# Connect to an S7 PLC

> Read and write a Siemens S7-300, S7-400, S7-1200 or S7-1500 over ISO-on-TCP (port 102) - what is supported, the PLC-side setup (PUT/GET, data blocks without optimized access, access level), rack and slot, S7 addresses, and importing the symbol table for tag names.

Product: eaxScada · Type: How-to guide · Editions: Starter, Pro, Enterprise
Source: https://eaxware.com/docs/eaxscada/how-to/connect-to-an-s7-plc/
Status: migrated page, not yet verified against the current code.

eaxScada reads and writes Siemens S7-300, S7-400, S7-1200 and S7-1500 CPUs over ISO-on-TCP (RFC 1006, TCP port 102), the S7 protocol's transport. The protocol id in the configuration is `ISO_ON_TCP`.

## What is supported

Supported:

- Siemens S7-1500, S7-1200, S7-300 and S7-400 CPUs, through the CPU's Ethernet port or an Ethernet module, on TCP port 102.
- Absolute addresses: data blocks, memory M, inputs I and outputs Q (see [Addresses](#addresses)).
- Types: Bool (one bit), Int16 (INT), UInt16 (WORD), Int32 (DINT), Float32 (REAL).
- Tag names from the symbol table you export from the engineering software as CSV and import for the connection: the PLC does not hold them.

Not supported:

- Siemens S7-1200/1500 data blocks with optimized access: only absolute offsets can be read.
- Reading tags by name from the PLC (symbolic access).
- LREAL (8 bytes): a Float64 tag reads a 4-byte REAL. STRING, timers T and counters C.
- LOGO!, S7-200 and S7-200 SMART: they need other connection parameters than the S7-300/400/1200/1500.

The driver is checked by unit tests of its addresses and frames. It has not yet been run against a CPU in eaxware's test bench; report what you see on yours.

## Set up the PLC (S7-1200 and S7-1500)

In the engineering software, then compile and download:

1. **CPU properties → Protection & Security → Connection mechanisms**: allow access with **PUT/GET communication from remote partner**.
2. **Each data block you read**: in its properties, **Attributes**, clear **Optimized block access**. The offsets of its variables then appear in the block; those are the addresses you map.
3. **Access level**: the CPU's protection must let an HMI connection read, and write for the tags you command, without a password. **Full access** is the simplest.

An S7-300 or S7-400 needs no change.

## Add the connection

1. **Drivers → Add connection**, and choose **Siemens S7 (S7-300/400/1200/1500, ISO-on-TCP)**.
2. **CPU family**, **IP address**. The port stays 102.
3. **Rack** and **Slot** of the CPU:

   | CPU | Rack | Slot |
   |---|---|---|
   | S7-1200, S7-1500 | 0 | 1 |
   | S7-300 | 0 | 2 |
   | S7-400 | 0 | the CPU's slot in the rack |

   Changing the family sets the usual slot. A wrong rack or slot is refused by the CPU after the TCP connection opens: **Test connection** shows it.
4. **UNS prefix** (optional): where this PLC's tags go in the UNS, for example `Plant/Reactor`.
5. **Create connection**, then **Test connection**. A success means the CPU accepted the connection and the S7 setup at that rack and slot, not only that port 102 is open.

[Image: Add connection with Siemens S7 chosen: CPU family, IP address, port, rack, slot, the UNS prefix and the supported controllers and requirements.]
[Image: Add connection with Siemens S7 chosen: CPU family, IP address, port, rack, slot, the UNS prefix and the supported controllers and requirements.]

## Addresses

| Area | Bit | Byte | Word (2 bytes) | Double word (4 bytes) |
|---|---|---|---|---|
| Data block | `DB1.DBX2.4` | `DB1.DBB2` | `DB1.DBW4` | `DB1.DBD8` |
| Memory | `M10.3` | `MB10` | `MW10` | `MD10` |
| Inputs | `I0.0` (or `E0.0`) | `IB0` | `IW0` | `ID0` |
| Outputs | `Q4.1` (or `A4.1`) | `QB4` | `QW4` | `QD4` |

The tag's data type sets how the bytes are read: a Bool needs a bit address; Int16 and UInt16 read 2 bytes, Int32 and Float32 read 4. An address the driver cannot read is refused with the forms above, never read as another address.

## Tag names

S7 keeps its symbol names in the engineering project, not in the PLC. Export the PLC tags or the data block as CSV with at least an `address` column (the operand, such as `DB1.DBD0` or `M10.3`) and a `name` column; `data_type`, `scale`, `unit` and `uns` are read when present, and a double word needs `data_type` Float32 or Int32. In **Browse tags**, choose the connection: with no table yet, the browser says so and offers **Import register map (CSV)**. After the import it lists the symbols with their addresses and reads each one from the PLC, so you see which answer.

## The connection afterwards

The **Connection** tab holds the address, rack, slot and family, with the same requirements panel. **Polling & UNS** holds the scan rate and the UNS prefix; **Tag Mappings** the mapped tags.

Families saved before this version as `ISO-1500`, `ISO-1200`, `ISO-300` or `ISO-400` are read as the S7 names. An `ISO-300` or `ISO-400` connection saved with slot 0 now gets the S7-300/400 default slot, 2; it used to get slot 1.