# Data model: global variables, data types and external access

> What global variable lists, data types (STRUCT, UNION, enumeration, subrange, alias type), aliases, FUNCTIONs and VAR_IN_OUT are in eaxPLC, how the PLC enforces external access (none, read, read-write) and write ranges on every outside path, how forces and CONSTANTs fit in, and why access is signed with the program while descriptions are not.

Product: eaxPLC · Type: Explanation · Editions: Free, Pro
Source: https://eaxware.com/docs/eaxplc/explanation/data-model/
Verified against commit 9828d73.

An eaxPLC project declares its data once and uses it everywhere. Global variables live in **global variable lists**, user types in **data types**, and the **tag database** in the Studio shows every declared variable in one grid, with its external access, write range, unit and description.

This page explains the pieces and the rules the PLC enforces. For the exact syntax see [ST language: phase 3 additions](/docs/eaxplc/reference/st-language-phase-3/). Everything here is in every edition (eaxPLC Free, Standard and Performance); only the new cross-reference checks are in Standard and Performance.

## The kinds of POU

A project holds five kinds of POU. The two new kinds for data and the new FUNCTION kind are Structured Text only.

| Kind | Holds | Tree group |
|---|---|---|
| PRG | a PROGRAM, in ST or ladder | Programs (PRG) |
| FB | a FUNCTION_BLOCK, in ST or ladder | Function Blocks (FB) |
| FUN | one `FUNCTION`, named like the POU | Functions (FUN) |
| GVL | one or more `VAR_GLOBAL` blocks, nothing else | Global variables (GVL) |
| DUT | one `TYPE`, named like the POU | Data types (DUT) |

A project that uses none of this behaves byte for byte as before: same linked text, same program hash, same storage. The project file format changes (to format 2) only when you add the first FUN, GVL or DUT, or change a project compile setting.

## Global variables

A global is declared once, in a global variable list, and every POU can use it by name. A POU looks a name up in its own declarations first, then among the globals. `VAR_EXTERNAL` is optional; when you write it, its type must equal the global's, and `VAR_EXTERNAL CONSTANT` makes the global read-only inside that POU.

- **Names are unique.** Two globals with the same name (in any list) are an error. A PROGRAM variable named like a global is an error too (*Speed is a global variable (GVL_Line): rename the local or use the global*), because both would share one place in the process image. Inside a FUNCTION_BLOCK or a FUNCTION, a local may hide a global, with a warning: a reusable block must not stop compiling because a project adds a global.
- **Same place as the main program's variables.** A global has the same storage key as a variable of the main program with that name. Moving a main-program variable into a list (**Promote to global**) keeps its storage, its live value and its UNS path, so eaxScada tags bound to it keep working.
- **Initialised before any task.** The PLC initialises the globals in a set-level step that runs first in the program's first cycle, before inputs reach any task. A task program that reads a global in cycle 1 sees its initial value.
- **Located globals.** A global may have a direct address (`AT %QX0.1`), like a program variable.

## Data types

A data type POU holds one `TYPE`:

| Form | Example | Stored as |
|---|---|---|
| Structure | `TYPE ST_Recipe : STRUCT Temp_SP : REAL; Time_s : DINT := 600; END_STRUCT END_TYPE` | its members, each naturally aligned (at most 8 bytes) |
| Union | `TYPE U_Word : UNION AsWord : WORD; AsBytes : ARRAY[0..1] OF BYTE; END_UNION END_TYPE` | every member at offset 0; size of the largest |
| Enumeration | `TYPE E_State : (Idle, Run := 10, Fault) DINT; END_TYPE` | its base type (default `INT`); values count up from the previous one |
| Subrange | `TYPE T_Speed : INT(0..3000); END_TYPE` | its base type |
| Alias type | `TYPE T_Level : REAL; END_TYPE` | the type it names |

A type may use one declared later: the compiler collects every type name first. A type that holds itself by value (`A` holds `B` holds `A`) is an error naming the cycle.

- **Enumerations** compare, take part in `CASE`, and convert to and from an integer with `E_STATE_TO_INT` and `INT_TO_E_STATE`. Comparing two different enumerations, or assigning an integer without a conversion, is an error. A value is written `E_State.Run`, or `Run` when only one enumeration declares it.
- **Subranges.** A constant out of range is a compile error. Any other store into a subrange variable is checked at run time. By default the value is **clamped** to the bound and counted (the live values `system/RangeClamps` and `system/RangeClamps/`, and a diagnostic event at most every 10 seconds); the PLC never stops for it. The project setting `subrange_violation := 'fault'` faults the task instead. See [Set the project compile settings](/docs/eaxplc/how-to/set-the-project-compile-settings/).

## Aliases

An alias gives a second, symbolic name to a variable, one member of a structure or block, one array element, or one bit of an integer:

```text
PumpRun AT Motors[3].Run : BOOL;
Ready   AT Status.3      : BOOL;   (* bit 3 of Status *)
```

An alias has no storage and no initial value of its own: it reads and writes its target's storage. It is declared in a `VAR_GLOBAL` block or in a PROGRAM's `VAR`, has exactly its target's type (a bit is `BOOL`), and its indexes are constants. An alias of an alias is allowed up to four deep. The cross-reference lists each use of the alias under its own name with the target's storage, so the AI guard's storage rule also covers writes made through an alias.

## FUNCTION and VAR_IN_OUT

A `FUNCTION` returns one value and is called in expressions, with formal (`Scale(IN := x, LO := 0.0, HI := 100.0)`) or positional arguments. You set the result by assigning to the function's name. Its locals do not persist: every call starts from their initial values. A FUNCTION cannot call itself, directly or through others, and declares no function block instances.

`VAR_IN_OUT` parameters (in FUNCTIONs and FUNCTION_BLOCKs) are **copied in and copied out**: the actual is copied into the parameter before the body runs and back after it. The actual must be a variable of exactly the parameter's type: no expression, no CONSTANT, no bit. A parameter is at most 4096 bytes; for more, pass a global. One consequence of copying: if the body also uses the actual's global directly by name during the call, it sees the value from before the call, and the copy back overwrites its own write. The compiler warns about that case.

## External access

Every global and program variable has an **external access** that the PLC enforces against everything outside the program:

| Access | From outside |
|---|---|
| **None** | Invisible and unwritable: not in the registry, so not published on UNS, not browsable in OPC UA, not in `/api/registry`. Every write refused, never forced. |
| **Read** | Published and readable. Every external write refused. Forcing allowed. |
| **Read-write** | Readable and writable, within the write range. UNS and OPC UA still need the server's writable patterns to allow the name (the patterns stay an outer limit). |

You set it with an attribute in the declaration, `{attribute 'access' := 'read'}`, or in the tag database's **External access** column. Engineers in the Studio still see every variable, whatever its access: access controls clients outside the program, not the people who program it.

**Defaults.** A declaration without an access attribute is **read-write**, so a project written before this release behaves as it did. Variables you create in the Studio (Add POU, the tag database's **Add**, a CSV import) get an explicit `read`: read-only from outside until you allow more.

**Write range.** `{attribute 'write_range' := '0.0..120.0'}` bounds every external write of a numeric variable. A subrange type narrows it further. A value outside is refused (`WRITE_OUT_OF_RANGE`). An enumeration accepts only its own values from outside, by number or by name.

**Members.** A member of a structure, union or function block can carry its own `access` and `write_range` attributes; they apply to that member in every instance. A member's access can only narrow the access of the variable that holds it. A member without its own write range takes the nearest enclosing one (for example a `write_range` on an array of values bounds every element).

**Writes by path.** Outside clients can write and force one elementary member or array element by its path: `Recipes[2].Temp_SP`, `GVL_Line.Recipes[3].Temp_SP`, `Line2.Valves[3].Cmd` over `/api/write` and `/api/force` (HTTP and NATS); `Recipes/2/Temp_SP` over UNS; OPC UA lists the member paths as nodes. Every check applies to the leaf: the access narrowed through each member on the way, CONSTANT, the subrange, the enumeration's values, and the member's own write range (else the enclosing one). Only an elementary leaf (BOOL, an integer, an enumeration, REAL, LREAL) is written; a path to a structure or an array is refused (`400`), and so is an index that is not a constant or is outside the bounds.

**Function block instances.** Of a function block instance, only its `VAR_INPUT`s can be written or forced from outside, by path or by symbol, on every path. Its outputs and internal variables are published read-only: a write by path answers `400` (*... is not a VAR_INPUT of ...: only a function block's inputs are written or forced from outside by path*), UNS `WRITE_ACCESS_DENIED`, OPC UA `BadNotWritable`, each audited. Writes by direct address keep the storage rules below.

**Bits.** A bit alias (`Ready AT Status.3 : BOOL`) of an integer that has a write range is read-only from outside: setting one bit could take the integer out of its range.

**Aliases.** An alias's effective access is the narrower of its own and its target's: an alias narrows access, never widens it. An alias's own narrower access applies **to the alias's name only**. If `Oven2_SP AT Recipes[2].Temp_SP : REAL` is declared with access `read`, writes by the name `Oven2_SP` are refused, while `Recipes` keeps its own access for writes by its name or by address.

### Where it is enforced

One check in the runtime covers every path into the process image, always against the program that is running now (during an online test, the test program's access applies from its first cycle; an untest puts the accepted program's back at once):

**Diagram: One check for every outside write** (data flow)

A write from outside the program, by name, member path or direct address, on any path, passes the same four checks against the program that runs: the storage it hits is not a constant, not an input a fieldbus or MQTT source drives, belongs to read-write variables, and the value is within the write range. A failed check refuses the write, nothing is written and the refusal is audited. A write that passes is queued with the program version and written into the process image at the next cycle boundary.

**Parts**

- **Outside write** (external system): /api/write, /api/force (HTTP, NATS), OPC UA, UNS, Modbus TCP
- **Not a constant** (check or decision)
- **Not a driven input** (check or decision): fieldbus or MQTT
- **Access read-write** (check or decision): narrowed by members
- **Within its range** (check or decision): or the subrange
- **Refused** (outcome): nothing written; audited
- **Write queue** (data store): tagged with the program version
- **Process image** (data store): next cycle boundary

**Connections**

- **Outside write → Not a constant** (next step)
- **Not a constant → Not a driven input** (next step): yes
- **Not a driven input → Access read-write** (next step): yes
- **Access read-write → Within its range** (next step): yes
- **Within its range → Write queue** (next step): yes
- **Not a constant → Refused** (refusal): CONSTANT_READ_ONLY. Also a force onto a constant's storage.
- **Not a driven input → Refused** (refusal): IO_INPUT_DRIVEN
- **Access read-write → Refused** (refusal): WRITE_ACCESS_DENIED. Access none or read. A force is refused only for access none (FORCE_ACCESS_DENIED): access read may be forced.
- **Within its range → Refused** (refusal): WRITE_OUT_OF_RANGE
- **Write queue → Process image** (command to equipment): applied. Only while the program version the write was checked against still runs; after a deploy or an online-edit switch it is dropped (WRITE_STALE_PROGRAM).

The checks look at the storage the write hits, so a direct address cannot reach a protected variable.

| Path | Refusal |
|---|---|
| `POST /api/write` by name or member path (HTTP and the NATS API) | `403 WRITE_ACCESS_DENIED` for access none or read; `400 WRITE_OUT_OF_RANGE` outside the write range; `409 CONSTANT_READ_ONLY` for a constant |
| `POST /api/write` by direct address (`%MW40`) | the same codes when the written bytes overlap the storage of any protected variable or member; the answer names it |
| `POST /api/force` | `403 FORCE_ACCESS_DENIED` for access none (by name or by overlap); `409 CONSTANT_READ_ONLY` for a constant; access read may be forced |
| OPC UA | a variable with access none is not in the address space; a write needs the `plc.write` right (`BadUserAccessDenied` otherwise), and is refused with `BadNotWritable` (access read, constant) or `BadOutOfRange` |
| UNS commands | access none is not published; access read and constants answer an error |
| Modbus TCP server | a write over protected storage, or out of the range of a subrange or enumeration member or of an element of a range-limited array, is refused with a Modbus exception and audited under the client's address |

The direct-address check matters: variables without an `AT` address live in the `%M` area, so before this release `%MW<n>` could reach any of them. Now a write by address is checked against the storage it hits, not only the name it gives.

Refused writes are audited (`IO_WRITE` / `WRITE_DENIED`, or `TAG_WRITE` / `WRITE_REFUSED` for UNS, OPC UA and Modbus), refused forces as `FORCE_DENIED`.

### Forces and access

Forcing is an engineer's commissioning right (`plc.force`), not an external client's. So a variable with access **read** can be forced; access **none** and CONSTANTs cannot. When a deploy makes a forced location access none, the deploy releases the force (`FORCE_RELEASED`, *deploy vN made X inaccessible from outside (access none): it is never forced*). An online test that would do the same is refused with `forced_symbol_changes`: unforce first.

### CONSTANTs

A `CONSTANT` (global, program or block member) is always **read** from outside, whatever its access attribute says, and is never forced: no outside path can change a value the logic relies on. A constant with access `none` stays none. See [Constants, outside writes and forces](/docs/eaxplc/reference/constants-writes-and-forces/).

## RETAIN is not persistent yet

`RETAIN` (and `VAR RETAIN`) is accepted and shown in the tag database, but **nothing is written to persistent storage**. A retain variable keeps its value across deploys and online edits, like every variable both versions share. A cold reset or a power cycle resets it to its initial value, like any other variable. The tag database says so: its Retain column reads *not persistent*. Do not rely on RETAIN to survive a restart of the PLC.

## Why access is signed and descriptions are not

What the PLC **enforces** is part of the declaration text: access, write range, initial value, CONSTANT and the address. That text is linked into the program, hashed and signed, so changing it needs a test or a deploy like any other logic change, with its e-signature and audit. No one can widen access on a running PLC without a signed change.

What people **read** lives beside the program, in a documentation file per POU: description, engineering unit, display format and notes. That file is never linked and never part of the program hash. A description change is a project revision under the POU's lock (audited `PROJECT_TAGDOC_SAVE`) and needs no deploy, no test and no signature. Otherwise every typo fix in a description would need an e-signed online edit.

The tag database marks the two kinds of column: initial value, external access and write range go to the POU's **draft**; unit, display and description save at once. See [Document variables without a deploy](/docs/eaxplc/how-to/document-variables/).

## Related

- [Create a global variable list and a structure](/docs/eaxplc/how-to/create-global-variables-and-structures/)
- [Set external access and write limits](/docs/eaxplc/how-to/set-external-access-and-write-limits/)
- [Online changes to data structures](/docs/eaxplc/explanation/online-changes-to-data-structures/)
- [ST language: phase 3 additions](/docs/eaxplc/reference/st-language-phase-3/)