# Connect serial and CAN devices

> Poll Modbus RTU and ASCII devices on RS-485/RS-232 lines (directly or through a serial device server) and CANopen or raw CAN devices, with multi-drop addressing, line timing, quality and link diagnostics, and Modbus block reads on every Modbus channel.

Product: eaxScada · Type: How-to guide · Editions: Starter, Pro, Enterprise
Source: https://eaxware.com/docs/eaxscada/how-to/connect-serial-and-can-devices/
Status: migrated page, not yet verified against the current code.

eaxScada polls field devices on serial lines and CAN buses as driver channels, like any other protocol: a **channel** is one line or bus, each **device** on it is one unit or node, and **tags** map device addresses to UNS paths. Values carry quality (GOOD, UNCERTAIN, BAD) and every write goes through the same write policy as the rest of the system (confirmation, e-signature, read-only tags, standby node).

| Protocol | Channel protocol | Medium |
|---|---|---|
| Modbus RTU | `MODBUS_RTU` | RS-485 / RS-232 serial port, or a serial device server (`tcp://host:port`) |
| Modbus ASCII | `MODBUS_ASCII` | as RTU |
| Modbus RTU over TCP | `MODBUS_RTU_TCP` | serial device server or gateway in transparent mode (RTU frames with CRC on a TCP socket) |
| CANopen | `CANOPEN` | SocketCAN interface (Linux), or an SLCAN adapter on a serial port or device server |
| Raw CAN | `CAN_RAW` | as CANopen |

**Diagram: Serial lines and CAN buses as channels** (network topology)

Each channel is one line or bus. eaxScada reaches an RS-485 line through a serial port or a serial device server (Modbus RTU or ASCII), or through a gateway in transparent mode (Modbus RTU over TCP); each unit on the line is a station with its unit id, 1 to 247. It reaches a CAN bus through a SocketCAN interface or an SLCAN adapter (CANopen or raw CAN); each node is a station with its node id, 1 to 127.

**Parts**

- **eaxScada** (product): a channel per line or bus
- **Serial port** (service or process): COM5, /dev/ttyUSB0, or a device server tcp://host:port
- **Transparent gateway** (service or process): its address and TCP port
- **CAN interface** (service or process): SocketCAN can0, or slcan:COM7, slcan:tcp://host:port
- **RS-485 line** (bus or line)
- **Stations** (device or controller): unit id 1-247
- **CAN bus** (bus or line)
- **Stations** (device or controller): node id 1-127

**Connections**

- **eaxScada → Serial port** (relation): MODBUS_RTU, MODBUS_ASCII
- **eaxScada → Transparent gateway** (relation): RTU_TCP. Channel protocol MODBUS_RTU_TCP: RTU frames with their CRC on a TCP socket.
- **eaxScada → CAN interface** (relation): CANOPEN, CAN_RAW
- **Serial port → RS-485 line** (relation)
- **Transparent gateway → RS-485 line** (relation)
- **RS-485 line → Stations** (relation)
- **CAN interface → CAN bus** (relation)
- **CAN bus → Stations** (relation)

One channel per line or bus, one station per unit or node: the station id is the address on that line.

The settings of each channel are listed in [Driver channels, devices and tags](/docs/eaxscada/reference/generated/config/drivers/). For a Rockwell / Allen-Bradley MicroLogix, SLC 500 or PLC-5 on its serial port (DF1 full-duplex), see [Connect a MicroLogix, SLC 500 or PLC-5 on a serial port (DF1)](/docs/eaxscada/how-to/connect-a-df1-serial-controller/).

## Modbus on a serial line

### 1. Create the channel

In the Studio, **Drivers → Add connection**, and choose **Modbus RTU serial line** (or **Modbus ASCII serial line**): this creates the line. Then set:

- **Serial Port**: `COM5` on Windows, `/dev/ttyUSB0` on Linux. A serial device server in raw TCP mode is entered as `tcp://192.168.1.200:4001`.
- **Baud Rate** and **Data / Parity / Stop**: as configured on every device of the line. RTU is normally 8-E-1 (8-N-2 when the devices use no parity); ASCII is normally 7-E-1. One port runs at one setting: a second channel on the same port with different settings is refused.
- **Byte & Word Order**: how the devices lay out 32- and 64-bit values over registers (ABCD big-endian, CDAB word-swapped, BADC byte-swapped, DCBA little-endian). Single 16-bit registers are always big-endian.
- **Request Timeout** and **Retries** (channel timing section): the time a request waits for an answer, and how many times a read is repeated after a timeout or a checksum error.

### 2. Add one station per unit

A line is a whole RS-485 segment. **Drivers → Add station**, choose the line, and enter the device's **unit id** (1-247); repeat for each unit on the line. A unit id already on the line is refused. The line's **Default Unit ID** is used only by a station without a unit id (one from an older configuration). See [Connections, lines and stations](/docs/eaxscada/explanation/connections-and-stations/).

### 3. Map tags

Addresses are the same as for Modbus TCP: `HR:<offset>`, `IR:<offset>`, `COIL:<offset>`, `DI:<offset>` (protocol offsets 0-65535), or a classic reference such as `40001`. The tag's data type sets how many registers are read: Int16, UInt16 and Bool take one register; Int32, UInt32 and Float32 two; Int64, UInt64 and Float64 four.

A tag's **Access** is a property of the field point, enforced by the server for every protocol: **Read Only** (`RO`) refuses every write before anything is sent to the device, whoever asks (an administrator, a NATS command, an approved AI setpoint, a script or faceplate through the HMI). The write is answered `409 Conflict` with the reason (`tag <path> is read-only`) and the refusal is recorded in the audit trail. **Read / Write** (`RW`, also a mapping saved without an access) and **Write Only** (`WO`) are written. Tags that are not mapped to a device (internal tags) are not affected.

Modbus carries no names, so a device is browsed from an imported register map (CSV), exactly as for Modbus TCP. The browse reads every row back from the device and shows which addresses answer.

### Line timing

- Frames are separated by the inter-frame silence: 3.5 character times, fixed at 1750 µs above 19200 baud. **Inter-frame Silence** overrides it.
- **Turnaround** adds quiet time after every transaction, for slow devices and radio modems.
- One transaction is on the line at a time. Several channels on the same port share it safely.
- **RS-485 direction by OS** asks Linux to drive RTS for the transmitter (with **RTS lead** and **RTS lag**). Most USB adapters switch direction automatically and need nothing; on Windows the option is refused.

### Faults and quality

| Condition | Tag quality | Notes |
|---|---|---|
| Valid answer | GOOD | |
| Timeout, CRC/LRC error, wrong unit or function | BAD | the reason is shown on the tag and the channel |
| Exception from the device (e.g. illegal data address) | BAD | not retried: the device answered |
| Unit silent for 3 consecutive timeouts | BAD | the unit is polled once every 5 s until it answers again, so a dead unit does not slow the others |
| Port missing, in use or unplugged | BAD | the port is reopened every 2 s |

Writes are sent **once**. A write that gets no answer is reported as *not confirmed*: the device may or may not have applied it, and repeating it automatically could apply it twice. Writes to unit 0 (broadcast: every unit executes it, none answers) are refused unless **Allow broadcast writes** is set on the channel. A value that does not fit the register type (70000 into a UInt16, 1.5 into an integer) is refused rather than truncated. A write value travels as a 64-bit float, so an Int64 or UInt64 write is limited to ±9007199254740992 (2^53), the range in which every integer is exact; a larger value is refused rather than rounded.

## Modbus RTU over TCP

Use `MODBUS_RTU_TCP` when a serial device server or gateway forwards the RTU frames unchanged over TCP (often called transparent or raw TCP mode). Enter its address and TCP port. If the gateway converts to Modbus TCP (MBAP header), choose **Modbus TCP gateway (several devices behind one IP address)** instead and add one station per unit id (see [Connections, lines and stations](/docs/eaxscada/explanation/connections-and-stations/#a-modbus-tcp-gateway-several-devices-behind-one-ip-address)).

## Modbus block reads

Every Modbus channel reads in blocks when its device has block reads on (**Enable Block Read Optimization** on the device, `block_read_optimization`; on for a device created in the Studio): Modbus TCP, the Modbus TCP gateway, Modbus RTU, Modbus ASCII and Modbus RTU over TCP. Within a poll, tags of one unit id and one area (coils, discrete inputs, holding registers, input registers) whose addresses are close are read with one request. Each tag takes its own registers or bits from that answer, at its own address.

- **Size.** A block holds at most 125 registers or 2,000 bits (the protocol's limit), and at most the device's **Max Block Read Size** (in registers; 16 bits per register for coils and discrete inputs). A device created in the Studio has 64.
- **Gaps.** A block spans at most 16 unmapped registers, or 64 unmapped bits, between two tags. To change it, set **Block gap (registers)** (0 to 125, empty: 16) and **Block gap (bits)** (0 to 2000, empty: 64) on the connection form in the Studio (Modbus TCP, the gateway, RTU, ASCII and RTU over TCP), or `block_gap_registers` and `block_gap_bits` in the channel's settings. 0: only tags next to each other are read together. A value outside its range, or not a whole number, is refused on save: "Not saved: Block gap (registers) is a whole number from 0 to 125, or empty for the default (16)."
- **A refused block.** When the device answers a block with exception 01 (illegal function), 02 (illegal data address) or 03 (illegal data value), its tags are read again one by one in the same poll, so one bad address makes only its own tag BAD. The refused address is remembered: it is read alone from then on, and no block spans it.
- **Other failures.** A timeout, a lost connection or another exception (04 device failure, 0B gateway target failed to respond) makes every tag of the block BAD with that error.
- **Fresh values only.** A block's answer serves only the poll that read it, and only within the request timeout. A later poll reads again. A write ends the poll's blocks: the reads after it in that poll are made one by one.
- **Inter-request delay.** The channel's delay between requests (`inter_request_delay_ms`) applies only after a read that sent a request, not after a tag served from a block already read.

A tag alone in its block, and every tag of a device with block reads off are read with their own request, as before. Writes are never grouped.

## CANopen

### 1. Connect the bus

- **Linux**: configure the interface with the system, then name it in the channel: `ip link set can0 type can bitrate 500000 && ip link set can0 up`, interface `can0`.
- **Any system, including Windows**: a USB CAN adapter that speaks the SLCAN protocol appears as a serial port. Enter `slcan:COM7` (or `slcan:/dev/ttyACM0`) and the bit rate; eaxScada sets the rate and opens the adapter. An SLCAN adapter behind a serial device server is `slcan:tcp://host:port`.
- A SocketCAN interface name on Windows is refused with a message pointing to SLCAN.

### 2. Add one station per node

**Drivers → Add station**, choose the bus, and enter the device's CANopen **node id** (1-127).

### 3. Map tags

| Address | Reads | Writes |
|---|---|---|
| `SDO:0x6064:0` | object 6064h sub 0 by SDO (expedited or segmented) | SDO download of the value |
| `TPDO1:2` | bytes 2.. of the node's transmit PDO 1 (COB-ID 180h + node) | refused |
| `TPDO1:0.3` | bit 3 of byte 0 (Bool) | refused |
| `PDO:0x1A5:0` | a PDO by its COB-ID | refused |
| `NMT` | NMT state: 0 boot-up, 4 stopped, 5 operational, 127 pre-operational | NMT command: 1 start, 2 stop, 128 pre-operational, 129 reset node, 130 reset communication |
| `EMCY` | last emergency error code (0 = none) | refused |

The tag's data type sets the size and encoding (CANopen is little-endian): Bool, Int8, UInt8, Int16, UInt16, Int32, UInt32, Int64, UInt64, Float32, Float64.

PDO values are read-only in eaxScada: process outputs carried by RPDOs belong to a controller with a deterministic cycle. Write parameters by SDO.

### Browse and EDS import

Browsing a node reads its identity and its transmit PDO mapping from the node itself (objects 1800h-1803h and 1A00h-1A03h), and lists each mapped object as a ready-made PDO tag. Import the node's **EDS** file as the device's register map to see object names and types, and to list its objects as SDO tags with their current values.

### Liveness and quality

- **Heartbeat Timeout**: a node whose heartbeat is older than this is lost, and every tag of the node is BAD until it is heard again. Set it to about three times the node's heartbeat period. **Node Guarding** polls nodes that produce no heartbeat.
- **PDO / Frame Stale**: a PDO value older than this is UNCERTAIN (last value kept). A PDO value is also UNCERTAIN while its node is not operational.
- **SDO Poll Interval**: an SDO tag is read at most this often; SDO is a request/response service and polling it at the scan rate loads the bus.
- SDO aborts are shown with their meaning (for example *object does not exist in the object dictionary*).

### Safety defaults

- Nodes are **not** started automatically. Enable **Start nodes (NMT) when first polled** only when this channel is the network manager: an operational node acts on the RPDOs other devices send it.
- The channel produces **no SYNC** unless **SYNC Period** is set; a bus must have only one SYNC producer.
- NMT commands to node 0 (every node) are refused unless **Allow NMT broadcast** is set.
- An SDO write to a node that is lost is refused.

## Raw CAN frames

`CAN_RAW` decodes values from any CAN frame without taking part in CANopen. Addresses are `FRAME:<id>:<byte>[.<bit>]`, with the id in hex; ids above 7FFh are extended 29-bit ids. Browsing lists the ids heard on the bus and their bytes. Values are read-only.

## Link diagnostics

Each serial and CAN channel shows **Link diagnostics** under its settings in the Studio, and the same figures appear in the driver diagnostics (`link_stats`): frames sent and received, CRC/LRC errors, timeouts, exceptions, retries, units that stopped answering, and for CAN the SDO requests and aborts, heartbeat losses, emergencies and the state of every node. A count of checksum errors or timeouts that keeps rising while tags stay GOOD is the early sign of a marginal line: termination, biasing, grounding or one device at the wrong baud rate.

## Test without hardware

- **Modbus**: point a `MODBUS_RTU_TCP` channel, or a `MODBUS_RTU` channel with port `tcp://host:port`, at a Modbus RTU simulator listening on TCP.
- **CANopen**: on Linux, a virtual CAN interface behaves like a real bus: `ip link add dev vcan0 type vcan && ip link set vcan0 up`, interface `vcan0`.
- Any channel can be set to simulated mode (`"simulated": true` in its settings): no port or bus is opened, values are generated, and the channel, its devices and its tags are marked SIMULATED everywhere. The server marks each value simulated: SIM on screens and trends, simulated history samples and alarm events. An interlock that reads one stays active unless it is **Allowed in commissioning**, a limit tag on one refuses the write, and the plant e-stop signal on one reads as unknown (fail closed). Switching the channel to or from simulated restarts it; its next reading carries the new mark. See [Accept or refuse simulated PLCs](/docs/eaxscada/how-to/accept-simulated-plcs/#on-commissioning-only-accepted-and-marked).