# Connect MQTT and Sparkplug B inputs (network I/O, not for safety functions)

> Map MQTT JSON values and Sparkplug B metrics onto the PLC's %I inputs, with a quality signal the program can see, broker security, the safety-target refusals, and the Sparkplug B and JSON rules. Network I/O, not for safety functions. eaxPLC Standard and Performance.

Product: eaxPLC · Type: How-to guide · Editions: Pro
Source: https://eaxware.com/docs/eaxplc/how-to/connect-mqtt-sparkplug-inputs/
Verified against commit f67e38d.

**Network I/O, not for safety functions.** An MQTT input brings values that
other clients publish on a broker into the PLC's `%I` area. The program reads
them like any input, together with a quality signal that tells it when a
value is not Good. An MQTT input never drives a safety target, never drives
an output and never sends a command.

## Goal

A fieldbus bus of type **MQTT broker** (`"type": "mqtt"`) connects the PLC to
one broker. Each of its **sources** is one Sparkplug B edge node (or one of
its devices), or one JSON topic root. Each **entry** of a source maps one
Sparkplug B metric or one JSON topic to a `%I` address, and must also have a
quality output.

**Diagram: An MQTT input, from the publisher to the program** (data flow)

Sparkplug B edge nodes and JSON publishers publish to one MQTT broker. The MQTT input bus of the PLC holds one connection to that broker and keeps, for each entry, the latest value with its quality code and time. The scan thread copies each entry into the process image at the start of a cycle: the value at its %I address and the quality outputs beside it. The program reads both. The storage an entry drives is never a safety target, and no outside write reaches it.

**Parts**

- **Publishers** (external system): Sparkplug B edge nodes, JSON publishers
- **MQTT broker** (external system): one per bus
- **MQTT input bus** (service or process): sources and entries, off the scan thread
- **Program** (service or process): reads the value and its quality
- **Process image** (data store): the %I value; quality bit, status, timestamp, age
- **Scan thread** (service or process): reads the inputs
- **Downstream** (external system): NATS UNS, MQTT publisher, OPC UA
- **Safety target** (data store): storage of a variable on the safety list
- **Outside write** (external system): on any path

**Connections**

- **Publishers → MQTT broker** (data or telemetry): publish
- **MQTT broker → MQTT input bus** (data or telemetry): topics of the sources. Over TLS. A plaintext connection to a broker on another computer is refused unless it is allowed with a reason.
- **MQTT input bus → Scan thread** (data or telemetry): latest value, code and time. Per entry. A message the rules refuse (a retained Sparkplug B message, a source that says it is simulated, a message over a limit) places no value.
- **Scan thread → Process image** (data or telemetry): each cycle. Before the program runs. A Good value with no update within its maximum age turns Stale here, even when the network side hangs.
- **Process image → Program** (data or telemetry): inputs
- **Process image → Downstream** (data or telemetry): the worse quality. A variable wholly inside an entry's value is published, and read over OPC UA, with the worse of the PLC's quality and the entry's.
- **Process image → Safety target** (refusal): never. A configuration whose entries cover a safety target is refused (SAFETY_TARGET), and so is a deploy, a rollback or an online test that puts a safety target onto storage an entry drives (MQTT_INPUT_SAFETY_TARGET).
- **Outside write → Process image** (refusal): IO_INPUT_DRIVEN. A write through the runtime API, UNS and MQTT commands, OPC UA or Modbus TCP onto a byte or bit an entry writes is refused.

The network side never touches PLC memory: the scan copies the inputs, and decides there when a value is stale.

| Edition | MQTT inputs |
|---|---|
| eaxPLC Free | No. A configuration with an enabled MQTT bus is refused, and a saved one is not started. |
| eaxPLC Standard | Yes. An MQTT bus does not count as the edition's one fieldbus master. |
| eaxPLC Performance | Yes |

MQTT inputs are network I/O, not for safety functions, in every edition. A
bus that was approved keeps starting after the licence lapses, as the other
buses do.

## Before you start

- **A broker you control**, reachable from the PLC. Use `ssl://` (or
  `tls://`, `mqtts://`) or `wss://`. An unencrypted broker on another
  computer is refused unless you allow it with a reason (see
  [Broker security](#broker-security)).
- **Access rules on the broker.** They are the trust boundary: any client
  the broker lets publish on the input topics drives these PLC inputs.
- **Free `%I` addresses** for each value and its quality outputs.
- You are signed in as an engineer: applying a fieldbus configuration needs
  your e-signature. Test connection and Browse also need the engineer role.
- eaxPLC Standard or Performance.

## Add the broker

1. Open **Fieldbus** and click **+ MQTT**.
2. Set the broker connection:
   - **Brokers**: one or more URLs, tried in order: `ssl://`, `tls://`,
     `mqtts://`, `wss://` (encrypted), or `tcp://`, `mqtt://`, `ws://`
     (plaintext). No user name or password in a URL: use the fields below.
   - **Client ID**: empty uses `eaxPLC-<plc id>-in`, cut to 23 characters
     with a hash suffix when the PLC id is long. Your own ID has at most 128
     characters and no `/`, `+` or `#`. It must not be the ID of this PLC's
     own MQTT publisher: a broker drops the older session of a duplicate ID.
   - **User name**, **Password**, **CA certificates (PEM)**, **Client
     certificate (PEM)** and **Client key**.
   - **Keepalive (s)**: 2 to 60, default 5. A lost broker is noticed within
     about 1.5 × the keepalive.
   - **Messages/s (whole bus)**, **Max payload (bytes)** and **Max metrics
     per payload**: see [Limits](#limits).
3. Click **Test connection**. The PLC connects once with these settings and
   the stored secrets, then disconnects. Nothing is subscribed or published.
   The test uses its own client ID, so it never drops the running input
   connection.

The PLC connects with a clean session, subscribes at QoS 1, and subscribes
only to the exact topics its entries need (see [Broker security](#broker-security)).

## Add a source

Select the bus and add a source. Its **Source** is `sparkplug` or `json`.

**Sparkplug B source:**

- **Group ID** and **Edge node ID** (required), and **Device ID** for one
  device of the node. No `/`, `+` or `#`. One Sparkplug source per node or
  device on a bus.
- **Request rebirth**: off by default. See [Sparkplug B rules](#sparkplug-b-rules).

**JSON source:**

- **Topic root**: exact topic levels (no `+` or `#`, no empty level). A
  root under `spBv1.0` is refused: use a Sparkplug source.
- **Timestamp unit**: `ns`, `ms` or `s`, required. The unit of a payload's
  `timestamp` is never guessed. **eaxPLC publisher** marks a source that is
  another eaxPLC's MQTT publisher, which stamps in `ns`.
- **Online topic** (optional): an exact topic saying whether the source is
  alive.
- **Max age (ms)** or an **Online topic** is required. See
  [Quality](#quality).

**Both kinds:**

- **Status bit (%IX)** (optional): TRUE while the source is alive.
- **Max age (ms)** (0 to 86 400 000), **Max source age (ms)** (0 to
  86 400 000), **On not Good** (`hold`, `substitute`, `zero`) and
  **Messages/s (this source)**: defaults for the entries.

Click **Browse** to see what the source sends: the PLC listens for up to 9 s
for the node's NBIRTH and DBIRTH messages (Sparkplug B), or for the topics
under the root (JSON). It lists each metric or topic with a suggested PLC
type, and you pick the entries. Browse never sends anything, not even a
rebirth request.

## Map the entries

Each entry has:

- **Metric** (Sparkplug B) or **Topic** below the topic root (JSON).
- **Data type** and **PLC address** in `%I` only, of the type's size:
  `BOOL` on `%IX`; `SINT`, `USINT`, `BYTE` on `%IB`; `INT`, `UINT`, `WORD`
  on `%IW`; `DINT`, `UDINT`, `DWORD`, `REAL` on `%ID`; `LREAL`, `LINT`,
  `ULINT`, `LWORD` on `%IL`. The 64-bit types exist for MQTT entries only.
  `STRING` is not an MQTT input yet. One value per entry.
- **A quality signal, required**: a **quality address** (`%IX`, TRUE only
  while the value is Good) on the entry, or the source's status bit.
  Without one the entry is refused: the program could not know that a value
  is not Good.
- Optional quality outputs: **status** (`%IB`, the quality code),
  **timestamp** (`%IL`, the source's timestamp in Unix ms) and **age**
  (`%ID`, ms since the last accepted update).
- **On not Good** and **Substitute** (a literal of the entry's type,
  required for `substitute`), and the entry's own **Max age (ms)**.

The entries are on the data grid with their live value, quality and age.
[Image: The Fieldbus view with the MQTT bus Plant broker and its Sparkplug B source Line 2 edge node: the broker access-rules warning, the source settings, and four entries on the data grid, each marked Bad (not connected) with a warning while the broker cannot be reached.]
[Image: The Fieldbus view with the MQTT bus Plant broker and its Sparkplug B source Line 2 edge node: the broker access-rules warning, the source settings, and four entries on the data grid, each marked Bad (not connected) with a warning while the broker cannot be reached.]

A Sparkplug B source whose broker cannot be reached: every entry reads code 8, Bad (not connected), and the program sees its quality bit FALSE.
Click **Validate**, then **Apply** with your e-signature. The e-signature's
meaning says how many PLC inputs the broker's publishers drive, and names
an allowed plaintext broker with its reason.

A change to a source or an entry of an MQTT bus restarts that bus's
connection (one connection serves all its sources); other buses keep
running. An Apply that changes MQTT secrets reconnects every MQTT bus.
See [Apply fieldbus changes without stopping the other
devices](/docs/eaxplc/how-to/apply-fieldbus-changes/).

Values are converted exactly or refused. An integer out of the target
type's range, a fraction into an integer type, NaN or infinity, or a `BOOL`
other than 0 or 1 is Bad (code 4) and is never copied: never wrapped, never
clamped. 64-bit integers arrive bit for bit. A `REAL` takes any finite value
within the 32-bit range, with the loss of precision that implies.

The metrics of one Sparkplug B payload, or one JSON message, reach the
program in the same scan. The scan never waits on the network.

## Safety: an MQTT input never drives a safety target

An MQTT entry's storage is its value and each of its quality outputs
(quality bit, status, timestamp, age), plus its source's status bit. This
storage never covers a safety target (the safety-target list in Project
Settings, or eaxScada's signed list). The PLC checks this at every step:

- **Configuration:** `PUT /api/fieldbus` refuses such a configuration with
  `422` and `"code": "SAFETY_TARGET"`, naming the entry and the target;
  **Validate** lists the same problem. Disabled sources count too. If the
  safety-target list cannot be read, every configuration with an MQTT entry
  is refused (fail closed).
- **Programs:** a deploy, a rollback, a project deploy or an online test
  whose program puts a safety target onto storage an MQTT entry drives is
  refused with `409 MQTT_INPUT_SAFETY_TARGET`. The running program stays.
  If the list cannot be checked, the change is refused the same way.
- **A local safety-target list** that names storage an MQTT entry drives is
  refused when saved: `409 MQTT_INPUT_SAFETY_TARGET`, nothing changed.
- **eaxScada's signed list** is always accepted. An MQTT bus whose entries
  then cover one of its targets is stopped: its entries show code 8 and
  their substitute, and the fieldbus load error and a notice say why.
- **A safety-target list that becomes unreadable** stops every MQTT bus
  with entries (fail closed).
- **At start-up**, a saved MQTT bus that conflicts with the loaded program
  (for example a file edited by hand) is not started, with a notice.
- **Outside writes** onto any byte or bit an MQTT entry writes are refused
  with `IO_INPUT_DRIVEN` on every outside path (`/api/write`, UNS and MQTT
  commands, OPC UA, Modbus TCP). See
  [Constants, outside writes and forces](/docs/eaxplc/reference/constants-writes-and-forces/#refusals-per-path).

Further limits:

- **A simulated PLC never opens an MQTT input connection.** Its entries keep
  code 8 and their substitute; Test connection and Browse answer `409`.
- **The AI co-pilot cannot configure, test or browse MQTT inputs**, whatever
  its level: the route guard refuses it, and the handlers refuse it again
  (`403`).
- **A source that says it is simulated is refused** (code 4): a Sparkplug B
  birth with the metric `Properties/Simulated` TRUE or a metric property
  `simulated` TRUE, or a JSON payload with `"simulated": true`. A source
  that never marks itself as simulated is treated as real: the PLC cannot
  tell otherwise.

## Broker security

**Plaintext.** A `tcp://`, `mqtt://` or `ws://` URL to anything other than
this computer (`localhost` or a loopback address) is refused, because anyone
on the network path could inject PLC inputs. To allow it, set **Allow an
unencrypted broker on the network** with a reason of at least 8 characters;
the e-signature of the change carries the reason.

**Secrets are write-only.** The password and the client key are stored in
`data/fieldbus/secrets.json`, restricted to the PLC's account. They are never
in `fieldbus.json`, the export, `GET /api/fieldbus` (it shows **Set** or
**Not set**), the e-signature meaning or the audit record, which says
`[secrets changed]`. A client certificate needs its key and they must
match; a key without a certificate is refused. **Clear secrets** removes
them at the next Apply.

**Access rules.** The broker decides who may publish on the input topics.
Give the PLC's input connection its own account that may only subscribe, and
let only the real source publish on its topics. The PLC subscribes to:

- Sparkplug B: `spBv1.0/<group>/NBIRTH/<node>`, `NDATA` and `NDEATH`, and
  `spBv1.0/<group>/DBIRTH/<node>/+`, `DDATA` and `DDEATH`. Never a command
  topic, STATE or `#`;
- JSON: each entry's exact topic and the online topic;
- Browse: the node's NBIRTH and DBIRTH topics, or `<topic root>/#`.

With **Request rebirth** on, the PLC also publishes on
`spBv1.0/<group>/NCMD/<node>`. A generic example, to write in your broker's
own access-rule syntax:

```text
# PLC input connection (account plc-line1-in): subscribe only
plc-line1-in   subscribe   spBv1.0/Plant1/NBIRTH/Edge7
plc-line1-in   subscribe   spBv1.0/Plant1/NDATA/Edge7
plc-line1-in   subscribe   spBv1.0/Plant1/NDEATH/Edge7
plc-line1-in   subscribe   spBv1.0/Plant1/DBIRTH/Edge7/+
plc-line1-in   subscribe   spBv1.0/Plant1/DDATA/Edge7/+
plc-line1-in   subscribe   spBv1.0/Plant1/DDEATH/Edge7/+
plc-line1-in   subscribe   site/line1/meters/#
# only with Request rebirth on
plc-line1-in   publish     spBv1.0/Plant1/NCMD/Edge7

# the edge node (account edge7): the only publisher of its topics
edge7          publish     spBv1.0/Plant1/+/Edge7
edge7          publish     spBv1.0/Plant1/+/Edge7/+
edge7          subscribe   spBv1.0/Plant1/NCMD/Edge7

# the meter gateway (account meters-gw): the only publisher under its root
meters-gw      publish     site/line1/meters/#

# every other account: no publish on spBv1.0/Plant1/+/Edge7,
# spBv1.0/Plant1/+/Edge7/+ or site/line1/meters/#
```

**Loop guard.** A source that is this PLC's own MQTT publisher is refused:
a Sparkplug source with the publisher's group and edge node, or a JSON root
that overlaps the publisher's topic root. The PLC would read its own values
back as inputs.

## Quality

Every entry has a quality code; the program sees it through the quality
bit, the status byte, the timestamp and the age. The codes, labels and
outputs are listed in [MQTT input quality and limits](/docs/eaxplc/reference/mqtt-input-quality/).

- **Uncertain is never Good.** The quality bit is TRUE only for a Good
  code; Uncertain (64 to 127) and Stale (68) are FALSE.
- **Staleness is decided in the scan.** A Good value with no update within
  **Max age (ms)** turns Stale (68) in the scan itself, so the inputs go
  stale on time even if the network side hangs. Sparkplug sources default
  to 0 (off): their births and deaths say when a node is gone.
- **A JSON source needs a quality signal of its own**: **Max age (ms)** on
  the source (or on every entry), or an **Online topic**. A publisher that
  only sends changes never proves it is alive otherwise.
- **On not Good** the program sees the last value (`hold`, the default), the
  substitute (`substitute`) or 0 (`zero`). Before the first value, `hold`
  shows the substitute, or 0 without one, with code 8.

**Downstream.** A variable wholly inside an MQTT entry's value is published
by the NATS UNS and by the MQTT publisher (JSON `quality`, Sparkplug B
`Quality` property) with the worse of the PLC's quality and the entry's, and
is republished when only the entry's quality changes. The OPC UA server
does the same: such a variable is read with the worse of the two as its
status (`Good`, `UncertainLastUsableValue` for Stale, `Uncertain`, or a Bad
status), and its subscriptions are notified when only the entry's quality
changes. Variables no MQTT entry drives are unchanged. The status mapping is
in [MQTT input quality and limits](/docs/eaxplc/reference/mqtt-input-quality/#downstream-quality-uns-mqtt-publisher-opc-ua).

**Read-only to clients.** A variable on storage an MQTT entry drives is
listed read-only in `GET /api/registry` (`"writable": false`) and in its OPC
UA access level, and a write onto it is refused (`IO_INPUT_DRIVEN`).

## Sparkplug B rules

**Diagram: A Sparkplug B session: births, data, a sequence gap and a death** (sequence)

The edge node publishes to the MQTT broker and the PLC receives what it subscribed to. A session starts with the node's NBIRTH and each device's DBIRTH; only then are values placed. Data messages carry a sequence number. A gap in it makes the node's values Uncertain until the next NBIRTH, and the PLC may ask the node for one. A death turns the entries to code 24, comm failure.

**Participants**

- **eaxPLC** (product)
- **MQTT broker** (external system)
- **Edge node** (external system)

**Steps, in order**

1. **eaxPLC → MQTT broker** (data or telemetry): Subscribes. births, data and deaths of each source
2. The session starts:
   1. **Edge node → MQTT broker** (data or telemetry): NBIRTH, then a DBIRTH per device. metric names and aliases, bdSeq
   2. **MQTT broker → eaxPLC** (data or telemetry): NBIRTH, DBIRTH
   3. **eaxPLC**: Places the values: a device waits for its DBIRTH; a metric no birth names: code 8
   4. **Edge node → MQTT broker** (data or telemetry): NDATA, DDATA. each with the next seq
   5. **MQTT broker → eaxPLC** (data or telemetry): NDATA, DDATA. values Good
3. A gap or a repeat in seq:
   1. **MQTT broker → eaxPLC** (data or telemetry): A message with the wrong seq
   2. **eaxPLC**: Node and devices: Uncertain: until the next NBIRTH
   3. **eaxPLC → MQTT broker** (data or telemetry): NCMD Node Control/Rebirth. only with Request rebirth, once per 30 s
   4. **MQTT broker → Edge node** (data or telemetry): NCMD
   5. **Edge node → MQTT broker** (data or telemetry): NBIRTH. a new session: the values are placed again
4. The node or a device is gone:
   1. **MQTT broker → eaxPLC** (data or telemetry): NDEATH or DDEATH. ignored only when its bdSeq is an old session's
   2. **eaxPLC**: Entries: code 24, comm failure: NDEATH: the node and its devices; DDEATH: the device

No value is placed before a birth, and nothing stays Good after a gap or a death.

- **Births:** the aliases come from the node's NBIRTH and the device's
  DBIRTH. No value is placed before a birth: until then the entries show
  code 8. A device waits for its DBIRTH after each NBIRTH. A metric the last
  birth does not name stays code 8.
- **Deaths:** NDEATH turns the node's and its devices' entries to code 24
  (comm failure); DDEATH does it for the device. A death is ignored only
  when the birth and the death both carry a `bdSeq` and they differ (a late
  death of an old session). A birth without `bdSeq` takes any death, and is
  counted and shown as a **No bdSeq** warning.
- **Sequence:** a gap or a repeat in `seq` makes the values of the node and
  its devices Uncertain until the next NBIRTH. A message dropped by a limit
  still advances the sequence.
- **Rebirth request** (opt-in, **Request rebirth**): after a sequence gap,
  data before a birth, a DBIRTH before the NBIRTH or an unknown alias, the
  PLC sends the node `Node Control/Rebirth` on NCMD, at most once per 30 s
  per node, and logs it.
- **Ignored:** retained Sparkplug messages (the specification never retains
  them, so they come from an old session) and historical metrics.
- **Timestamps:** the metric's timestamp, else the payload's, else the
  receive time. A timestamp more than 5 s in the future is accepted as
  Uncertain (clock skew).

## JSON rules

- **Payload:** a bare value (a number, `true` or `false`, or a numeric
  string), or an object `{"value": ..., "quality": n, "timestamp": t,
  "simulated": b}` where only `value` is required. `null`, an object or an
  array as the value is refused (code 4).
- **`quality`** is an OPC quality code: missing means Good; one that is not
  an integer is Uncertain.
- **`timestamp`** is read in the source's **Timestamp unit**; without one,
  the receive time is the timestamp.
- **Retained values:** a retained message is the current state when the PLC
  connects, but not proof that the source is alive. A Good retained value is
  Uncertain until a live update, unless its own timestamp is within **Max
  source age (ms)**.
- **Online topic:** `true` or `1` marks the source alive; `false` or `0`
  turns every entry of the source to code 24.
- **Max source age (ms)**: an update whose own timestamp is already older
  than this on arrival is Stale (68), history only. 0 turns it off.

## Limits

- **Rates:** 1000 messages/s per source and 10 000 per bus by default. The
  source's limit is checked first, so a flooding source only spends its own
  share of the bus. Messages over a limit are dropped and counted.
  Sparkplug B BIRTH and DEATH messages are never dropped for rate.
- **Size:** 256 KiB per payload and 10 000 metrics per Sparkplug B payload
  by default. A larger message is dropped and counted, whatever its type;
  an NBIRTH dropped this way leaves the node without a birth.
- **Browse** listens up to 9 s, connection included.

The exact ranges are in [MQTT input quality and limits](/docs/eaxplc/reference/mqtt-input-quality/#limits),
and every field is in the [fieldbus configuration reference](/docs/eaxplc/reference/generated/config/fieldbus/).

## Troubleshooting

| What you see | Meaning | What to do |
|---|---|---|
| `... is not encrypted and not on this computer` | A plaintext broker URL to another computer. | Use `ssl://` or `wss://`, or allow plaintext with a reason. |
| `needs a quality signal` | The entry has no quality address and its source no status bit. | Add a quality address (`%IX`) or the source's status bit. |
| `a JSON source needs max_age_ms or online_topic` | A JSON source with neither. | Set **Max age (ms)** or an **Online topic**. |
| `SAFETY_TARGET: ... writes the storage of the safety target ...` | An entry covers a safety target. | Move the entry, or the variable, off that storage. |
| `MQTT_INPUT_SAFETY_TARGET` on a deploy | The new program puts a safety target onto MQTT-driven storage. | Move the variable off that address, or remove the MQTT entry. |
| Entry code 8, `the birth does not name this metric` | The metric is not in the last NBIRTH or DBIRTH. | Check the metric name with **Browse**. |
| Entry code 4 | The value does not convert exactly, the payload is malformed, or the source says it is simulated. | Check the entry's type against the source's, and the payload. |
| **No bdSeq** warning | The node's NBIRTH carries no `bdSeq`. | Fix the edge node; until then every NDEATH is taken as the current session's. |

## See also

- [MQTT input quality and limits](/docs/eaxplc/reference/mqtt-input-quality/)
- [Publish to an MQTT broker](/docs/eaxplc/how-to/publish-to-an-mqtt-broker/)
- [Constants, outside writes and forces](/docs/eaxplc/reference/constants-writes-and-forces/)
- [Runtime HTTP API](/docs/eaxplc/reference/generated/http-api-runtime/)