# Classic dial gauge

> The classic dial gauge screen object: the dial gauge of the equipment palette, kept for screens that use it.

Product: eaxScada · Type: Reference · Editions: Starter
Source: https://eaxware.com/docs/eaxscada/reference/generated/widgets/gauges/classic-dial-gauge/
Verified against commit 55b8e98.

<!-- GENERATED by tools/docgen (node tools/docgen/docgen.mjs). Do not edit by hand: change the source and regenerate. -->

The dial gauge of the **Industrial Equipment** palette group, kept for the screens that use it. For new screens use the [gauge](/docs/eaxscada/reference/generated/widgets/gauges/gauge/): it reads its tag with its quality and draws alarm bands.

How it is drawn depends on how it is driven. Driven by the Bind tab's *Gauge Reading* target (`value`, or `gauge_value`, the key older screens saved), or by nothing yet, it is drawn by the live gauge engine as a radial dial, with alarm bands and quality. With any other binding or with a condition, or with *Drawing* set to *Classic dial*, it keeps the classic drawing; there too the Gauge Reading moves the needle (-135° to 135° over the range) and the readout.
[Image: Classic dial gauge in the operator runtime]
|  |  |
|---|---|
| Palette | Not in the palette |
| JSON `type` | `Gauge` |
| Name in the inspector | Gauge |
| Size | a resize is stored as a scale (`scaleX`, `scaleY`); `width` and `height` keep the size it was drawn at |

## Properties

| Shown as | Key | Type | Unit | Default | Allowed values | What it does |
|---|---|---|---|---|---|---|
| Range minimum | `minVal` | Number |  | — |  | Value at the start of the scale. Empty = 0. *Inspector hint: Empty = 0* |
| Range maximum | `maxVal` | Number |  | — |  | Value at the end of the scale. Empty = 100. *Inspector hint: Empty = 100* |
| Decimals shown | `decimals` | Number |  | — | min 0, max 6, step 1 | Decimals of the value shown. |
| Needle colour | `needleColor` | Colour |  | — |  | Colour of the needle. Empty: the theme grey; in an alarm band (live engine) the needle takes the band's colour. *Inspector hint: Empty = theme grey. A value in an alarm band is shown in the band colour.* |
| Drawing | `renderer` | Choice |  | — | `""` Live chart gauge (default)<br>`classic` Classic dial | The live gauge engine (default, when the gauge is driven by its Gauge Reading or nothing) or the classic dial. *Inspector hint: The live gauge fills its box, follows the theme, shows alarm bands and bad quality. Gauges with bindings other than the gauge value keep the classic dial.* |
| Band display | `bandStyle` | Choice |  | — | `zones` Zones: coloured bands to the scale ends<br>`marks` Limit marks: grey scale, colour only beyond a limit<br>`track` Band track: thin coloured track outside the scale<br>`auto` Auto: limit marks when the bands cover over 40 % of the scale | Live engine only: how the alarm bands are drawn (zones, limit marks, a band track, or auto). *Inspector hint: ISA-101: with a tight alarm window, limit marks keep a normal screen grey. Sparklines always draw limit lines.* |
| Unit | `unit` | Text |  | — |  | Unit shown under the value. |
| Faceplate command / setpoint tag | `setpointTag` | Tag path (written) |  | — |  | The tag the operator faceplate (a click on the object in the runtime) writes. Empty = the faceplate is read-only. Never the measured value: write a setpoint or command tag. *Inspector hint: Leave empty for a read-only faceplate. Never the measured value.* |
| Command minimum | `spMin` | Number |  | — |  | Lowest value the faceplate may write. The server refuses lower values from every writer of that tag. |
| Command maximum | `spMax` | Number |  | — |  | Highest value the faceplate may write. The server refuses higher values from every writer of that tag. |
| W | `width` | Number | px | `80` |  | Width of the object's box. Objects sized by scale keep their drawing and use it only as the selection box. |
| H | `height` | Number | px | `80` |  | Height of the object's box. |
| — | `fill` | Colour |  | `"#0f172a"` |  | Colour of the dial face. |
| — | `stroke` | Colour |  | `"#38bdf8"` |  | Colour of the rim. |
| Stroke width | `strokeWidth` | Number | px | `2` |  | Outline thickness in pixels; 0 draws no outline. |
| — | `label` | Text |  | `"DIAL GAUGE"` |  | The caption drawn with the gauge. |
| On-screen keyboard | `keyboard` | Choice |  | — | `inherit`<br>`auto`<br>`numeric`<br>`full`<br>`numeric_full`<br>`none` | Shown once a command / setpoint tag is set: which on-screen keyboard the operator faceplate's entry opens on a touch panel. inherit: the screen's, then the project's setting. |
| X | `x` | Number | px | — |  | Horizontal position of the object's top-left corner on the screen, in screen pixels from the left edge. |
| Y | `y` | Number | px | — |  | Vertical position of the object's top-left corner, in screen pixels from the top edge. |
| Rotation | `rotation` | Number | ° | — |  | Rotation of the object, clockwise, in degrees. |
| Opacity | `opacity` | Number |  | — |  | 0 (invisible) to 1 (opaque). An object disabled by an interlock is drawn at 0.45 whatever this says. |
| Scale X | `scaleX` | Number |  | — |  | Horizontal scale factor (1 = drawn size). Set by resizing an object that is sized by scale. |
| Scale Y | `scaleY` | Number |  | — |  | Vertical scale factor (1 = drawn size). |
| States | `states` | Object |  | — |  | This object's own state styles (normal, hover, pressed, on, disabled, bad, locked, unconfigured), edited in the inspector's States section. Visual only. Empty: the project's state styles. |
| State family | `styleFamily` | Text |  | — |  | The state family whose project styles apply (button, input, toggle, selector, faceplateButton, default). Empty: the family of the object's type. |

## Bindings and conditions

The object reads this tag through its own properties, with their quality: `setpointTag`. A Bad or Uncertain value is marked on the object (see Quality below), never drawn as good.

The **Bind** tab ties a property to a tag or an expression: a *tag* binding takes the tag's value, an *expression* binding computes one (see the [expression language](/docs/eaxscada/reference/expression-language/)), optionally through a map, format or script transform. The targets the Bind tab offers for this object:

| Bind tab target | Key | What the bound value does |
|---|---|---|
| Gauge Reading (Numeric) | `value` | Shows the value as the object's readout (with the unit and decimals). A Bad value shows a dash. |
| Needle Rotation Angle (-135° to 135°) | `needle_angle` | Turns the needle of a classic dial to the value, in degrees (-135 to 135). |
| Dial Border Color | `stroke` | Sets the outline colour from the value. |
| Gauge Face Color | `fill` | Sets the fill colour from the value (a colour text such as #22c55e, or a colour mapped by a map transform). |
| Engineering Unit / Tag | `label` | Replaces the caption with the value (on a Text object a number gets the unit and decimals). |
| Opacity (0.0 - 1.0) | `opacity` | Sets the opacity from the value (0 to 1). |
| Visibility (Boolean) | `visible` | Shows the object when the value is true or non-zero, hides it otherwise. |
| Rotation (°) | `rotation` | Rotates the object by the value, in degrees. |
| Scale / Pulse | `scale` | Scales the object by the value (1 = drawn size). |
| Text / Label | `text` | Replaces the text drawn with the value, formatted by the binding's format. On a Text object a number is followed by the object's unit, as with the Value target (never a word). A Bad value shows a dash. |

The **Cond** tab adds rules evaluated on every value change: **Visibility** (show or hide, by condition or role), **Color & Fill** (colour bands, alarm blinking), **Position** and **Size & Fill** (motion and level mapped from a value), **Rotation** (angle or continuous spin; an empty input range is 0 to 100 and empty angles are -135° to 135°, while 0 is a value), **Security & Touch** (the interlock: a *disable condition*, the role required, what happens when the interlock reads a Bad value) and **Text & Value** (formatted text). A condition that reads a Bad value is never applied as if the value were good: visibility shows the object marked Bad, colours go neutral grey, motion stays where it is, text shows a dash.

## Actions

**Operator faceplate.** In the runtime, a click or tap on this object (without an action of its own) opens the operator faceplate: its name, the value of the tag it shows (the first tag it is bound to) and, only when a *Faceplate command / setpoint tag* is set, an entry that writes that tag within *Command minimum* and *Command maximum*. Without a command tag the faceplate is read-only: the measured value is never offered for writing. The write goes through the same confirmation, limits and interlock checks as every command.

**Commands.** This object sends commands to equipment. Before it writes:

- **Confirmation and e-signature.** Set *Confirmation* to ask the operator to confirm, or to sign with their password and a reason (electronic signature). The signer is always the signed-in user; the dialog never pre-fills a signer, a reason or a password. The server requires the same confirmation from every writer of the tag.
- **Limits.** Minimum, maximum and step (or the tag's write range) are enforced by the server for every writer; the screen's own check only saves a round trip. A limit read from a tag that is missing or not Good refuses every write.
- **Interlocks.** A *Disabled condition* (buttons) or the *disable condition* of the Security & Touch condition dims the object and blocks the press while it is true. When the interlock is a simple tag comparison (`{Plant/Processing/Pumps/P101/Interlock} == 1`), the server also refuses the write from every writer (`409 interlocked`); other interlocks are screen only, and the designer says which. If the interlock reads a Bad value the object is disabled, unless *If the interlock reads a Bad value* is set to *Allow* (for stop, trip and emergency commands, so a failed sensor never stops an operator stopping a machine). See [screen interlocks](/docs/eaxscada/explanation/operator-runtime/#54-screen-interlocks).
- **Unconfigured means disabled.** Without its tag the object is drawn as not configured and sends nothing.
- **Deliberate taps.** On touch, only a still, short tap operates it.

A real safety interlock belongs in the PLC: screen and server interlocks only stop writes that go through eaxScada.

Any object can carry a click or tap action (the **Action** tab, or **Full Dialog...**). A write action whose tag, value or target is missing is *not configured*: the inspector says so and the operator's press does nothing (unconfigured means disabled). Navigation actions write nothing and ask no confirmation. On touch screens only a deliberate tap runs an action: a swipe or a pinch that ends on the object never does. Action types:

| Action | Key (`action.type`) | What it does |
|---|---|---|
| Set tag to 1 | `set_1` | Writes 1 to the action's tag. |
| Set tag to 0 | `set_0` | Writes 0 to the action's tag. |
| Toggle tag value | `toggle` | Writes the opposite of the tag's LIVE value: 0 when it is not 0, 1 when it is 0. When the live value is unknown, not Good or not a number, nothing is written and the operator is told why; when it changes while the operator confirms or signs, nothing is written either. |
| Set tag to 1 on press and to 0 on release | `momentary_1_0` | Writes 1 while pressed and 0 on release (hold to run). On touch, the press counts only after the finger is held still; the release is always sent. A held press is also released when the browser window loses focus or the page is hidden, and in the designer when a drag or a resize of the object starts. |
| Set tag to 0 on press and to 1 on release | `momentary_0_1` | Writes 0 while pressed and 1 on release. Released in the same cases as the 1/0 momentary. |
| Write custom value | `write_val` | Writes the number in write_value. |
| Run script | `run_command` | Runs a client script with the scripting API (system.tag.write, system.nav.openPopup...). Ctrl+Space completes the API. |
| Navigate to page / screen | `navigate` | Opens another screen, optionally with parameters or a parameter set. |
| Open popup screen | `open_popup` | Opens a screen in a popup window: modal or not, centred, next to the object or at a fixed position, with parameters. |
| Close popup | `close_popup` | Closes the popup the object is in, or the popup with the given id. |
| Open dock | `open_dock` | Opens a screen docked to an edge of the runtime (top, bottom, left, right). |
| Close dock | `close_dock` | Closes the dock on that edge. |
| Open or close dock | `toggle_dock` | Opens or closes the dock on that edge. |
| Back | `nav_back` | Goes back to the previous screen. |
| Forward | `nav_forward` | Goes forward again after Back. |
| Home screen | `nav_home` | Opens the project's home screen. |
| Open downtime panel | `open_downtime` | Opens the operator runtime's Downtime panel (OEE and downtime, Pro and Enterprise), optionally on one machine (its machine id). Navigation only: nothing is written to a tag or a machine. A machine the operator may not read is not shown; where the panel is not available, a notice says so. Offered in the designer only when the licence includes OEE and downtime. |

## States, text and parameters

**States.** An object's look follows its state: normal, hover, pressed, on, disabled, bad (quality), locked (role) and unconfigured. The project's state styles (opened from an object's **States** section, or from the Project manager's Operator runtime section) give each family of objects its colours per state, and the inspector's **States** section overrides them for one object (stored in `props.states`). States are visual only: whether an object can be operated is decided by its interlock, the user's rights and the server.

This object belongs to the state family `default` (all other objects): disabled (an interlock dims it to 0.45 opacity), bad (a tag it reads is Bad) and locked (missing role) apply when the object has conditions or an action; the other states apply to objects that are operated.

**Screen parameters.** On a screen with parameters, `{Name}` in any text of the object (tag paths of bindings and actions, expressions, conditions, interlocks, the confirmation tag, texts) is replaced by the parameter's value when the screen opens, so one screen serves many pieces of equipment (`{Pump}/Running`). See [screen parameters](/docs/eaxscada/reference/screen-parameters/).

**Quality.** Drawn by the live gauge engine, the dial shows the quality of its value on its own face, as the [gauge](/docs/eaxscada/reference/generated/widgets/gauges/gauge/) does, not with the markers of other objects: a Bad, Uncertain or stale value is dimmed, hatched and labelled BAD QUALITY, UNCERTAIN or NO LINK - STALE, and before a first value it shows a dash and NO DATA. A tag the signed-in account may not read shows a dash, a padlock and NOT READABLE on a blue label (NO ACCESS on a narrow dial), with no number and no needle; a device Bad keeps BAD QUALITY. Driven by an expression, the dial shows the quality of the tags the expression reads: a Bad input gives a dash and BAD QUALITY, never the last good number, every Bad input refused gives NOT READABLE with the padlock, and an Uncertain or stale input keeps the value, dimmed, with its label. A value from a simulated PLC gets the SIM badge. With the classic drawing the dial is marked like every other object: a red x and a grey veil (or hatching, per the project's quality style) for Bad or no connection, a blue lock for a tag the signed-in account may not read, an amber ? for Uncertain, a dashed outline for stale. The lock shows only when every Bad tag of the object is not readable: a device fault keeps the red x. Each object shows one marker, for its worst state, and markers that would overlap merge into one, drawn on the largest object with the worst state of all. The marker's tooltip lists every tag, its quality and its age. See [show bad and stale values](/docs/eaxscada/how-to/show-bad-and-stale-values/).

**Comments.** In the studio, right-click the object and choose **Add comment** to start a design-review thread on it; a numbered pin marks objects with open threads (Starter, Pro and Enterprise). Pins are shown in the designer only, never in the runtime. See [review screens before deploy](/docs/eaxscada/how-to/review-before-deploy/).

## Examples

### A discharge pressure dial bound on the Bind tab

The dial shows pump P-101's discharge pressure on 0 to 10 bar, bound with the Bind tab's Gauge Reading target: the live gauge engine draws it, with the value's quality.

1. Place a **Dial Gauge** from **Industrial Equipment**; label `PT101`.
2. **Bind** tab: target **Gauge Reading (Numeric)**, type **Tag**, tag `Plant/Processing/Pumps/P101/DischargePressure`.
3. Inspector: range 0 to 10, unit `bar`, 2 decimals.
[Image: A discharge pressure dial bound on the Bind tab]

3.42 bar on the dial.
<details>
<summary>The classic dial gauge as saved in the screen (JSON)</summary>

```json
{
  "type": "Gauge",
  "props": {
    "minVal": 0,
    "maxVal": 10,
    "decimals": 2,
    "unit": "bar",
    "fill": "#0f172a",
    "stroke": "#38bdf8",
    "strokeWidth": 2,
    "label": "PT101"
  },
  "bindings": {
    "value": {
      "type": "tag",
      "tagPath": "Plant/Processing/Pumps/P101/DischargePressure"
    }
  }
}
```

</details>

## See also

- [Gauge](/docs/eaxscada/reference/generated/widgets/gauges/gauge/)
- [Transmitter](/docs/eaxscada/reference/generated/widgets/equipment/transmitter/)