# Connect to a Logix controller

> Read and write tags of a Rockwell / Allen-Bradley ControlLogix, CompactLogix or Micro800 over EtherNet/IP - what is supported and what is not (MicroLogix, SLC 500, PLC-5, implicit I/O; drives and other EtherNet/IP devices have their own connection kind), slot, route and the no-backplane Micro800 connection, External Access, tag addresses and the live tag browse.

Product: eaxScada · Type: How-to guide · Editions: Starter, Pro, Enterprise
Source: https://eaxware.com/docs/eaxscada/how-to/connect-to-a-logix-controller/
Status: migrated page, not yet verified against the current code.

eaxScada reads and writes the tags of Rockwell / Allen-Bradley Logix controllers (ControlLogix, CompactLogix) and of Micro800 controllers (Micro820/850/870), by name over EtherNet/IP (CIP, TCP port 44818). The protocol id in the configuration is `ETHERNET_IP`.

## What is supported

Supported:

- Rockwell / Allen-Bradley ControlLogix (1756): set the controller's slot in the chassis, or a route through other modules.
- Rockwell / Allen-Bradley CompactLogix (1769, 5370, 5380, 5069): slot 0.
- Rockwell / Allen-Bradley Micro800 (Micro820, Micro850, Micro870): choose **Micro800** as the controller. A Micro800 has **no chassis backplane**, so eaxScada connects with no route at all and the slot is not used. Its global variables are read by name.
- Tags by name: controller tags (`Tank_Level`), UDT members (`Tank101.Level`) and program tags (`Program:Main.Speed`).
- Types: BOOL, DINT (Int32), REAL (Float32). INT (Int16) and LREAL (Float64) are accepted but not yet verified on a controller.
- **Browse tags** lists the controller-scope tags read from the controller. Program tags are typed by address.
- GuardLogix: standard tags, as on ControlLogix and CompactLogix (not yet verified on a controller).
- Array elements (`Tag[3]`): accepted, not yet verified on a controller.

Not supported:

- MicroLogix, SLC 500 and PLC-5: they use the older PCCC protocol. Use the connection kind **Rockwell / Allen-Bradley MicroLogix, SLC 500, PLC-5 (PCCC)**, which reads their data table by address (`N7:0`, `F8:3`): see [Connect to a MicroLogix, SLC 500 or PLC-5](/docs/eaxscada/how-to/connect-to-a-micrologix-slc-or-plc-5/).
- Micro800 program-scope variables and system/global-system variables: only controller-global variables are read by name.
- Drives, remote I/O adapters and other EtherNet/IP devices: they are not Logix controllers. Use the connection kind **EtherNet/IP device (drives, I/O adapters)**, which reads them by class, instance and attribute: see [Connect to an EtherNet/IP device](/docs/eaxscada/how-to/connect-to-an-ethernet-ip-device/).
- Implicit (Class 1) I/O connections, and produced/consumed tags.
- STRING tags, and a whole UDT or array as one value.

The ControlLogix / CompactLogix lines are verified against eaxware's Logix controller simulator (connection with the slot route, a refused wrong slot, reads of controller, UDT member and program tags, BOOL, DINT and REAL, a write read back, a refused write, an unknown tag, the tag browse). The Micro800 support is verified against eaxware's Micro800 simulator (a session opened with an empty route, a refused backplane-slot route, reads of BOOL, DINT and REAL by name, a write read back, an unknown tag and the tag browse). Neither is yet verified against a controller in the test bench; the Micro800 path has not been run against real Micro820/850/870 hardware.

## Set up the controller

- Each tag you write needs **External Access** set to **Read/Write**. **Read Only** refuses writes; **None** hides the tag. On a Micro800 (Connected Components Workbench) this is the variable's read/write external access.
- TCP port 44818 must be open between eaxScada and the controller's Ethernet port or module.
- For a ControlLogix, note the slot of the controller (not of the Ethernet module) in the chassis. A Micro800 has no slot.

## Add the connection

1. **Drivers → Add connection**, and choose **Rockwell / Allen-Bradley Logix (ControlLogix, CompactLogix — EtherNet/IP)**.
2. **Controller**: CompactLogix (slot 0), ControlLogix (set the slot), or **Micro800 (Micro820/850/870 — no backplane)**. The "other EtherNet/IP device" entry cannot be created here: it points to the **EtherNet/IP device (drives, I/O adapters)** connection kind.
3. **IP address** of the controller or of the Ethernet module in its chassis.
4. **Controller slot** (ControlLogix / CompactLogix only). Leave **Route** empty: the route is then the backplane and that slot (`1,<slot>`). To reach a controller through other modules, enter the full route (for example `1,2,2,10.0.0.5,1,0`); a route replaces the slot. For a **Micro800** the slot is hidden and not used - eaxScada connects with no route; a route you enter here still overrides.
5. **UNS prefix** (optional): where this controller's tags go in the UNS. A Logix tag carries at most program and UDT structure, so the prefix supplies the site, area and line.
6. **Create connection**, then **Test connection**. A success means the controller accepted a CIP session (RegisterSession and Forward Open) at that slot or route, not only that port 44818 is open.
7. **Browse tags** opens the tag browser on the new connection.

**Diagram: The route to a Logix controller** (network topology)

eaxScada opens EtherNet/IP on TCP port 44818 to the IP address of the controller or of the Ethernet module in its chassis. In an Allen-Bradley ControlLogix chassis the route goes over the backplane to the controller's slot (1,\<slot>). A CompactLogix takes slot 0 (1,0). A Micro800 has no backplane, so there is no route. A full route through other modules, entered in Route, replaces the slot.

**Parts**

- **eaxScada** (product): EtherNet/IP, TCP port 44818
- **Ethernet module** (device or controller, inside Allen-Bradley ControlLogix chassis): its IP address
- **Backplane** (bus or line, inside Allen-Bradley ControlLogix chassis)
- **Controller** (device or controller, inside Allen-Bradley ControlLogix chassis): in its slot
- **CompactLogix** (device or controller): slot 0
- **Micro800** (device or controller): Micro820, 850, 870: no backplane

**Connections**

- **eaxScada → Ethernet module** (relation): route 1,\<slot>
- **Ethernet module → Backplane** (relation)
- **Backplane → Controller** (relation)
- **eaxScada → CompactLogix** (relation): route 1,0
- **eaxScada → Micro800** (relation): no route

The IP address reaches the chassis; the slot, or a full route, reaches the controller in it.

[Image: Add connection with a ControlLogix or CompactLogix chosen: controller, IP address, slot, port, route and the supported controllers and requirements.]
[Image: Add connection with a ControlLogix or CompactLogix chosen: controller, IP address, slot, port, route and the supported controllers and requirements.]

## Reads, writes and errors

A tag that does not exist, or a write the controller refuses (External Access Read Only), is reported with the reason, the controller's CIP status where it gives one; a failed read makes the tag's quality BAD and never shows an invented value.

## The connection afterwards

The **Connection** tab holds the controller, address, slot and route, with the same requirements panel; **Polling & UNS** the scan rate and the UNS prefix; **Tag Mappings** the mapped tags.

Connections saved before this version keep their route: one saved with the route `1,0` still reaches slot 0, whatever its slot field says. Clear the route to use the slot.