# Connect to Omron CJ2, CS1, CP1 and NJ/NX controllers (FINS)

> Read and write the memory areas of an Omron CJ2M, CJ2H, CS1, CP1E, CP1L, CP1H or NJ/NX controller over FINS/UDP or FINS/TCP (port 9600) - the controller-side setup (FINS node, address conversion, write protection, NJ/NX memory for CJ-series units), the connection settings and their ranges, addresses (D100, D100.05, CIO 0.00, W10.03, E0_100, T12, D200[10]), data types including STRING text, the per-device scan rate, link diagnostics and the limits.

Product: eaxScada · Type: How-to guide · Editions: Starter, Pro, Enterprise
Source: https://eaxware.com/docs/eaxscada/how-to/connect-to-an-omron-fins-controller/
Status: migrated page, not yet verified against the current code.

## Goal

Read and write the memory of an Omron CJ2, CS1, CP1 or NJ/NX controller from eaxScada over **FINS**, through the CPU's Ethernet port or an Ethernet Unit, by memory-area address as the programming software writes it (`D100`, `CIO 0.00`, `W10.03`, `E0_100`). The protocol id in the configuration is `FINS`.

Supported controllers, as the Drivers catalogue names them (**Omron CJ2M, CJ2H, CS1, CP1E, CP1L, CP1H, NJ/NX (FINS)**):

- **CS/CJ series**: CS1, CJ1, CJ2M and CJ2H, on the built-in EtherNet/IP port or an Ethernet Unit;
- **CP series**: CP1E, CP1L and CP1H, on the built-in Ethernet port or an Ethernet option board;
- **NJ/NX series** with FINS enabled on the built-in EtherNet/IP port, reading the memory for CJ-series units (see [Set up an NJ/NX](#nj-and-nx-controllers)).

Over **FINS/UDP** (the default) or **FINS/TCP**, port **9600** unless changed.

:::caution[Simulator-verified only]
**Verified with:** eaxware's FINS simulator (`tools/fins-sim`) and an in-process simulated controller, over FINS/UDP and FINS/TCP. Benches with real CJ2, CP1 and NJ/NX hardware are pending: commission the connection on a test bench before you use it on a running plant.
:::

## Before you start: set up the controller

### CS, CJ and CP controllers

In the controller's programming software, on the Ethernet port or Ethernet Unit settings, then transfer them and restart the unit:

1. **IP address** of the port. Note it: it is the connection's **Controller IP address**.
2. **FINS node number.** By default the node is the last number of the IP address (`192.168.250.1` is node 1) and the **address conversion** is automatic (dynamic). Keep that unless your network needs another node: then note the node, it becomes the **Controller FINS node**.
3. **FINS/UDP port**: 9600 by default. For **FINS/TCP**, enable the FINS/TCP server connections on the unit; the port is 9600 too unless changed.
4. **Static address conversion** (an IP address table, or a fixed node table): the controller answers FINS/UDP to port 9600 of the sender, so set eaxScada's **Local UDP port** to 9600 (see [Networks, units, ports and byte order](#networks-units-ports-and-byte-order)).
5. **Writes from the network.** If eaxScada is to write, the controller must accept FINS writes from it: on a CJ2, turn **FINS write protection** off, or put eaxScada's FINS node in the list of nodes allowed to write.

Then open **UDP port 9600** (FINS/UDP) or **TCP port 9600** (FINS/TCP) between the eaxScada server and the controller, in both directions for UDP.

### NJ and NX controllers

An NJ/NX controller answers FINS only for the memory it shares with CJ-series units. In its programming software:

1. On the built-in EtherNet/IP port, enable **FINS** (FINS/UDP, port 9600).
2. Turn on the **memory used for CJ-series units** you need (CIO, WR, HR, DM, EM).
3. Give each variable you want to read an **AT specification** in that memory, for example `%D100` or `%W10.03`, and map the address in eaxScada (`D100`, `W10.03`).

Variables are not read by name, and NJ/NX controllers have no A, T or C area over FINS: an address in those areas is refused when you save the mapping.

## Add the connection

1. In the Studio, **Drivers → Add connection**, and in **Connects to** choose **Omron CJ2M, CJ2H, CS1, CP1E, CP1L, CP1H, NJ/NX (FINS)**.
2. Fill in the settings:

| Field | Default | Range | What to enter |
|---|---|---|---|
| **Controller IP address** | empty | required | The IP address of the CPU's Ethernet port or of the Ethernet Unit, for example `192.168.250.1`. |
| **Port** | 9600 | 1-65535 | The port FINS uses on the controller. |
| **Transport** | FINS/UDP | FINS/UDP or FINS/TCP | As enabled on the controller. |
| **Controller series** | CS/CJ (CS1, CJ1, CJ2M, CJ2H) | CS/CJ, CP, NJ/NX | It decides the memory areas and ranges addresses are checked against, and the largest read. |
| **Controller FINS node** (DA1) | automatic | 1-254 | Empty (automatic): the last number of the controller's IP address over FINS/UDP, the node the controller gives over FINS/TCP. |
| **eaxScada FINS node** (SA1) | automatic | 1-254 | Empty (automatic): the last number of the eaxScada server's IP address over FINS/UDP, the node the controller assigns over FINS/TCP. It must differ from the controller's node on the same network. |

3. **Create connection**, then **Test connection**. The test reads the controller's model and its mode: a success names the model and version, the node that answered and the mode (PROGRAM, MONITOR or RUN). A node that answers but refuses the model read still proves a controller speaks FINS there; no answer at all says which node was asked, and, over FINS/UDP, to check the IP address, the FINS node and the local port.

A connection whose IP address is empty, whose port, nodes, networks or units are out of range, or whose two nodes are the same is refused before anything is sent.

### Networks, units, ports and byte order

The **Networks, units, ports and byte order** section of the form holds settings you rarely change:

| Field | Default | Range | Means |
|---|---|---|---|
| **Controller network** (DNA) | 0 | 0-127 | 0: the local network. |
| **Controller unit** (DA2) | 0 | 0-255 | 0: the CPU Unit. |
| **eaxScada network** (SNA) | 0 | 0-127 | 0: the local network. |
| **eaxScada unit** (SA2) | 0 | 0-255 | |
| **Local UDP port** | 0 (any) | 0-65535 | The UDP port eaxScada sends from. Set **9600** when the controller's address conversion is static. Not used over FINS/TCP. |
| **32/64-bit word order** | Low word first (controller default) | low first, high first | How DINT, UDINT, REAL, LINT and LREAL are split over their words. |
| **String byte order** | First character in the high byte (controller default) | high first, low first | How the two characters of each STRING word are stored. |

In the connection's **Communication Timing**, **Request Timeout** (2000 ms when unset) is how long a command waits for its response, and **Retry Count** (0-10) is how many times a **read** with no response is sent again. A write is never sent again.

In the stored configuration the settings are `host`, `port`, `transport` (`udp`, `tcp`), `series` (`CS/CJ`, `CP`, `NJ/NX`), `dest_network`, `dest_node`, `dest_unit`, `src_network`, `src_node`, `src_unit`, `local_port`, `word_order` (`low_first`, `high_first`), `string_byte_order` (`high_first`, `low_first`) and `simulated`.

## Addresses

Addresses are written as in the programming software, in upper or lower case, with a space allowed after the area. A word is a decimal number; a bit is `.00` to `.15`.

| Area | Word | Bit | Also written |
|---|---|---|---|
| CIO (core I/O) | `CIO 100` | `CIO 0.00` | `0.00`, `100` (a bare number is CIO) |
| Work | `W10` | `W10.03` | `WR10` |
| Holding | `H0` | `H0.15` | `HR0` |
| Auxiliary | `A448` | `A448.00` | `AR448` |
| Data memory | `D100` | `D100.05` | `DM100` |
| Extended data memory, by bank | `E0_100` | `E10_5.03` | `EM2_100`, `E0:100` (bank in hexadecimal, 0-18) |
| Timer | `T12` (present value) | `T12` with BOOL: the completion flag | `TIM12` |
| Counter | `C3` (present value) | `C3` with BOOL: the completion flag | `CNT3` |
| STRING of n words | `D200[10]` | - | `E0_100[20]` |

The ranges the driver accepts, by controller series:

| Area | CS/CJ | CP | NJ/NX |
|---|---|---|---|
| CIO | 0-6143 | 0-6143 | 0-6143 |
| W | 0-511 | 0-511 | 0-511 |
| H | 0-1535 | 0-511 | 0-1535 |
| A | 0-1471 | 0-959 | none |
| D | 0-32767 | 0-32767 | 0-32767 |
| T, C | 0-4095 | 0-4095 | none |
| EM banks | 0-18 (hexadecimal) | bank 0 only (CP1H) | 0-18 (hexadecimal) |

A given CPU can have less memory than its series (a CP1E has far fewer D words than a CJ2H). An address the controller does not have is answered with an address error: that tag is BAD with the controller's words, and its neighbours are not affected.

The server checks the address and the data type against the connection's series when the mapping is saved, and the driver checks them again before every read and write. The Studio shows the same errors as you type.

## Data types

| Data type | Words | Notes |
|---|---|---|
| **BOOL** | one bit | A bit address (`D100.05`), or a timer or counter (`T12`, `C3`) for its completion flag. |
| **INT**, **UINT**, **WORD** | 1 | 16-bit signed, unsigned, raw bits. A timer or counter present value takes one of these. |
| **DINT**, **UDINT** (also DWORD), **REAL** | 2 | From the address on, low word first unless the connection says high word first. |
| **LINT**, **LREAL** | 4 | Same word order. |
| **STRING** | n | The length in words is in the address: `D200[10]` is 10 words, up to 20 characters. 1-500 words. |

eaxScada's own type names are accepted too: Bool, Int16, UInt16, Int32, UInt32, Float32, Int64, Float64, String.

### STRING tags: text read and write

A STRING mapping (`D200[10]`, data type **STRING**) is read and written as text:

- **Read**: the whole string is read in one command. The text ends at the first NUL character. It is shown in the **Tag Mappings** grid's value column, in quotes, with the read's quality and time. A read that fails is BAD; the last text is never shown as GOOD. Screens and the tag engine hold numbers, so a screen does not display the text.
- **Write**: printable ASCII only (space to `~`), at most 2 characters per word (20 for `D200[10]`). The text is padded with NUL to the full length and written in **one** MEMORY AREA WRITE, never split. A longer text or another character is refused before sending.
- The tag's write range applies first: **Longest text** (256 characters when empty) and **Only these texts**. Set **Longest text** to the string's length so the operator sees the limit. See [Limit tag writes](/docs/eaxscada/how-to/limit-tag-writes/#text-tags).
- A number written to a STRING tag, or text to any other tag, is refused.

## Scan rate and reads

Each device of the connection is polled at its own **Device Scan Rate (ms)** (`scan_rate_ms`, on the **Polling & UNS** tab): 250 ms for a connection created in the Studio, 100 ms when the setting is empty. See [Scan rates](/docs/eaxscada/explanation/connections-and-stations/#scan-rates).

Within a poll, neighbouring words of one area (gaps of up to 8 unmapped words) are read with one MEMORY AREA READ, up to the device's **Max Block Read Size** and the series' limit: 999 words on CS/CJ and NJ/NX, 256 on CP. A block the controller refuses for an address is read again tag by tag, so one bad address never makes its neighbours BAD. STRING tags and completion flags are read alone. With block reads off on the device, every tag is read alone. The connection's delay between requests (`inter_request_delay_ms`) follows a read that sent a command only, not a tag served from a block already read: 20 words in one block at 100 ms take about 0.1 s, not 2 s.

Every response is matched to its command by its service id (SID) and source; any other frame is dropped and counted. After **3 timeouts in a row** the controller is polled once every **5 s** until it answers, and its tags say so.

## Writes

A write goes through the same path as every other write: the server's write policy and e-signature, the mapping's **read only** flag and [write range](/docs/eaxscada/how-to/limit-tag-writes/). Then the driver:

- **refuses before sending** an invalid address or type, a value the type cannot hold, a BOOL other than 0 or 1, and the read-only memory: **A0-A447 and A960 and up** (only A448-A959 may be written), and **timer and counter completion flags**;
- writes **exactly the mapped address in one command**: a BOOL with the bit area code, so only that bit changes and the other 15 bits of the word are never read and written back; a 2- or 4-word value or a STRING in one MEMORY AREA WRITE;
- **sends it once**. A write succeeds only on the controller's response to that command. A response with an error end code is a refusal, reported in words (for example *read-only area* or *controller in RUN mode*). A write whose response does not come, a lost UDP datagram included, or does not match its SID and source, is reported **NOT CONFIRMED**: the controller may or may not have applied it. eaxScada never repeats it on its own; check the value and write again yourself if needed.

## Link diagnostics

The connection's **Controller link** card (under its settings) and the driver diagnostics show:

| Row | Means |
|---|---|
| **Connection** | FINS/UDP or FINS/TCP, address and port, series, eaxScada's and the controller's FINS addresses, and the model once read |
| **Commands sent / answered** | FINS commands sent and responses matched to them |
| **No answer in time** | commands whose response did not come within the request timeout |
| **Error end codes answered** | responses with an error end code (address out of range, read-only area, wrong mode...) |
| **Frames dropped (other SID or source)** | frames that answered no command in flight, or could not be read |
| **Reads sent again** | reads repeated after no answer |
| **Scan** *device* | the device's scan rate, set and measured; marked when the measured rate is well above the set one |

A link error stays shown until the controller answers again, plus a short hold, so the card does not flicker; the previous error is kept below the current one.

## Not supported

- **Browsing**: the controller holds no tag names over FINS. Map each address.
- **NJ/NX variables by name**: map them to memory for CJ-series units (AT specification) and read that memory.
- **Host Link** (serial FINS), CV-series addresses, and routing through other networks beyond the network and node numbers set here.
- **Other memory areas**: index registers (IR), data registers (DR) and task flags (TK). Only CIO, W, H, A, D, T, C and EM are read.
- **Showing a STRING's text on a screen**: the text is read into the tag mapping, not into the tag engine (see [STRING tags](#string-tags-text-read-and-write)).

## Test without hardware

A connection with **Simulated** on (`"simulated": true`) contacts nothing: an in-process controller holds the values in memory, so you can build screens and mappings before the controller is connected. The FINS simulator `tools/fins-sim` answers FINS/UDP and FINS/TCP on a test machine.

## Related

- [Connections, lines and stations](/docs/eaxscada/explanation/connections-and-stations/)
- [Limit tag writes](/docs/eaxscada/how-to/limit-tag-writes/)
- [Driver channels, devices and tags](/docs/eaxscada/reference/generated/config/drivers/)
- [Connect to Mitsubishi Electric MELSEC iQ-R, iQ-F, Q and L controllers](/docs/eaxscada/how-to/connect-to-a-mitsubishi-mc-protocol-controller/)