# Alarm annunciator

> The alarm annunciator screen object: a panel of counter tiles, one per alarm class and priority.

Product: eaxScada · Type: Reference · Editions: Starter
Source: https://eaxware.com/docs/eaxscada/reference/generated/widgets/alarms/alarm-annunciator/
Verified against commit 4064fb4.

<!-- GENERATED by tools/docgen (node tools/docgen/docgen.mjs). Do not edit by hand: change the source and regenerate. -->

A panel of counter tiles: one row per alarm class, one column per priority, like a classic annunciator panel. Each tile takes the class's colour while it counts an alarm and blinks while one is unacknowledged. A click on a tile shows its alarms or opens a screen.
[Image: Alarm annunciator in the operator runtime]
|  |  |
|---|---|
| Palette | Not in the palette |
| JSON `type` | `AlarmAnnunciator` |
| Name in the inspector | Alarm annunciator |
| Size | drawn from `width` and `height`; a resize changes them |
| Added by | `designer_alarm_widgets.js` |

:::caution[Safety-relevant]
Counts live alarms by class and priority (alarm surface).
:::

## Properties

| Shown as | Key | Type | Unit | Default | Allowed values | What it does |
|---|---|---|---|---|---|---|
| Area (tag folder) | `alarmAreaFilter` | Tag folder |  | — |  | Shows only the alarms of tags under this folder (Plant/Line1). Empty: every alarm. The product's built-in safety alarms (plant emergency stop, PLC faults) are always shown, first. *Inspector hint: Only the alarms of tags under this folder, e.g. Plant/Line1. Built-in safety alarms are always shown.* |
| Screen to open | `navScreen` | Screen id |  | — |  | The screen opened on a click when the click action is "Open the screen". *Inspector hint: Opened on click when the click action is "Open the screen".* |
| Classes (rows) | `panelClasses` | List (comma separated) |  | — |  | The classes, one row each, comma separated. Default Safety, Process, Environmental, Equipment, Diagnostic. |
| Priorities (columns) | `panelPriorities` | List (comma separated) |  | — |  | The priorities, one column each, comma separated. Default CRITICAL, HIGH, MEDIUM, LOW. |
| Row and column headers | `panelHeaders` | Yes / no |  | — |  | Shows the class names on the left and the priorities on top. |
| Shows | `counterShow` | Choice |  | — | `unacked_total` Unacknowledged / total<br>`unacked` Unacknowledged<br>`total` Total | What a counter shows: unacknowledged / total, unacknowledged only, or total only. |
| Click | `clickAction` | Choice |  | — | `summary` The alarms in a dialog<br>`screen` Open the screen<br>`none` Nothing | What a click does: the alarms in a dialog, open the screen (navScreen), or nothing. |
| — | `width` | Number |  | `520` |  | Width of the panel. |
| — | `height` | Number |  | `220` |  | Height of the panel. |
| — | `label` | Text |  | `"Alarm annunciator"` |  | The panel's name in the layers list. |
| X | `x` | Number | px | — |  | Horizontal position of the object's top-left corner on the screen, in screen pixels from the left edge. |
| Y | `y` | Number | px | — |  | Vertical position of the object's top-left corner, in screen pixels from the top edge. |
| Rotation | `rotation` | Number | ° | — |  | Rotation of the object, clockwise, in degrees. |
| Opacity | `opacity` | Number |  | — |  | 0 (invisible) to 1 (opaque). An object disabled by an interlock is drawn at 0.45 whatever this says. |
| States | `states` | Object |  | — |  | This object's own state styles (normal, hover, pressed, on, disabled, bad, locked, unconfigured), edited in the inspector's States section. Visual only. Empty: the project's state styles. |
| State family | `styleFamily` | Text |  | — |  | The state family whose project styles apply (button, input, toggle, selector, faceplateButton, default). Empty: the family of the object's type. |

## Bindings and conditions

The object reads this tag through its own properties, with their quality: `alarmAreaFilter`. A Bad or Uncertain value is marked on the object (see Quality below), never drawn as good.

The **Bind** tab ties a property to a tag or an expression: a *tag* binding takes the tag's value, an *expression* binding computes one (see the [expression language](/docs/eaxscada/reference/expression-language/)), optionally through a map, format or script transform. The targets the Bind tab offers for this object:

| Bind tab target | Key | What the bound value does |
|---|---|---|
| Fill Color | `fill` | Sets the fill colour from the value (a colour text such as #22c55e, or a colour mapped by a map transform). |
| Stroke / Border Color | `stroke` | Sets the outline colour from the value. |
| Opacity (0.0 - 1.0) | `opacity` | Sets the opacity from the value (0 to 1). |
| Visibility (Boolean) | `visible` | Shows the object when the value is true or non-zero, hides it otherwise. |
| Rotation (°) | `rotation` | Rotates the object by the value, in degrees. |
| Scale / Pulse | `scale` | Scales the object by the value (1 = drawn size). |
| Text / Label | `text` | Replaces the text drawn with the value, formatted by the binding's format. On a Text object a number is followed by the object's unit, as with the Value target (never a word). A Bad value shows a dash. |
| Value (Numeric) | `value` | Shows the value as the object's readout (with the unit and decimals). A Bad value shows a dash. |

The **Cond** tab adds rules evaluated on every value change: **Visibility** (show or hide, by condition or role), **Color & Fill** (colour bands, alarm blinking), **Position** and **Size & Fill** (motion and level mapped from a value), **Rotation** (angle or continuous spin; an empty input range is 0 to 100 and empty angles are -135° to 135°, while 0 is a value), **Security & Touch** (the interlock: a *disable condition*, the role required, what happens when the interlock reads a Bad value) and **Text & Value** (formatted text). A condition that reads a Bad value is never applied as if the value were good: visibility shows the object marked Bad, colours go neutral grey, motion stays where it is, text shows a dash.

## Actions

Any object can carry a click or tap action (the **Action** tab, or **Full Dialog...**). A write action whose tag, value or target is missing is *not configured*: the inspector says so and the operator's press does nothing (unconfigured means disabled). Navigation actions write nothing and ask no confirmation. On touch screens only a deliberate tap runs an action: a swipe or a pinch that ends on the object never does. Action types:

| Action | Key (`action.type`) | What it does |
|---|---|---|
| Set tag to 1 | `set_1` | Writes 1 to the action's tag. |
| Set tag to 0 | `set_0` | Writes 0 to the action's tag. |
| Toggle tag value | `toggle` | Writes the opposite of the tag's LIVE value: 0 when it is not 0, 1 when it is 0. When the live value is unknown, not Good or not a number, nothing is written and the operator is told why; when it changes while the operator confirms or signs, nothing is written either. |
| Set tag to 1 on press and to 0 on release | `momentary_1_0` | Writes 1 while pressed and 0 on release (hold to run). On touch, the press counts only after the finger is held still; the release is always sent. A held press is also released when the browser window loses focus or the page is hidden, and in the designer when a drag or a resize of the object starts. |
| Set tag to 0 on press and to 1 on release | `momentary_0_1` | Writes 0 while pressed and 1 on release. Released in the same cases as the 1/0 momentary. |
| Write custom value | `write_val` | Writes the number in write_value. |
| Run script | `run_command` | Runs a client script with the scripting API (system.tag.write, system.nav.openPopup...). Ctrl+Space completes the API. |
| Navigate to page / screen | `navigate` | Opens another screen, optionally with parameters or a parameter set. |
| Open popup screen | `open_popup` | Opens a screen in a popup window: modal or not, centred, next to the object or at a fixed position, with parameters. |
| Close popup | `close_popup` | Closes the popup the object is in, or the popup with the given id. |
| Open dock | `open_dock` | Opens a screen docked to an edge of the runtime (top, bottom, left, right). |
| Close dock | `close_dock` | Closes the dock on that edge. |
| Open or close dock | `toggle_dock` | Opens or closes the dock on that edge. |
| Back | `nav_back` | Goes back to the previous screen. |
| Forward | `nav_forward` | Goes forward again after Back. |
| Home screen | `nav_home` | Opens the project's home screen. |
| Open downtime panel | `open_downtime` | Opens the operator runtime's Downtime panel (OEE and downtime, Pro and Enterprise), optionally on one machine (its machine id). Navigation only: nothing is written to a tag or a machine. A machine the operator may not read is not shown; where the panel is not available, a notice says so. Offered in the designer only when the licence includes OEE and downtime. |

## States, text and parameters

**States.** An object's look follows its state: normal, hover, pressed, on, disabled, bad (quality), locked (role) and unconfigured. The project's state styles (opened from an object's **States** section, or from the Project manager's Operator runtime section) give each family of objects its colours per state, and the inspector's **States** section overrides them for one object (stored in `props.states`). States are visual only: whether an object can be operated is decided by its interlock, the user's rights and the server.

This object belongs to the state family `default` (all other objects): disabled (an interlock dims it to 0.45 opacity), bad (a tag it reads is Bad) and locked (missing role) apply when the object has conditions or an action; the other states apply to objects that are operated.

**Screen parameters.** On a screen with parameters, `{Name}` in any text of the object (tag paths of bindings and actions, expressions, conditions, interlocks, the confirmation tag, texts) is replaced by the parameter's value when the screen opens, so one screen serves many pieces of equipment (`{Pump}/Running`). See [screen parameters](/docs/eaxscada/reference/screen-parameters/).

**Quality.** When a value the object reads is Bad, not readable, Uncertain or stale, the object is marked: a red x and a grey veil (or hatching, per the project's quality style) for Bad or no connection, a blue lock for a tag the signed-in account may not read, an amber ? for Uncertain, a dashed outline for stale. A tag that is not readable is greyed as Bad and its value is never shown as good. The lock shows only when every Bad tag of the object is not readable: a device fault keeps the red x. Each object shows one marker, for its worst state, and markers that would overlap merge into one, drawn on the largest object with the worst state of all. The marker's tooltip lists every tag, its quality and its age. A Bad value is never drawn as a good one. See [show bad and stale values](/docs/eaxscada/how-to/show-bad-and-stale-values/).

**Comments.** In the studio, right-click the object and choose **Add comment** to start a design-review thread on it; a numbered pin marks objects with open threads (Starter, Pro and Enterprise). Pins are shown in the designer only, never in the runtime. See [review screens before deploy](/docs/eaxscada/how-to/review-before-deploy/).

## Examples

### An annunciator for the processing area, three classes

The Safety, Process and Equipment classes of the processing area, against CRITICAL, HIGH, MEDIUM and LOW.

1. Place **Annunciator panel** from **Alarms**.
2. **Area** `Plant/Processing`; **Classes (rows)** Safety, Process, Equipment.
[Image: An annunciator for the processing area, three classes]

Safety: one critical; Process: one high and one medium; Equipment: one low.
<details>
<summary>The alarm annunciator as saved in the screen (JSON)</summary>

```json
{
  "type": "AlarmAnnunciator",
  "props": {
    "alarmAreaFilter": "Plant/Processing",
    "panelClasses": "Safety,Process,Equipment",
    "panelPriorities": "CRITICAL,HIGH,MEDIUM,LOW",
    "panelHeaders": true,
    "label": "Processing annunciator"
  }
}
```

</details>

## See also

- [Alarm counter](/docs/eaxscada/reference/generated/widgets/alarms/alarm-counter/)
- [Alarm classes and history](/docs/eaxscada/reference/alarm-classes-and-history/)
