
workers integer yes
seed integer
nats NATS
http HTTP
telemetry Telemetry Telemetry: the PLCs’ UNS telemetry on the broker (pkg/sim/host); absent: on whenever NATS is, automatic pacing, read-only.
sites map of string to Site yes Sites locate the plant on the map (templates name their site).
library map of string to Unit yes Library: reusable units (a pump station, a reactor) that templates “use”; Include: files adding units ({“library”: {…}}), relative to the scenario.
include list of string yes
templates list of Template
expect list of Expect yes Expect: the run’s pass/fail checks (checks.go), read-only; evaluated by eaxsimctl test in virtual time.

ModelSpec is one model of an instance.

Source: eaxPLC/pkg/sim/system.go

Key Type Optional Description
name string
type string
params Params yes

LinkSpec copies a model output to a model input every step (“T1.level_m”).

Source: eaxPLC/pkg/sim/system.go

Key Type Optional Description
from string
to string

IOSpec wires a model port to the PLC’s process image: %I addresses are written from the port (sensors), %Q addresses are read into the port (actuators). Scale [raw_min, raw_max, eng_min, eng_max] converts engineering units to the raw value; Type picks the encoding of W/D/B addresses (INT, UINT, WORD, DINT, UDINT, DWORD, REAL, SINT, USINT, BYTE).

Source: eaxPLC/pkg/sim/system.go

Key Type Optional Description
plc string
port string
scale list of number yes
type string yes

NATS: the broker the PLCs serve their API on (empty URL: no NATS).

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
url string yes
mode string yes Mode: mux (default: all PLCs on one connection and 4 wildcard subscriptions) | per_plc (a controller and ~12 subscriptions each).
pool integer yes Pool: shared connections (PLC i uses i % pool); default 4.
nkey_dir string yes NKeyDir: <dir>/<plc id>.nk seeds give a PLC its own connection and identity (a secured eaxScada broker allows each identity plc.<id>.>).

HTTP is the host’s API.

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
addr string yes default 127.0.0.1:8090

Telemetry configures the hosted PLCs’ UNS telemetry (host.Telemetry):

"telemetry": {"interval\_ms": 200, "plcs": ["tank-00\*"], "prefix": "{site}/{area}/{id}",
"refresh\_s": 30, "writable": ["SetpointM", "Cmd\*"]}

eaxsim’s -uns-* flags override each field.

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
off boolean yes Off: no UNS telemetry or commands (alone: no other field with it).
interval_ms number yes IntervalMs: the sampling period in wall time; 0: 50 ms, longer in proportion beyond 250 publishing PLCs.
plcs list of string yes PLCs: the publishing PLCs by id (path.Match patterns); empty: all.
prefix string yes Prefix: the UNS prefix pattern ({site}, {area}, {unit}, {id}, “/” between levels); empty: site/area/unit/id.
refresh_s number yes RefreshS: every value republished this often; 0: 30 s, < 0: never.
writable list of string yes Writable: the variables UNS commands may write (path.Match patterns, case-insensitive, as a real runtime’s --uns-writable); empty: read-only, a real runtime’s default.

Site is a place of the plant.

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
name string yes
lat number
lon number
info string yes

Unit is a reusable template body: a PLC program with its process. A template that uses it adds or overrides parameters, initial values and faults, and may add models, links and I/O.

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
description string yes
program string
scan_ms number
params map of string to Param yes
init map of string to Value yes
models list of ModelTemplate yes
links list of LinkSpec yes
io list of IOSpec yes
faults list of FaultSpec yes
kpi KPI yes KPI is the signal that sums the unit up on overview maps (“T1.level_pct”), with its normal range.

Template is replicated Count times.

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
use string yes a library unit
kpi KPI yes
id string “tank-{i:04}”; {i} is 0-based
count integer
site string yes
area string yes
unit string yes
program string
scan_ms number
params map of string to Param yes
init map of string to Value yes “%MD100:REAL”: number | “${p}”
models list of ModelTemplate yes
links list of LinkSpec yes
io list of IOSpec yes
faults list of FaultSpec yes

Expect is a pass/fail check of a virtual-time run (virtual commissioning): a PLC variable or a plant signal compared with a value, at a time, throughout a window, never in a window, or eventually in it. Checks only read: no field writes a variable, forces a signal or injects a fault, and an unknown key (a “write”, “set”, “force”) is refused like everywhere else in a scenario.

"expect": [
{"id": "settled", "plc": "tank-00", "signal": "T1.level\_m", "check": "at", "at\_s": 90,
"cmp": "within", "value": 2.0, "tol": 0.05},
{"id": "no-spill", "plc": "tank-\*", "signal": "T1.level\_pct", "check": "never", "cmp": "&gt;", "value": 95},
{"id": "alarm", "plc": "tank-00", "var": "HighAlarm", "check": "eventually",
"after\_fault": "pump-on", "within\_s": 30, "cmp": "==", "value": true},
{"id": "pump-off", "plc": "tank-00", "var": "%QX0.0", "check": "always",
"from\_s": 200, "to\_s": 300, "cmp": "==", "value": false}]

Times are simulated seconds from the run’s start (0), or from the start of the fault after_fault names (its at_s on each PLC that has it). eaxsimctl test runs a scenario in virtual time and reports the checks; eaxsim itself does not evaluate them.

Source: eaxPLC/pkg/sim/scenario/checks.go

Key Type Optional Description
id string
description string yes
plc string yes PLC: the PLCs checked (path.Match on their ids); empty: every PLC. Each matching PLC must pass.
signal string yes Signal: a model port (“T1.level_m”); Var: a PLC variable by name (“LevelM”, “Line2.Valve1.Q”) or a direct address with its type (“%MD104:REAL”, “%QX0.1”; W: INT, D: DINT, B: BYTE without one). Exactly one of them.
var string yes
check string Check: at (the first sample at or after at_s), always (every sample in [from_s, to_s]), never (no sample in the window), eventually (a sample in [from_s, to_s] or [from_s, from_s + within_s]). A window without to_s runs to the run’s end.
cmp string Cmp: ==, !=, <, <=, >, >=, or within (|x - value| <= tol).
value Number yes
tol number yes
at_s number yes times, simulated seconds
from_s number yes
to_s number yes
within_s number yes
after_fault string yes AfterFault: the id of a scenario fault; the times count from its start on each PLC that has it.

Params are a model’s numeric parameters.

Source: eaxPLC/pkg/sim/model/model.go

Underlying type: map[string]float64.

Param is a per-instance parameter: a number, {“uniform”: [lo, hi]}, {“list”: [a, b, …]} (by instance, cycling) or {“step”: [start, inc]}.

Source: eaxPLC/pkg/sim/scenario/scenario.go

This type has its own JSON decoding: it accepts more than its fields below (see its description).

Key Type Optional Description
uniform list of number yes
list list of number yes
step list of number yes

Value is a number or a “${param}” reference.

Source: eaxPLC/pkg/sim/scenario/scenario.go

This type has its own JSON decoding: it accepts more than its fields below (see its description).

Key Type Optional Description
Num number yes
Ref string

ModelTemplate is a model whose parameters may use ${param}.

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
name string
type string
params map of string to Value yes

FaultSpec schedules a fault (sim.Fault) on the template’s instances: every one, or every Nth (i % every_n == 0).

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
id string
target string
kind string
value number yes
at_s number
duration_s number yes
held number yes runtime (snapshot): the value a stuck sensor holds
latched boolean yes
every_n integer yes

KPI names a model signal and its range (for colouring).

Source: eaxPLC/pkg/sim/scenario/scenario.go

Key Type Optional Description
signal string
min number
max number
unit string yes

Number is a check’s value: a number, or true (1) / false (0).

Source: eaxPLC/pkg/sim/scenario/checks.go

This type has its own JSON decoding: it accepts more than its fields below (see its description).