# Limit tag writes

> Set the values a tag accepts - a write range on the tag (minimum, maximum, step, allowed values, or text length and allowed texts), limits on the screen's inputs and faceplates, limits bound to other tags - and know that the server refuses any other value from every writer, and refuses writes to tags that do not exist.

Product: eaxScada · Type: How-to guide · Editions: Starter, Pro, Enterprise
Source: https://eaxware.com/docs/eaxscada/how-to/limit-tag-writes/
Status: migrated page, not yet verified against the current code.

## Goal

The speed setpoint of pump P-201 accepts 20 to 95 % in steps of 0.5, and its mode only 0, 1 or 2. Any other value is refused by the server, whoever sends it: a screen, a script, an API client, a NATS command, an assistant's setpoint or a recipe.

## Where limits come from

Every limit below applies. When several limit the same tag, the strictest wins: the highest minimum, the lowest maximum.

| Source | Set in | Checked for |
|---|---|---|
| **The tag's write range** | Drivers → tag mappings (**Write range** action); for an eaxTag, its editor (**Edit range…**) | every writer through eaxScada, and again by the driver just before the device (recipe downloads included) |
| **An input object's limits** (numeric entry, slider, spinner): minimum, maximum, step | the inspector | every writer of that tag, from the moment the screen is saved |
| **A limit bound to a tag** (**Minimum from tag**, **Maximum from tag**) | the inspector | every writer; read when the write arrives |
| **A faceplate's setpoint limits** (`spMin`, `spMax`), on a screen or a dashboard | the faceplate | every writer of the setpoint tag |
| **The engineering range** of the tag | the tag definition | every writer (refused with `422`) |

**Diagram: Where a write is held to the limits of its tag** (data flow)

A write from any writer that goes through eaxScada passes these checks of the server in order. A tag that does not exist is refused first, before any limit. A write sent from a screen the writer may not open, or opened with parameters it does not admit, is refused next. Then every limit on the tag applies at once and the strictest wins: the fixed limits (the write range of the tag, the limits of the inputs and faceplates on saved screens) and a limit bound to another tag, which is read when the write arrives. Then the engineering range of the tag. A write that passes goes on to the interlock, signature and confirmation checks, which are not drawn, and for a tag mapped to a device the driver checks the write range once more before it sends anything.

**Parts**

- **Any writer** (service or process): a screen, a script, an API client, a NATS command, an assistant's setpoint
- **Does the tag exist?** (check or decision): before any limit or signature
- **Its screen allowed?** (check or decision): level and parameters, when sent from a screen
- **Every limit on the tag** (check or decision): the strictest wins
- **Engineering range** (check or decision): of the tag definition
- **Driver** (check or decision): the write range again
- **Fixed limits** (file or document): the tag's write range, input limits, faceplate spMin and spMax
- **A limit bound to a tag** (service or process): read when the write arrives; missing or not Good: refused
- **Device** (device or controller)
- **Refused: 404** (outcome): unknown_tag WRITE_DENIED_UNKNOWN_TAG
- **Refused: 403** (outcome): screen_access_denied or parameters_refused. The audit codes are WRITE_DENIED_SCREEN_ACCESS and WRITE_DENIED_SCREEN_PARAMETERS.
- **Refused: 400** (outcome): out_of_range WRITE_DENIED_OUT_OF_RANGE. The answer carries the minimum and the maximum that apply.
- **Refused: 422** (outcome): refused. The audit code is WRITE_DENIED_OUT_OF_ENG_RANGE.
- **Refused: 409** (outcome): refused, nothing is sent. For a write through POST /api/tags/write, the audit trail records MANUAL_OVERRIDE_REFUSED after the record of the write.

**Connections**

- **Any writer → Does the tag exist?** (command to equipment). A write through POST /api/tags/write, a NATS command or an assistant's setpoint. For a request of a signed-in user, the permission to write the tag is checked before. Raising the plant emergency-stop signal skips every check of the write policy.
- **Does the tag exist? → Refused: 404** (refusal). No eaxTag, driver tag mapping or live tag has this path. A write never creates a tag.
- **Does the tag exist? → Its screen allowed?** (command to equipment)
- **Its screen allowed? → Refused: 403** (refusal). The write was sent from a screen whose Required Access Level is above the writer's, or from a screen opened with parameters its declaration does not admit.
- **Its screen allowed? → Every limit on the tag** (command to equipment)
- **Fixed limits → Every limit on the tag** (configuration or deploy). The write range comes from the tag mapping or the eaxTag; the limits of inputs and faceplates come from every saved screen that writes the tag.
- **A limit bound to a tag → Every limit on the tag** (data or telemetry). Minimum from tag, Maximum from tag: the server reads the bound tag when the write arrives.
- **Every limit on the tag → Refused: 400** (refusal). The value is below the highest minimum, above the lowest maximum, off the step or not one of the allowed values, or a bound limit cannot be read.
- **Every limit on the tag → Engineering range** (command to equipment)
- **Engineering range → Refused: 422** (refusal). The value is outside the engineering range of the tag.
- **Engineering range → Driver** (command to equipment). In between, not drawn: the interlock check, the signature and the confirmation the tag asks for, and the audit record. Only a tag mapped to a device reaches a driver.
- **Driver → Refused: 409** (refusal). The value is outside the write range of the tag mapping, or not a value its data type can hold.
- **Driver → Device** (command to equipment). The value is inside the write range: the driver sends it.

Limits add up, they never replace each other, and a limit that cannot be read refuses the write. A signature does not lift any of them.

## 1. Set the tag's write range

1. Open **Drivers → tag mappings** and click **Write range** on the tag's row (offered for writable mappings). For an eaxTag, open **Drivers → Local tags (eaxTags)**, click **edit** on the tag and **Edit range…**.
2. Fill in what the tag accepts:

   | Field | Example | Meaning |
   |---|---|---|
   | Lowest value | `20` | |
   | Highest value | `95` | |
   | Step | `0.5` | a value must be the lowest value plus a whole number of steps: 20, 20.5, 21... |
   | Only these values | `0, 1, 2` | for a mode or a selector: nothing else is accepted |

   For a **String** tag: **Longest text** (characters; 256 when empty) and **Only these texts** (one per line).
3. **Save**. Empty fields set no limit; clearing every field removes the range.
[Image: The Write range dialog: lowest value 20, highest 95, step 0.5.]
[Image: The Write range dialog: lowest value 20, highest 95, step 0.5.]

The write range of a speed setpoint.
For an eaxTag the range is saved with the tag: click **Save** in the tag editor as well (the editor says "Changed: saved with the tag."). The editor shows the current range under **Write range**; a tag saved without opening **Edit range…** keeps its stored range.
[Image: The eaxTag editor of DocsPlant/Pumps/P201/SpeedSetpoint: its write range 20 to 95, step 0.5, with Edit range...]
[Image: The eaxTag editor of DocsPlant/Pumps/P201/SpeedSetpoint: its write range 20 to 95, step 0.5, with Edit range...]

The eaxTag editor: the write range is edited in its own dialog and saved with the tag.
In the eaxTags file or the API, the member is `write_range`, as on a driver tag mapping (the other members of a definition are listed in [eaxTags local tags](/docs/eaxscada/reference/eaxtags-local-tags/#tag-definition)):

```json
{ "path": "DocsPlant/Pumps/P201/SpeedSetpoint", "writable": true,
  "write_range": { "min": 20, "max": 95, "step": 0.5 } }
{ "path": "DocsPlant/Pumps/P201/Mode", "writable": true,
  "write_range": { "values": [0, 1, 2] } }
```

## 2. Limit the input on the screen

On the numeric entry, slider or spinner that writes the setpoint, set **Minimum**, **Maximum** and **Step** too. The screen then refuses a wrong value before sending it and tells the operator why; the keypad shows the range. See [Add setpoint inputs](/docs/eaxscada/how-to/add-setpoint-inputs/).

To follow a limit that changes (a recipe's maximum), bind **Maximum from tag**. The bound tag is read when the write arrives. If it is missing or its quality is not Good, every write is refused, and the object says why: a limit that cannot be read never lets a value through.

## 3. What a refused write looks like

```json
{ "status": "out_of_range", "error": "...", "path": "DocsPlant/Pumps/P201/SpeedSetpoint", "min": 20, "max": 95 }
```

The answer is `400`; the audit trail records `WRITE_DENIED_OUT_OF_RANGE` with the user and the value tried, and the tag keeps its value. An electronic signature never lifts a limit. In the runtime the operator reads "Refused by the server (allowed 20 … 95)" and the field returns to the live value.

## Writes to tags that do not exist

A write to a path that no eaxTag, driver tag mapping or live tag has is refused with `404`:

```json
{ "status": "unknown_tag", "path": "DocsPlant/Pumps/P210/SpeedSetpoint" }
```

It is journaled as `WRITE_DENIED_UNKNOWN_TAG`, before any limit or signature. A write never creates a tag. Earlier versions created a memory tag of that name and answered `200`, so a mistyped folder looked accepted while the real tag never changed. The same applies to NATS commands and to assistant setpoints when they are staged and approved. The plant emergency-stop signal always exists. If a screen or integration relied on a write to create a memory tag, define the tag as an eaxTag.

The Problems panel lists every screen reference to a tag that does not exist (`broken-tag`).

## Text tags

A driver tag mapping whose data type is **String** takes text, never a number; every other tag takes numbers, never text. Text must be valid UTF-8 without control characters, at most the range's **Longest text**, and one of **Only these texts** when set. Omron FINS, Mitsubishi Electric MC protocol / SLMP, OPC UA, MQTT (JSON) and the NATS bridge write text (the NATS bridge never on a `uns.telemetry` subject, and a write its broker refuses is reported as failed); station-addressed drivers (serial lines, buses, gateways) and every other driver refuse it and send nothing. FINS and MC protocol also read a String tag's text and show it, with its quality, in the **Tag Mappings** grid; their text is printable ASCII and at most the string's length in controller memory, so set **Longest text** to that length. The tag engine holds numbers, so the written text is sent and journaled, not shown as the tag's value on screens. See [Connect to Omron CJ2, CS1, CP1 and NJ/NX controllers (FINS)](/docs/eaxscada/how-to/connect-to-an-omron-fins-controller/#string-tags-text-read-and-write) and [Connect to Mitsubishi Electric MELSEC iQ-R, iQ-F, Q and L controllers](/docs/eaxscada/how-to/connect-to-a-mitsubishi-mc-protocol-controller/#string-tags-text-read-and-write).

## Verify

- Write 96 to the setpoint from the runtime: the input refuses it before sending.
- Send it with the API: `400 out_of_range` with `min` 20 and `max` 95.
- Write 20.25: refused, it is not on the step of 0.5.
- Write 3 to the mode: refused, it is not one of 0, 1, 2.
