# Alarm definitions and events

> Alarm definitions and events: every key, its type and meaning, generated from the Go structs that decode it.

Product: eaxScada · Type: Reference · Editions: Starter
Source: https://eaxware.com/docs/eaxscada/reference/generated/config/alarms/
Verified against commit 47a580c.

<!-- GENERATED by tools/docgen (node tools/docgen/docgen.mjs). Do not edit by hand: change the source and regenerate. -->

Alarm definitions (data/alarms/alarm\_definitions.json) and the alarm events the engine records.

Keys are the JSON keys. **Optional** marks keys that are omitted when empty, or that may be absent (pointers).

## AlarmDefinition

AlarmDefinition configures an alarm rule

Source: `eaxScada/internal/alarms/alarms.go`

| Key | Type | Optional | Description |
|---|---|---|---|
| `id` | string |  |  |
| `tag_path` | string |  |  |
| `name` | string |  |  |
| `description` | string |  |  |
| `category` | string |  | "Safety", "Process", "Environmental", "Equipment", "Diagnostic" |
| `severity` | [Severity](#severity) |  |  |
| `condition` | [ConditionType](#conditiontype) |  |  |
| `setpoint` | number |  |  |
| `deadband` | number |  |  |
| `trip_delay_ms` | integer |  |  |
| `clear_delay_ms` | integer |  |  |
| `target_roles` | string |  | "ALL", "Operator,Supervisor", etc. |
| `require_comment` | boolean |  |  |
| `sound_alert` | boolean |  |  |
| `updated_at` | integer |  |  |
| `ack_required` | boolean | yes | Controller handshake (handshake.go). All optional: a definition without them behaves as before. AckRequired: false = the alarm needs no acknowledgement (it is active while its condition holds and returns to normal on its own; it never enters UNACK_ALARM or RTN_UNACK). Absent (nil) or true = required. |
| `ack_tag` | string | yes | AckTag: eaxScada writes 1 to it when the activation is acknowledged (by an operator or by PlcAckTag). Never 0: the controller resets it. |
| `shown_tag` | string | yes | ShownTag: eaxScada writes 1 to it once the activation has been shown on a signed-in operator's screen. Never 0: the controller resets it. |
| `plc_ack_tag` | string | yes | PlcAckTag: a rising edge (0 to non-zero) of this tag while the activation is unacknowledged acknowledges it, recorded as the controller's. Ignored when AckRequired is false. |

## AlarmEvent

AlarmEvent represents a live or historical alarm state transition

Source: `eaxScada/internal/alarms/alarms.go`

| Key | Type | Optional | Description |
|---|---|---|---|
| `event_id` | string |  |  |
| `alarm_id` | string |  |  |
| `tag_path` | string |  |  |
| `name` | string |  |  |
| `description` | string |  |  |
| `category` | string |  |  |
| `severity` | [Severity](#severity) |  |  |
| `condition` | [ConditionType](#conditiontype) |  |  |
| `setpoint` | number |  |  |
| `event_type` | [EventType](#eventtype) |  |  |
| `previous_state` | [State](#state) |  |  |
| `current_state` | [State](#state) |  |  |
| `value` | number |  |  |
| `target_roles` | string | yes |  |
| `timestamp` | integer |  | Nanoseconds |
| `active_time` | integer | yes |  |
| `ack_time` | integer | yes |  |
| `ack_user` | string | yes |  |
| `ack_reason` | string | yes |  |
| `shelved_until` | integer | yes |  |
| `shelved_user` | string | yes |  |
| `shelved_reason` | string | yes |  |
| `unshelved_user` | string | yes | UnshelvedUser is who lifted a shelve (UNSHELVE events only); "SYSTEM" when the shelve expired. |
| `suppressed` | boolean | yes | Suppressed: alarm evaluation is suspended (the runtime is stopped), so this state is the last one known, not a live one. Set on the copies the engine returns, never journaled. |
| `suppressed_reason` | string | yes |  |
| `message_key` | string | yes | Translatable texts (messages.go): the translation keys of the definition's name (MessageKey) and description, and the arguments of their {placeholders}. Name and Description keep the literal text in the project's default language, so a reader without translations (an export, an older client) still has it. Journaled with the event. |
| `message_args` | map of string to string | yes |  |
| `description_key` | string | yes |  |
| `activation_id` | string | yes | Controller handshake (handshake.go). ActivationID: the event id of the TRIP that started the current activation (occurrence); unchanged by its ACK, RTN, SHOWN and SIGNAL events. A shown confirmation and every handshake write name it. |
| `no_ack_required` | boolean | yes | NoAckRequired: this activation needs no acknowledgement (its definition's ack_required is false): ACK_ALARM here means "active", not "acknowledged by someone". |
| `confirm_shown` | boolean | yes | ConfirmShown: the definition has a shown_tag, so an operator screen that displays this activation confirms it (POST /api/alarms/shown). |
| `shown_user` | string | yes | ShownUser / ShownTime: the first signed-in operator whose screen displayed this activation, and when. |
| `shown_time` | integer | yes |  |
| `shown_signal` | [SignalState](#signalstate) | yes | ShownSignal / AckSignal: the state of this activation's write of 1 to the shown_tag / ack_tag: "" none due, "pending", "written" (confirmed: never sent again, by this node or by a new primary after failover), "dropped" (not written before the activation ended: never sent). |
| `ack_signal` | [SignalState](#signalstate) | yes |  |
| `ended_time` | integer | yes | EndedTime: when this activation ended (the alarm went from a standing state to NORMAL or SHELVED); 0 while it stands. Its pending signals are not retried after it (handshake.go). |
| `note` | string | yes | Note: what this journal record adds ("no acknowledgement required", "shown on an operator screen", the handshake write). Per event. |
| `simulated` | boolean | yes | Simulated: Value came from a simulated source (a simulated eaxPLC accepted for commissioning: tagengine/source.go), not the plant. On a TRIP or RTN it says the alarm was raised or cleared by a simulated value; on the live alarm, that its latest value is simulated. Only a marker: it never changes how the alarm evaluates. Journaled; rows written before it read false. |
| `quality` | string | yes | Value quality (quality.go). Quality: the quality name of the value the alarm last saw when it was not Good ("Uncertain (EU exceeded)", "Bad"); "" for Good. On a quality alarm, the quality of the value that raised or cleared it. Journaled. |
| `held` | boolean | yes | Held / HeldSince: the tag's value is Bad, so the alarm keeps the state it had (it neither trips nor returns to normal on a Bad value) since HeldSince (Unix ns). Value is the last reading. Live record only. |
| `held_since` | integer | yes |  |
| `quality_alarm` | boolean | yes | QualityAlarm: this is a tag's "signal unreadable" alarm (derived, no stored definition); Covers lists the alarms on the tag it covers. |
| `covers` | list of string | yes |  |

## Severity

Severity levels

Source: `eaxScada/internal/alarms/alarms.go`

Underlying type: `string`.

| Value | Name | Description |
|---|---|---|
| `CRITICAL` | `SeverityCritical` |  |
| `HIGH` | `SeverityHigh` |  |
| `MEDIUM` | `SeverityMedium` |  |
| `LOW` | `SeverityLow` |  |
| `INFO` | `SeverityInfo` |  |

## ConditionType

AlarmCondition indicates the threshold rule

Source: `eaxScada/internal/alarms/alarms.go`

Underlying type: `string`.

| Value | Name | Description |
|---|---|---|
| `HIGH_HIGH` | `CondHighHigh` |  |
| `HIGH` | `CondHigh` |  |
| `LOW` | `CondLow` |  |
| `LOW_LOW` | `CondLowLow` |  |
| `EQUAL` | `CondEqual` |  |
| `NOT_EQUAL` | `CondNotEqual` |  |
| `DEVIATION_HIGH` | `CondDeviationHigh` |  |
| `DEVIATION_LOW` | `CondDeviationLow` |  |
| `RATE_OF_CHANGE` | `CondROC` |  |
| `BAD_QUALITY` | `CondBadQuality` |  |

## EventType

EventType categorizes state machine transitions in the SOE journal

Source: `eaxScada/internal/alarms/alarms.go`

Underlying type: `string`.

| Value | Name | Description |
|---|---|---|
| `TRIP` | `EventTrip` |  |
| `ACK` | `EventAck` |  |
| `RTN` | `EventRTN` |  |
| `SHELVE` | `EventShelve` |  |
| `UNSHELVE` | `EventUnshelve` |  |
| `SHOWN` | `EventShown` | EventShown: the activation was displayed on a signed-in operator's screen (handshake.go). The state does not change. |
| `SIGNAL` | `EventSignal` | EventSignal: a controller handshake tag was written (1) for the activation (handshake.go). The state does not change. |

## State

ISA-18.2 Alarm States

Source: `eaxScada/internal/alarms/alarms.go`

Underlying type: `string`.

| Value | Name | Description |
|---|---|---|
| `NORMAL` | `StateNormal` |  |
| `UNACK_ALARM` | `StateUnackAlarm` |  |
| `ACK_ALARM` | `StateAckAlarm` |  |
| `RTN_UNACK` | `StateRTNUnack` |  |
| `SHELVED` | `StateShelved` |  |

## SignalState

SignalState is the state of one handshake write of an activation.

Source: `eaxScada/internal/alarms/handshake.go`

Underlying type: `string`.

| Value | Name | Description |
|---|---|---|
| `""` | `SignalNone` |  |
| `pending` | `SignalPending` |  |
| `written` | `SignalWritten` |  |
| `dropped` | `SignalDropped` | SignalDropped: not written before the activation ended, and never sent (DropSignal). |