# KPI card

> The KPI dashboard card: one live value, large, with its unit, quality, change over a time window and an optional target.

Product: eaxScada · Type: Reference · Editions: Starter
Source: https://eaxware.com/docs/eaxscada/reference/generated/widgets/dashboard-cards/card-kpi/
Verified against commit 17f9c67.

<!-- GENERATED by tools/docgen (node tools/docgen/docgen.mjs). Do not edit by hand: change the source and regenerate. -->

One value, large: its unit, its quality, the change over the last 15 minutes to 24 hours (from the historian) and an optional target. A badge appears only for a Bad or Uncertain value or an active alarm on the tag. Without a tag the card shows a fixed value marked STATIC, or a dash: never an invented reading.
[Image: KPI card card]
|  |  |
|---|---|
| Card palette | Display Widgets › Digital KPI Metric Card |
| Card kind | `kpi_card` (`body.widget`) |
| Default size | 3 × 2 grid cells |

## Settings

Double-click the card (or select it and press Enter) to open its settings. The settings are stored in the card's `body.params`.

| Shown as | Key (`body.params`) | Type | Unit | Default | Allowed values | What it does |
|---|---|---|---|---|---|---|
| Tag | `tagPath` | Tag path (read) |  | — |  | The tag shown. A card without a tag shows its fixed value marked STATIC, or a dash. *Settings hint: Without a tag the card shows the fixed value below, marked STATIC.* |
| Unit | `unit` | Text |  | `""` |  | Unit shown after the value. Display only. |
| Decimals | `decimals` | Number |  | — |  | Decimals shown. Empty: automatic from the range. |
| Target | `target` | Number |  | `""` |  | A reference value shown under the value (a production target). *Settings hint: Optional reference shown under the value.* |
| Change over | `deltaWindow` | Choice |  | — | `15m`<br>`1h`<br>`8h`<br>`24h` | The change shown is the value now minus the value at the start of this window, read from the historian. *Settings hint: The change shown is the value now minus the value at the start of this window (historian).* |
| Fixed value (no tag) | `value` | Text |  | `"—"` |  | A fixed value shown when no tag is set, marked STATIC. The palette places a dash. |

## Quality and parameters

Values come with their quality: a Bad or Uncertain value is marked on the card, and a value not yet received shows a dash, never an invented number. A card on a screen with parameters takes `{Name}` in its tag paths.

## Examples

### Line 1 throughput against its target

The throughput of line 1 in units per hour, with its target of 1300.

1. Click **Digital KPI Metric Card** in the dashboard palette (or an empty cell).
2. Double-click the card: **Tag** `Plant/Processing/Lines/L1/Throughput`, **Unit** `u/h`, **Decimals** 0, **Target** 1300, **Change over** 8h.
3. Title `Line 1 throughput`.
[Image: Line 1 throughput against its target]

1240 u/h against a target of 1300.
## See also

- [Dashboard grid](/docs/eaxscada/reference/generated/widgets/data/dashboard-grid/)
- [Gauge card](/docs/eaxscada/reference/generated/widgets/dashboard-cards/card-gauge/)