# Centrifugal pump card

> The centrifugal pump dashboard card: a pump with its running state, flow, speed and discharge pressure, and a start / stop button.

Product: eaxScada · Type: Reference · Editions: Starter
Source: https://eaxware.com/docs/eaxscada/reference/generated/widgets/dashboard-cards/card-centrifugal-pump/
Verified against commit 9bd8f3f.

<!-- GENERATED by tools/docgen (node tools/docgen/docgen.mjs). Do not edit by hand: change the source and regenerate. -->

A pump on one card: the pump drawing with its running state, the flow, the speed and the discharge pressure, and one command button. The values read `<folder>/Running`, `/Flow`, `/Speed` and `/DischargePressure` unless a tag is set for one of them.
[Image: Centrifugal pump card card]
|  |  |
|---|---|
| Card palette | Full Industrial Faceplates › Centrifugal Pump |
| Card kind | `centrifugal_pump` (`body.faceplate`) |
| Default size | 4 × 3 grid cells |

:::caution[Safety-relevant]
Its start / stop button writes to the pump's tag (control command).
:::

## Settings

Double-click the card (or select it and press Enter) to open its settings. The settings are stored in the card's `body.params`.

| Shown as | Key (`body.params`) | Type | Unit | Default | Allowed values | What it does |
|---|---|---|---|---|---|---|
| Equipment name | `pumpName` | Text |  | `"Pump"` |  | The name shown on the card. |
| Tag folder | `tagPrefix` | Tag path (read) |  | `""` |  | The folder holding the equipment's tags (Plant/Processing/Pumps/P101). Each value reads &lt;folder&gt;/&lt;signal&gt; exactly, unless a tag is set for that signal. *Settings hint: The folder holding this equipment's tags, e.g. Area/Equipment. Each value below reads &lt;folder&gt;/&lt;name&gt; exactly, unless a tag is set for it.* |
| Running tag (optional) | `runningTag` | Tag path (read) |  | — |  | The running feedback tag (1 running, 0 stopped). Empty: &lt;folder&gt;/Running. *Settings hint: Empty = &lt;folder&gt;/Running.* |
| Flow tag (optional) | `flowTag` | Tag path (read) |  | — |  | The flow tag. Empty: &lt;folder&gt;/Flow. *Settings hint: Empty = &lt;folder&gt;/Flow.* |
| Speed tag (optional) | `speedTag` | Tag path (read) |  | — |  | The speed tag. Empty: &lt;folder&gt;/Speed. *Settings hint: Empty = &lt;folder&gt;/Speed.* |
| DischargePressure tag (optional) | `pressureTag` | Tag path (read) |  | — |  | The discharge pressure tag. Empty: &lt;folder&gt;/DischargePressure. *Settings hint: Empty = &lt;folder&gt;/DischargePressure.* |
| Confirmation | `confirmation` | Choice |  | `"none"` | `none`<br>`require`<br>`esignature` | What a press asks before it writes: none; require, a confirmation dialog; esignature, the signed-in user's password (the signer is shown read-only, the password field starts empty). The server requires the same confirmation or signature for `&lt;folder&gt;/Command` from every client. *Settings hint: none: the command is sent when pressed; require: a confirmation dialog first; esignature: the signed-in user signs with their password. The server requires the same for these tags from every client.* |
| Interlock tag (optional) | `interlockTag` | Tag path (read) |  | `""` |  | A tag that disables the button while it is not 0, has no value or a Bad value (an INTERLOCKED chip is shown). The server refuses the command while the interlock is active, from every client. Empty: no interlock. *Settings hint: While this tag is not 0, or has no value or a Bad value, the card's commands are disabled and the server refuses them. Empty: no interlock.* |

## Actions

The button follows the running feedback, never the click: **START PUMP** while the pump is stopped, **STOP PUMP** while it runs, and disabled (**STATE UNKNOWN**) when the feedback is missing, not Good or not 0 / 1. A press writes 1 (start) or 0 (stop) to `<folder>/Command`, after the card's confirmation or electronic signature when one is set, and never while its interlock is active. The tag's own write policy applies as well: the strictest wins.

**Commands.** The card writes to tags only in the live operator view, never in *Edit layout*, and only through the guarded write path: the server checks the user's rights, the tag's write range and the confirmation or electronic signature the tag requires, and the card reports the server's answer (a refused write is never shown as done). A card without its tag cannot send anything.

## Quality and parameters

Values come with their quality: a Bad or Uncertain value is marked on the card, and a value not yet received shows a dash, never an invented number. A card on a screen with parameters takes `{Name}` in its tag paths.

## Examples

### A pump whose tags are not in one folder

Pump P-102's running feedback is in its folder, but the card should show P-101's discharge pressure header. A tag set for one value replaces \<folder>/\<signal> for that value only.

1. Add the card; **Tag folder** `Plant/Processing/Pumps/P102`, **Equipment name** `P-102`.
2. **DischargePressure tag** `Plant/Processing/Pumps/P101/DischargePressure`.
[Image: A pump whose tags are not in one folder]

P-102 stopped; its flow and speed read P-102's folder, its pressure the tag set.
## See also

- [Centrifugal pump (screen object)](/docs/eaxscada/reference/generated/widgets/equipment/centrifugal-pump/)
- [Dashboard grid](/docs/eaxscada/reference/generated/widgets/data/dashboard-grid/)
