# Restrict a screen to a role level

> Set a screen's Required Access Level so that only users at or above a role level open it in the operator runtime and send its commands - what lower users see, how writes, the Studio, popups and the AI assistant follow the level, and the Problems panel warnings.

Product: eaxScada · Type: How-to guide · Editions: Starter, Pro, Enterprise
Source: https://eaxware.com/docs/eaxscada/how-to/restrict-screens-by-access-level/
Verified against commit dcb41d3.

## Goal

Keep a screen (a maintenance page, a tuning faceplate, a recipe editor) away from users below a role level. The server enforces the level: a lower user never receives the screen, and its buttons and inputs never count for that user's writes.

## Before you start

- Setting the level is part of the screen's Display Settings: an engineer who may edit the screen (Lead_Engineer or Administrator) changes it, and operators get it with the next **Deploy**.
- The level is compared with the user's **role level**: the highest level of the roles the user holds, directly or through a group. Custom roles have levels from 1 to 99.
- The level hides a screen; it does not grant anything. Tag permissions (**Security → Topic Rights**) still apply to every read and write, whatever screen it comes from.

## 1. Choose the level

1. In the display tree, click the settings icon next to the screen (or open the screen and choose **Project → Display Size & Properties...**).
2. Open the **Telemetry & Security** tab.
3. Choose **Required Access Level**, then **Apply & Save**.
4. **Deploy** the project.
[Image: Display Settings, Telemetry and Security tab: Required Access Level set to Lead_Engineer and above, with the hint that the server enforces it.]
[Image: Display Settings, Telemetry and Security tab: Required Access Level set to Lead_Engineer and above, with the hint that the server enforces it.]

A maintenance screen restricted to Lead_Engineer and above.
| Required Access Level | Stored as | Who opens the screen | Level |
|---|---|---|---|
| **No restriction (anyone signed in)** | `*` (or empty) | every signed-in user | 0 |
| **Shift_Operator and above** | `operator` | Shift_Operator, Process_Supervisor, Lead_Engineer, Administrator | 40 |
| **Process_Supervisor and above** | `supervisor` | Process_Supervisor, Lead_Engineer, Administrator | 60 |
| **Lead_Engineer and above** | `engineer` | Lead_Engineer, Administrator | 80 |
| **Administrator only** | `admin` | Administrator | 100 |
| any other stored value | | Administrator only (fail closed) | 100 |

An Administrator always passes. A Compliance_Auditor (level 20) is below **Shift_Operator and above**. The AI co-pilot account (level 10) opens only screens with no restriction.

## 2. What a user below the level sees

The server leaves the screen out of what it sends that user, so the operator runtime never has it:

- it is not in the **Screens** list, the menus or a page's docks;
- a link, an address (`/runtime?screen=...`), a page route, a dock or an embedded copy of it shows **You don't have access to this screen**, with the screen id;
- a popup of it (an **Open popup** action, `system.nav.openPopup`, `system.popup.open`) is refused with **You don't have access to this screen: &lt;id&gt;**.
[Image: The operator runtime signed in as a Process_Supervisor: the maintenance screen needs Lead_Engineer and above, so it shows You don't have access to this screen.]
[Image: The operator runtime signed in as a Process_Supervisor: the maintenance screen needs Lead_Engineer and above, so it shows You don't have access to this screen.]

A supervisor opens the address of a Lead_Engineer screen.
A screen that is missing or not deployed still says **This screen is not deployed.**: only a screen the user may not open says **You don't have access**.

## 3. What the level does to writes

A restricted screen's buttons and inputs count only for users at or above its level:

- a write that names the restricted screen as its source, from a user below the level, is refused: HTTP `403`, status `screen_access_denied`, code `WRITE_DENIED_SCREEN_ACCESS`;
- a command on a restricted screen never lets a lower user's value past another object's interlock on the same tag. The server's interlock check counts, for that user, only the commands of the screens the user may open, so a restriction can only narrow what is allowed, never widen it;
- writes over the broker (NATS) carry no user screen: they count only the commands of screens with no restriction.

## 4. In the Studio

- Users who may edit screens (Lead_Engineer and above) read every screen in the Studio, whatever its level.
- A user below Lead_Engineer who reads a screen above their level through the Studio API is refused (`403 screen_access_denied`).
- The project tree and the cross-reference search still list restricted screen names (not their content).

## 5. The AI assistant and MCP clients

The assistant's screen tools apply the same levels as the Studio, for the account that calls them:

- reading a screen (`scada_get_screen`) above the caller's level is refused with the `screen_access_denied` wording, and listing (`scada_list_screens`) leaves it out;
- proposing a change to or the deletion of such a screen (`scada_propose_screen`) is refused, because the proposal would carry its current design;
- the AI co-pilot account (level 10) reads only screens with no restriction; a call without a signed-in identity reads no screen;
- an authoring account that holds Lead_Engineer as well as AI_CoPilot keeps the engineer's reads, as in the Studio. Such an account still never signs or approves.

## 6. Check the links to restricted screens

The **Problems** panel has two warnings for screen access:

| Rule | Warns when |
|---|---|
| `nav-target-restricted` | a link, an **Open popup** action, a page or a dock opens a screen with a higher Required Access Level than the screen (or page) it is on. Users who can open the first screen but not the second see **You don't have access to this screen**. |
| `screen-access-unknown` | the stored level is not one of `*`, `operator`, `supervisor`, `engineer`, `admin`: the server treats the screen as **Administrator only**. Choose a level in Display Settings. |

After a deploy, the Studio also lists such links in a warning ("N link(s) open a screen with a higher Required Access Level..."). See [Check screens before deploying](/docs/eaxscada/how-to/check-screens-before-deploy/).

## Result

Users below the level never get the screen or its design; a link to it says why; its commands never count for their writes. Users at or above the level work as before.

## Troubleshooting

| Symptom | Cause and fix |
|---|---|
| An operator sees **You don't have access to this screen** on the start page | The startup page or a dock shows a restricted screen. Lower the screen's level, or give that role another home screen (Project manager, Operator runtime, **Home screen per role**). |
| A supervisor's START button on a shared faceplate is refused with `WRITE_DENIED_SCREEN_ACCESS` | The write names a screen above the supervisor's level. Put the command on a screen the supervisor may open. |
| A screen is for administrators only though nobody chose that | Its stored level is not a known value (`screen-access-unknown`). Choose a level and deploy. |

## Upgrading

Before this version the level was stored with the screen and read nowhere: every signed-in user could open every screen. After the upgrade, a screen whose level was set at some point is enforced. Check each screen's **Required Access Level** before upgrading a production server.

The **Telemetry Streaming Mode** setting of the same tab did nothing and is removed; a stored value is ignored.
